HEATING AND COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x
TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT
= SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG F)
SUBCOOLING
= DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
DESCRIPTION
HEATING
COOLING
NOTES
Voltage
Compressor Amp
1
Suction Temperature
2
Suction Pressure
2a
Saturation Temperature
2b
Superheat
3
Discharge Temperature
4
Discharge Pressure
4a
Saturation Temperature
4b
Subcooling
5
Liquid Line Temperature
6
Source Water In Temperature
7
Source Water Out Temperature
Temperature Difference —
8
Source Water In Pressure
9
Source Water Out Pressure
9a
Pressure Drop
9b
Flow Rate (gpm)
10
Load Water In Temperature
11
Load Water Out Temperature
Temperature Difference —
12
Load Water In Pressure
13
Load Water Out Pressure
13a
Pressure Drop
13b
Flow Rate (gpm)
COMPRESSOR
DISCHARGE
SUCTION
HWG*
EXPANSION
VALVE
FILTER
DRIER
REVERSING
VALVE
HEATING POSITION
COOLING POSITION
1
COAX
CO
A
X
5
12
10
13
11
9
7
8
6
4
3
2
FP2:
HEATING
LIQUID
LINE
5
FP1:
COOLING
LIQUID
LINE
CONDENSER (HT G)
EVAPORAT OR (CLG)
CONDENSER (COOLING)
EVAPORATOR (HEATING)
WATER-TO-WATER UNITS
REFRIG FLOW - HEATING
REFRIG FLOW - COOLING
Source
Load
LEGEND
*Turn off HWG (hot water generator)
before troubleshooting.
CLG
—
Cooling
HTG
—
Heating
8733830974
Содержание Aquazone 50PSW025
Страница 15: ...15 Fig 9 Unit Size 122 1 Phase Complete C Deluxe D Control Package DWG No 50PSW120000 Rev 3 ...
Страница 17: ...17 Fig 11 Unit Sizes 122 1 Phase W2W Open Control Package DWG No 50PSW120001 Rev 4 ...
Страница 19: ...19 Fig 13 Unit Size 122 240 420 3 Phase Complete C Deluxe D Control Package DWG No 50PSW320000 Rev 3 ...
Страница 21: ...21 Fig 15 Unit Size 122 240 420 3 Phase W2W Open Control Package DWG No 50PSW320001 Rev 3 ...
Страница 36: ...36 Fig 22 W2W Open Control Board ...
Страница 37: ...37 Fig 23 Unit Protection Module UPM Sequence Of Operation ...