13
Step 6 —
Wire Field Power Supply
All field wiring must comply with local and national fire, safety
and electrical codes. Power to the unit must be within the
operating voltage range indicated on the unit’s nameplate. On
three phase units, phases must be balanced within 2%.
Properly sized fuse or HACR (heating, air-conditioning, and
refrigeration) circuit breakers must be installed for branch circuit
protection. See equipment rating plate for maximum size.
The unit is supplied with an opening for attaching conduit. Be
certain to connect the ground lead to the ground lug in the control
box. Connect the power leads as indicated on the unit wiring
diagram. See Table 4 and Fig. 8-16.
Table 4 —
50PSW Electrical Data
LEGEND
WARNING
To avoid possible injury or death due to electrical shock, open
the power supply disconnect switch and secure it in an open
position during installation. Install lockout tag.
CAUTION
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other types
of conductors. Failure to heed this warning could result in
equipment damage.
50PSW UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
COMPRESSOR
MCA
MAX FUSE
QTY
RLA
LRA
025
208/230-1-60
1
11.7
58.3
14.6
25
265-1-60
1
9.1
54.0
11.4
20
208/230-3-60
1
6.5
55.4
8.1
15
035
208/230-1-60
1
15.3
83.0
19.1
30
265-1-60
1
13.0
72.0
16.3
25
208/230-3-60
1
11.6
73.0
11.6
25
460-3-60
1
5.7
38.0
7.1
15
049
208/230-1-60
1
21.2
104.0
26.5
45
208/230-3-60
1
14.0
83.1
17.5
30
460-3-60
1
6.4
41.0
8.0
15
061
208/230-1-60
1
27.1
152.9
33.9
60
208/230-3-60
1
16.5
110.0
20.6
35
460-3-60
1
7.2
52.0
9.0
15
071
208/230-1-60
1
29.7
179.2
37.1
60
208/230-3-60
1
17.6
136.0
22.0
35
460-3-60
1
8.5
66.1
10.6
15
122
208/230-1-60
2
28.3
178.0
63.7
90
208/230-3-60
2
19.2
136.0
43.2
60
460-3-60
2
8.7
66.1
19.6
25
180
208/230-3-60
1
48.1
245.0
60.1
100
460-3-60
1
18.6
125.0
23.3
40
575-3-60
1
14.7
100.0
18.4
30
210
208/230-3-60
1
55.8
340.0
69.8
125
460-3-60
1
26.9
173.0
33.6
60
575-3-60
1
23.7
132.0
29.6
50
240
208/230-3-60
2
33.3
239.0
74.9
100
460-3-60
2
17.9
125.0
40.3
50
575-3-60
2
12.8
80.0
28.8
40
360
208/230-3-60
2
48.1
245.0
108.2
150
460-3-60
2
18.6
125.0
41.9
60
575-3-60
2
14.7
100.0
33.1
45
420
208/230-3-60
2
55.8
340.0
125.6
175
460-3-60
2
26.9
173.0
60.5
80
575-3-60
2
23.7
132.0
53.3
70
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
Содержание Aquazone 50PSW025
Страница 15: ...15 Fig 9 Unit Size 122 1 Phase Complete C Deluxe D Control Package DWG No 50PSW120000 Rev 3 ...
Страница 17: ...17 Fig 11 Unit Sizes 122 1 Phase W2W Open Control Package DWG No 50PSW120001 Rev 4 ...
Страница 19: ...19 Fig 13 Unit Size 122 240 420 3 Phase Complete C Deluxe D Control Package DWG No 50PSW320000 Rev 3 ...
Страница 21: ...21 Fig 15 Unit Size 122 240 420 3 Phase W2W Open Control Package DWG No 50PSW320001 Rev 3 ...
Страница 36: ...36 Fig 22 W2W Open Control Board ...
Страница 37: ...37 Fig 23 Unit Protection Module UPM Sequence Of Operation ...