APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
LEGEND
SCREEN NAME
POINT NAME
PASSWORD
LEVEL
EDITABLE
RANGE
DEFAULT
NOTES
Configuration
Unit
Configuration
Fan Mode
Admin Password
level access only
X
Auto/Continuous/
Always On
Continuous
Auto= Intermittant operation during both
occupied and unoccupied periods/
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Fan On Delay
X
0 - 30 sec
10 sec
Defines the delay time before the fan begins
to operate after heating or cooling is started
Fan Off Delay
X
0 - 180 sec
45 sec
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
Heating Enable
X
Disable/Enable
Enable
Provides capability to manually
disable heating operation
Cooling Enable
X
Disable/Enable
Enable
Provides capability to manually
disable cooling operation
Minimum SAT in
Cooling
X
40 - 60
F
50
F
Defines the minimum acceptable operating
temperature for the Supply Air
Maximum SAT in
Heating
X
80 - 140 F
110 F
Defines the maximum acceptable operating
temperature for the Supply Air
Damper Ventilation
Position
X
0 - 100%
100%
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
damper type = DCV
DCV Maximum Vent
Position
X
0 - 100%
100%
Usually set at 100% - Used to limit maximum
damper opening in DCV mode
Filter Alarm Timer
X
0 - 9999 hrs
0 hrs
Disables Filter Alarm if set to 0
Pushbutton Override
X
Disable/Enable
Enable
Enables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
X
Disable/Enable
Enable
Enables Set Point adjustment capability
on Rnet Sensor
Lockout Cooling if
OAT <
X
-65 - 80 F
-65 F
Cooling is locked out when OAT is less than
configured value and OAT is actively being
broadcast
Lockout Heating if
OAT >
X
35 - 150 F
150 F
Heating is locked out when OAT is greater
than configured value and OAT is actively
being broadcast
Power Fail Restart
Delay
X
0 - 600 sec
60 sec
Delay before equipment starts
Occupancy Schedules
X
Disable/Enable
Enable
Enables unit occupied
Set Point Separation
X
2 - 9 F
4 F
Used to enforce minimum
set point separation
Configuration
Service
Test
Test Mode
Admin Password
level access only
X
Disable/Enable
Disable
Used to enable test mode. Will automatically
reset to disable after 1 hour
Fan Test
X
Disable/Enable
Disable
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Fan Speed
Off/Low Speed/Medium
Speed/High Speed/On
Displays current fan operation
Compressor Test
X
Disable/Enable
Disable
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
step. Resets to disable on completion.
Dehumidification Test
X
Disable/Enable
Disable
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Testing Compressor
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
Displays compressor test mode
Aux Heating Test
X
Disable/Enable
Disable
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
H
2
O Economizer Test
X
Disable/Enable
Disable
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
Preposition OA
Damper
X
Disable/Enable
Disable
Used to preposition OA damper
actuator to set proper preload
Open Vent
Damper 100%
X
Disable/Enable
Disable
Used to test OA damper operation
SAT
F
Displays SAT
LCWT
F
Displays Leaving Condenser
Water Temperature
BAS —
Building Automation System
DCV —
Demand Controlled Ventilation
IAQ
—
Indoor Air Quality
OAT
—
Outdoor Air Temperature
RH
—
Relative Humidity
SAT
—
Supply Air Temperature
SPT
—
Space Temperature
TPI
—
Third Party Integration