13
Fig. 12 - Manual changeover with Deluxe D controller wiring
FP2
CAP
PB
DELUXE D
CONTROL
BR 2
(HI)
UMT
PBS
OS
GROUND
LOG
TRANSFORMER
CR
BR 1
(LO)
BR2
(HI)
BR1
(LO)
S
JW1
LP
TEST
PINS
JW2
FP2
JW3
FP1 LOW
LOW
N.O.
ACC1
FUNCTIONS
ACC2
FUNCTIONS
H: HI FAN/DEHUMID
NOT USED
OFFON
S2
DIP SWITCH PACKAGE
S1
DIP SWITCH PACKAGE
OFFON
PM: DISABLE/ENABLE
UNIT STAGE: 2/1
T’STAT: HEAT COOL/HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS: ENABLE/DISABLE
BOILERLESS: 40
°
F/50
°
F
SEE
NOTE 4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Y1
O/W2
G
R
C
AL1
W1
AL2
A
P3
R
C
ALARM
RELAY
SEE
NOTE 6
SEE
NOTE 7
NSB
ESD
OVR
H
P2
C
R
Y2
P1
R
R
COM
NC2
NO2
COM
NC1
NO1
RELAY
ACC1
RELAY
ACC2
1
2
3
4
5
6
7
8
COM2
COM1
R C S
C
JW4
AL2
DRY
RED
RED
2
3
2A
ORG
3A
RED GRY
YEL
ORG
YEL
UMT
2
3
PBS
1A
1B
YEL YEL YEL
ORG
DM
BRN
BRN
RED
TIME CLOCK
CLOSED-UNOCCUPIED
BRN
GRY
YEL
WHT
WV
WHT
RED
OS
NLL
GRY
GRY
PBS
RED
5
6
5A
6A
RED
7
7A
RED
GRY
P7
P6
CCG
24V
DC
EH1
EH2
BRN
CC
YEL
CR
1
COMPR
RELAY
0
FAN
ENABLE
RELAY
STATUS
TEST
FAULT
G
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
1
2
RV RELAY
3
4
5
7
9
10
HP
LOC
FP1
RV
CO
HP
LOC
FP1
BRN
ORG
YEL
VIO
SEE
NOTE 4
FP2
CO
Y
R
GRY
COM
NO
NC
COM
NO
FAN
SPEED
RELAY
GRY
RED
RED
12
8
6
NOT USED
RVS
BLU
BRN
VIO
BRN
BRN
YEL
YEL
RED
GRY
POWER SUPPLY
REFER TO DATA
PLATE USE
COPPER
CONDUCTORS
ONLY.
SEE NOTE 2
PB
E (GND)
NEUTRAL
220/240-1-50
L
1
2
3
4
5
6
G/Y
G/Y
RED
BLK
CB
BLK
RED
(220V)
ORG (240V)
24V
YEL
BLU
GROUND
BLK
RED
BLK
(GROUND TO CONTROL DOOR)
G/Y
G/Y
GND LUG
GROUND
1
2
BRN
YEL
F
C
CAP
BLU
RED
COMPR. S
C
R
B (HIGH)
A (LOW)
TRANS
RED
BLK
BR 2 (HI)
COM NO
BR 1 (LO)
COM NO
CR
BLK
2
4
1
BM
Legend
AL
Alarm relay contacts
BM
Blower motor
BR
Blower relay
CAP
Capacitor
CB
Circuit breaker
CO
Sensor, condensate overflow
CR
Compressor relay
DM
Damper motor
FP1
Sensor, water coil freeze protection
FP2
Sensor, air coil freeze protection
GND
Ground
HP
High pressure switch
JW1
Jumper wire for alarm
LOC
Loss of charge pressure switch
NLL
Night low limit switch
OS
Override switch
PB
Power terminal block
PBS
Push button switch
PM
Performance Monitor
RVS
Reversing valve solenoid
TRANS
Transformer optional wiring
UMT
Unit mounted thermostat
WV
Water valve
Field line voltage wiring
Field low voltage wiring
Printed circuit trace
Option low voltage wiring
Relay/contactor coil
Solenoid coil
Thermistor
Circuit breaker
Relay contacts - NO
Temperature switch
High pressure switch
Low pressure switch
Ground
Wire nut
Mate-N-Lock
* Optional wiring
Notes:
1.
Compressor and blower motor thermally protected internally.
2.
All wiring to the unit must comply with local codes.
3.
Transformer is wired to 240 V (ORG) lead for 240-1-50 units. For 220-1-50
switch ORG and RED leads at PB(1) and insulate ORG lead. Transformer is
energy limiting or may have circuit breaker.
4.
FP1 thermistor provides freeze protection for water. When using anti-freeze
solutions, cut JW3 jumper.
5.
Typical unit-mounted thermostat wiring shown.
6.
24-V alarm signal shown. For dry alarm contact, cut AL2 DRY
(JW4) jumper, and dry contact will be available between AL1 and AL2.
7.
Transformer secondary ground via Deluxe D board stand-offs and screws to
control box. (Ground available from top two stand-offs as shown.)
>>
Push button switch attributes
X = closed
O = open
Terminals
1
2
3
4
5
6
7
8
1A
1B
2A
3A
4A
5A
6A
7A
8A
Stop
X
O
O
O
O
O
O
O
O
Fan only
X
O
O
O
O
X
O
O
O
Low cool
O
X
X
O
O
O
X
O
O
High cool
O
X
X
O
O
O
O
X
O
Low heat
X
O
O
X
X
O
X
O
O
High heat
X
O
O
X
X
O
O
X
X
Blower motor wiring
Unit size
Pole A Pole B
007
5
3
009
5
4
012
4
3
015
4
3
019
4
3
Power supply
Refer to data plate
Use copper
conductors only
See note 2
Earth (GRD)
Ground
Ground
Gnd lug
(Ground to control door)
Low
High
Compr.
Neutral
220/240-1-50
Deluxe D
micro-processor
control logic
Fan enable
relay
Alarm
relay
See
note 6
Fan
speed
relay
Time clock
Closed unoccupied
Status
Test
Fault
Test
pins
See
note 4
RV relay
Low
Off On
See
note 4
Not used
Low
PM : Disable/enable
Unit stage: 2/1
T-stat: heat cool/heat pump
RVon 8/RV on 0
Dehumid/normal
Not used
Boilerless: Enable/disable
Boilerless: 4.4
°
C/10
°
C
Relay
Relay
Acc1
Functions
Acc2
Functions
H:Hi fan/dehumid
Not used
Compr.
relay
Transformer
Dip switch package
Dip switch package
Ground
log
Deluxe D
control
See
note 7