Table 3A — Electrical Data — 50HQP072-120 Standard Units
Table 3B — Electrical Data — 50HQP072-120 Dual Point Power Units
LEGEND
*Time-delay fuse or HACR circuit breaker.
Table 4 — Low Voltage VA Ratings
* Standard transformer is 75 VA.
UNIT
50HQP
VOLTAGE
CODE
VOLTAGE
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE
QTY
RLA
LRA
072
9
380/420-3-50
360/440
A,B,C
2
5.4
38.0
1.8
12.6
13.9
15
096
9
380/420-3-50
360/440
A,B,C
2
6.1
43.0
3.4
15.6
17.1
20
120
9
380/420-3-50
360/440
A,B,C
2
7.8
51.5
4.9
20.5
22.5
30
UNIT
50HQP
VOLTAGE
CODE
VOLTAGE
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR
EMERGENCY
POWER SUPPLY
QTY
RLA
LRA
Total
Comp
FLA
Comp
MCA
Comp
Max
Fuse
Fan
Motor
FLA
Fan
MCA
FAN
MAX
FUSE
072
9
380/420-3-50
360/440
A,B,C
2
5.4
38.0
10.8
12.2
15
1.8
2.3
15
096
9
380/420-3-50
360/440
A,B,C
2
6.1
43.0
12.2
13.7
15
3.4
4.3
15
120
9
380/420-3-50
360/440
A,B,C
2
7.8
51.5
15.6
17.6
25
4.9
6.1
15
FLA
—
Full Load Amps
HACR
—
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
RLA
—
Rated Load Amps
COMPONENTS IN UNIT
VA
Typical Blower Contactor
6 - 9
Typical Reversing Valve Solenoid (2)
8 - 12
30A Compressor Contactor (2)
12 - 18
Complete C Board (2)
10 - 18
Deluxe D Board (2)
16 - 24
Remaining VA for Accessories*
Units with Complete C
Units with Deluxe D
18 - 39
12 - 33
NOTE: Low voltage connector may be removed for easy installation.
Fig. 16 — Low Voltage Field Wiring
Complete C 2
Complete C 1
POWER
BLOCK
Fig. 17 — Line Voltage Wiring