Remote Controller
GB - 4
wiring diagrams
Single-phase unit with accessory remote control
30aw
troubleshooting
1
2 3
6
7
8
6
7
8
1
2 3
Unit electrical panel
Electronic board connectors
Remote control
Symptom
Possible cause
action required
Solution
LED fault
1) Miswiring of the 12 volt power to
remote controller control.
1) Verify that 30AW unit is connected
to the proper terminals of the
controller.
Reference Installation cable para-
graph for correct connections.
After disconnecting the power, correct
the wiring problem and restart the
power.
2) Power not online
1) Check that the unit main power is
connected.
After verifying the wiring to the remote
controller, restart the unit power.
3) No 12 volt supply to terminal block.
1) Check the 12 connection on the
terminal block in the 30AW unit.
After disconnecting the power, correct
the wiring problem and restart the
power.
12 volts applied to remote controller
at the correct terminals but unit does
not operate
1) The remote controller is damaged.
Change the remote controller and
restart the power.