1
30AWH
Air / Water Cycle Heat Pump
This air conditioner adopts the new HFC refrigerant
•
(R410A) which does not destroy ozone layer.
R-410A refrigerant operates at 50%-70% higher pressures
•
than R-22. Be sure that servicing equipment and
replacement components are designed to operate with
R-410A.
R-410A refrigerant cylinders have a dip tube which allows
•
liquid to flow out with the cylinder in a vertical position
with the valve at the top.
R-410A systems should be charged with liquid
•
refrigerant. Use a commercial type metering device in the
manifold hose in order to vaporize the liquid refrigerant
before it enters in the unit.
As for other HFC, R-410A refrigerant is only compatible
•
with oils recommended by the compressor manufacturer.
A vacuum pump is not enough to remove moisture from
•
oil.
Oils absorb moisture rapidly. Do not expose oil to
•
atmosphere.
Never open system to atmosphere while it is under
•
vacuum.
When the system must be opened for service, break
•
vacuum with dry nitrogen.
Do not vent R-410A into the atmosphere.
•
Use this unit only for factory approved applications.
The capacity and unit code are stated on the nameplate
data.
R-410A - General info
SITING THE UNIT
INSTALLATION
R-410A - General info ..........................................................
1
Safety procedures ................................................................
2
Dimensions and clearances...............................................
4
Technical data .......................................................................
4
Installation .............................................................................
5
Water connections ...............................................................
6
Electrical connections .........................................................
8
Connection of Auxiliary Accessories ..............................
9
System test .............................................................................
12
Unit protection devices ......................................................
15
Maintenace ............................................................................
15
Contents
Page
WATER CONNECTIONS
ELECTRICAL CONNECTIONS
CONTROL WIRING (Optional)
POWER WIRING
FILLING THE SYSTEM
FLUSHING WATER AND AIR
CHECKING FOR WATER LEAKS
CONFIGURING AND CHECKING THE SYSTEM
CAUTION:
•
Do not leave system open to atmosphere any longer
than minimum required for installation.
• Oil in the compressor is extremely susceptible to
moisture absorption.
MODELS WITH HYDRONIC
MODULE
MODELS WITHOUT
HYDRONIC MODULE
30AWH004HB
30AWH004XB
30AWH006HB
30AWH006XB
30AWH008HB
30AWH008XB
30AWH012HB
30AWH012XB
30AWH015HB
30AWH015XB
English
Содержание AquaSnap Plus 30AWH004HB
Страница 1: ...AquaSNAPPLUSreversibleINVERTER 30AW InstallationManual ...
Страница 4: ...III 30AWH 10 11 1 2 4 6 7 4 3 6 5 5 2 4 1 7 3 4 9 1 2 3 1 2 3 4 4 1 2 3 4 4 1 2 3 ...
Страница 5: ...IV 30AWH 12 1 2 3 3 10 4 6 1 5 7 8 9 11 13 1 1 2 3 3 4 6 5 7 8 9 ...
Страница 7: ...VI 30AWH 16 A C B ...
Страница 159: ...151 30AWH ...