30AWH
System test
SW803
ON
2
3
4
1
SW803
ON
2
3
4
1
Error contents
Normal
Discharge temp. sensor (TD) error
Heat exchanger temp. sensor (TE) error
Heat exchanger temp. sensor (TL) error
Outside temp. sensor (TO) error
Suction temp. sensor (TS) error
Heat sink temp. sensor (TH) error
Heat exchanger sensor (TE, TS) miswiring
EEPROM error
Compressor break down
Compressor lock
Current detection circuit error
Case thermostat operation
Model unset
Communication error between MCU
Other error (Compressor disorder, etc.)
Discharge temp. error
Power supply error
Heat sink overheat error
Gas leak detection
4-way valve reverse error
High pressure protective operation
Fan system error
Driving element short-circuit
Position detection circuit erro
Present
error
Go off
Go on
Flash
Latest
error
(Legend)
( Yellow)
( Yellow)
( Yellow)
( Yellow)
( Yellow)
( Green)
The error which is generating at present and the latest
error (Latest error information including present) can be
confirmed by lighting LED D800 toD804 on the outdoor
control P.C. board.
a) When all DIP switch SW803 are OFF, the status of error
which is generating at present is displayed.
b) <1> only of DIP switch SW803 is turned on, the error
which generated before (Latest error information including
present) is displayed. )
c) If there is an error, any of LED D800 to D804 goes on.
(Display 1)
d) When pushing the pushdown button switch SW800 for
approx. 1 second, the display is exchanged. (Display 2)
e) When pushing SW800 again or after 2 minutes, the status
returns to that of Display 1
Display 1
(Initial display)
Display 2
(SW800 operation )
Inverter board alarm codes (only for 30AWH015_)
(Fig. 16)
English
Содержание AquaSnap Plus 30AWH004HB
Страница 1: ...AquaSNAPPLUSreversibleINVERTER 30AW InstallationManual ...
Страница 4: ...III 30AWH 10 11 1 2 4 6 7 4 3 6 5 5 2 4 1 7 3 4 9 1 2 3 1 2 3 4 4 1 2 3 4 4 1 2 3 ...
Страница 5: ...IV 30AWH 12 1 2 3 3 10 4 6 1 5 7 8 9 11 13 1 1 2 3 3 4 6 5 7 8 9 ...
Страница 7: ...VI 30AWH 16 A C B ...
Страница 159: ...151 30AWH ...