12
5.2 - Electrical data, hydronic module
30RQ
262
302
342
372
402
432
462
522
single and dual low-pressure pump
Shaft power
kW
2.2
3
3
4
4
4
5.5
5.5
Power input*
kW
2.7
3.6
3.6
4.6
4.6
4.6
6.3
6.3
Nominal current draw
A
4.5
6.0
6.0
7.6
7.6
7.6
10.3
10.3
Maximum current draw at 400 V**
A
4.7
6.4
6.4
8.2
8.2
8.2
11.2
11.2
single and dual high-pressure pump
Shaft power
kW
4
5.5
5.5
7.5
7.5
7.5
11
11
Power input*
kW
4.7
6.4
6.4
8.5
8.5
8.5
12.2
12.2
Nominal current draw
A
7.6
10.3
10.3
13.9
13.9
13.9
19.5
19.5
Maximum current draw at 400 V**
A
8.2
11.2
11.2
15.2
15.2
15.2
21.2
21.2
Note:
The water pump power input values are given for guidance only.
*
To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the electrical data table in section 5 to the pump
power input* in the table above.
** To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table in section 5 to
the pump current draw** in the table above.
5.3 - Compressor usage and electrical data
Compressor I Nom
I Max
I Max
lRa
Cosine
Circuit
262
302
342
372
402
432
462
522
(Un)
(Un-10%)
(Un)
Phi (max.)
sh240
30
40
44
215
0.86
a
-
3
-
4
-
-
4
-
B
-
-
-
-
-
3
-
-
sh300
38
51
56
260
0.86
a
2
-
3
-
4
4
-
4
B
2
2
2
2
2
-
4
4
legend
I Nom Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max Maximum operating current at 360 V, A
LRA Locked rotor current, A
5.4 - Electric power user reserve
There are only power reserves on the units without hydronic
modules. The reserve is the value corresponding to the high
pressure pump capacity (see information in the hydronic
module data table).
Control circuit power reserve:
The TC transformer with all possible options connected makes
1A available for 24 V, 50 Hz.
For the same TC transformer the 230 V, 50 Hz circuit with
connection ribbon only permits supply to the battery chargers
for portable computers, 0.8 A at 230 V maximum.
IMPORTANT: Only connect doubly-insulated class II
apparatus to these ribbons.