7. Install the bolts, and thread a nut finger-tight onto each bolt.
For couplings supplied with stainless steel hardware, apply
an anti-seize compound to the bolt threads. Make sure the
oval neck of each bolt seats properly in the bolt hole.
8. Tighten the nuts evenly by alternating sides until metal-to-
metal contact occurs at the bolt pads. Make sure the hous-
ings’ keys engage the grooves completely. It is important to
tighten the nuts evenly to prevent gasket pinching.
9. Visually inspect the bolt pads at each joint to ensure metal-
to-metal contact is achieved.
COMPRESSOR OIL SYSTEM
Each compressor/circuit has its own oil system which includes an
oil filter, oil solenoid, check valve, oil level switch, oil separator
heater, oil pressure transducer, and an oil shut-off valve. A typical
oil system is shown in Fig. 63 and 64. See Table 42 for required oil
quantity per circuit, initially included from the factory.
Table 42 — Unit Oil Quantities
Oil Charge
When additional oil or a complete charge is required it must
meet the following specifications:
• . .Manufacturer . . . . . . . . . Emkarate RL220XL
• Oil Type . . . . . . . . . . . . . Inhibited polyolester-based syn-
thetic compressor lubricant for
use with screw compressors.
• ISO Viscosity Grade . . . 220
Do not reuse drained oil or any oil that has been exposed to the
atmosphere.
Oil is available in the following quantities from your local
Carrier representative:
If unsure if there is low oil charge in the system, follow the
steps below:
1. If the unit shuts off repeatedly from a low oil level alert, it
may be an indication of inadequate oil charge: however, it
could also indicate the oil is not being reclaimed from the
low-side of the system.
2. Run the circuit at full load for 1
1
/
2
hours.
NOTE: An adequate load must be available.
3. After running the unit for 1
1
/
2
hours at full load, stop the unit.
Check the oil level in the oil separator sight glass. An oil lev-
el should be visible in the upper sight glass. If level is not
visible, the unit is low on oil charge.
4. Add oil until the oil is at the center of the upper sight glass.
Make sure not to add oil beyond this level as excess oil will
be carried out of the oil separator into the system and might
lead to system instabilities at certain conditions.
5. The factory oil charging stations are programed to add pre-
cise amount of oil to the oil separator and if the oil level
while inspection shows higher than middle of the top sight
glass then it could be due to refrigerant mixed in it. Do not
remove any oil.
Add oil to the oil separator using the
1
/
4
-in. access fitting on
the side of the separator.
NOTE: To facilitate the oil charging process, ensure that
the unit is not running when adding oil. The system is un-
der pressure even when the unit is not running, so it is nec-
essary to use a suitable pump to add oil to the system. Us-
ing a suitable pump, add
1
/
2
gal (1.9 L) of oil to the system.
Continue adding oil in
1
/
2
gal (1.9 L) increments until the
problem is resolved, up to a maximum of 1.5 gal (5.7 L).
6. Larger units (350 Circuit A and 400-500 ton units) will not
have sight glasses for reference. The same procedure should
be followed. To check for oil in the evaporator, determine the
approach, LWT - SST. This should be less than 10°F for
fresh water for a circuit running in steady state condition at
full load. If over this amount, there is still oil logged in the
evaporator. Continue to run at full load to remove it. If the
approach is low (less than 6) and there are low oil level
alarms, add 0.5 gal. to the circuit.
Oil Filter Maintenance
Each circuit has one oil filter bolted externally to the compres-
sor. Oil line pressure drop is monitored by the control. Oil line
pressure drop is calculated by subtracting oil pressure (OPT)
from discharge pressure (DPT). If the oil line pressure drop ex-
ceeds 30 psig (206.8 kPa) for 5 minutes the control will gener-
ate a High Oil Filter Pressure Drop alert. The High Oil Filter
Pressure Drop alert will not shut down the compressor, but in-
stead indicates that the oil filter is dirty. If oil pressure line
losses exceed 50 psig (344.7 kPa) for more than 30 seconds
then the control will shut down the circuit on Maximum Oil
Filter Differential Pressure Failure.
Replacing the Oil Filter
Close the oil service valves on either side of filter by removing
the cap and closing the valve. One is connected to the oil filter
and the other is mounted on the compressor. Connect a
charging hose to the ¼-in. access fitting port located between
the filter and compressor. Bleed off the oil located in this sec-
tion. A quart of oil is typically removed during this process.
Unscrew the nuts on either side of the filter. Remove the filter
and install the new one. Make sure to remove the plastic caps
from the new filter before installation. Take care not to lose or
damage the new O-rings on the new filter. Draw a vacuum at
the service port. Remove the charging hose and open the oil
service valves. Replace caps on access port and service valves.
Check both fittings for leaks.
Evaporator Service
The 30XV units use flooded style evaporators.
ISOLATION VALVE
The isolation valve is a factory-installed option for 30XV units.
The option includes a butterfly-style suction service valve on the
suction lines, and manual ball valves on discharge, evaporator
inlet and economizer lines. The butterfly valve is connected to
the suction line by Victaulic connections. See Fig. 65 and 66 for
details on the butterfly suction service valve operation. The
valve locks into place when fully opened or fully closed. See
Table 43 for compressor usage.
Table 43 — Compressor Usage
30XV UNIT SIZE
OIL CHARGE (gal, [liters])
Circuit A
Circuit B
140-325
5.5 [20.8]
5.5 [20.8
350
7.5 [28.4]
5.5 [20.8
400-500
7.5 [28.4]
7.5 [28.4]
QUANTITY
TOTALINE PART NO.
1 Quart
P903-2325
1 Gallon
P903-2301
5 Gallon
P903-2305
CAUTION
Compressor oil is pressurized. Use proper safety precautions
when relieving pressure.
30XV UNIT SIZE
COMPRESSOR MODELS
CKT A
CKT B
140 - 200
06ZCE1
06ZCE1
225
06ZFC2
06ZCE1
250 - 325
06ZFC2
06ZFC2
350
06ZJG3
06ZFC2
400-500
06ZJG3
06ZJG3
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...