55
OPERATION
Sequence of Operation
With a command to start the chiller, the evaporator pump will
start. After verifying water flow, the control will monitor the
entering and leaving water temperature. If the need for me-
chanical cooling is determined, the control decides which cir-
cuit and compressor to start. The control will start the required
compressor completely unloaded and de-energize the oil sep-
arator heater (if already energized). The control will continue
to load this circuit by increasing the VFD frequency to satisfy
cooling requirements. Once fully loaded, the control will start
the second circuit to satisfy load as required. Shutdown of each
circuit under normal conditions occurs in the opposite se-
quence to loading. Once a circuit is fully unloaded the com-
pressor is shut off and the EXV will close completely.
ACTUATED BALL VALVE (ABV)
For chillers equipped with this option (standard in most re-
gions), either one or two discharge ABVs are located in the dis-
charge line of each circuit of the unit. See Fig. 51 for a typical
ABV assembly with enclosure. The ABV is a motorized ball
valve, which is used to close the discharge line to prevent re-
frigerant migrating from condenser to the evaporator when the
circuit is off. The valve will be opened before the compressor
is started and will normally close when pressure equalizes be-
tween suction and discharge lines.
The actuated ball valves are linked to the evaporator heater op-
eration in the controls. Evaporator Heater option (
Main Menu
Configuration Menu
Factory Parameters
Evaporator
Heater Installed = yes
) must be enabled for the actuated ball
valve to operate.
See Fig. 52 for a view of a fully open ball valve with the actua-
tor removed. The flat surface at the top of the valve shaft is
parallel to the discharge line. The ball valve motor mounting
plate should be perpendicular to the discharge line at all times.
If not, adjust it by loosening the set screw on the side of the
valve, reposition assembly and tighten set screw.
See Fig. 53 for a view of the ball valve motor mounting with a
fully open valve. The motor actuator arm should be at a coun-
terclockwise position, with the valve shaft in a parallel posi-
tion. If not in a parallel position, loosen the clamping screw
and push the disengagement button to rotate the actuator arm
until it stops. Retighten the clamping screw.
ABV Manual Operation
The ABV can be operated manually as a discharge service
valve by completing the following steps:
1. Remove the actuator cover.
2. With the compressor off hold down the Disengagement
3. Close the ABV by turning the shaft adapter by hand or with
a wrench so that the flats on the end of the shaft are perpen-
dicular to the discharge line.
4. Release the Push button.
5. Disconnect the control power cable to the ABV.
Dual Chiller Sequence of Operation
With a command to start the chiller, the master chiller determines
which chiller will become the lead chiller based on the configura-
tion of Lead Lag Select (
lead_sel
) and Lead/Lag Balance Delta
(
ll_bal_d
). The lead chiller is always started first and the lag
chiller is held at zero percent capacity by the master chiller forcing
the lag demand limit value to 0%. If Lead Pulldown Time
(
lead_pul
) has been configured, the lead chiller will continue to
operate alone for that specified time. After the Lead Pulldown
Time timer has elapsed and when the lead chiller is fully loaded,
either all available compression is on or at the master demand lim-
it value, then the lag start timer (
lstr_tim
) is initiated.
Fig. 51 — Typical ABV Assembly with Enclosure
Fig. 52 — Fully Open Ball Valve
with Actuator Removed
Fig. 53 — Ball Valve Motor
BA
S
E PLATE
VALVE MOTOR
VALVE MOTOR COVER
a30-4236
VALVE
S
HAFT
a30-4237
CLAMPING
S
CREW
ACTUATOR ARM
DI
S
ENGAGEMENT
BUTTON
MOUNTING - FULLY CLO
S
ED
MOUNTING - FULLY OPEN
a30-4238
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...