Table 10 - Alarm and alert messages (continued)
I. CHILLER PROTECTIVE LIMIT FAULTS
ICVC
FAULT
STATE
PRIMARY MESSAGE SECONDARY
MESSAGE
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
200
PROTECTIVE LIMIT
RECTIFIER POWER
FAULT
200->Rectifier Power Fault: Check VFD
Status
Malfunction within VFD Power Module.
Call Carrier Service.
201
PROTECTIVE LIMIT
INVERTER POWER
FAULT
201->Inverter Power Fault: Check VFD
Status
Malfunction within VFD Power Module.
Call Carrier Service.
202
PROTECTIVE LIMIT
MOTOR AMPS NOT
SENSED
202->Motor Amps Not Sensed -
Average Load Current [VALUE]
Check main circuit breaker for trip. Increase Current % Imbalance
in VFD_CONF screen.
203
FAILURE TO START
MOTOR
ACCELERATION
FAULT
203->Motor Acceleration Fault -
Average Load Current [VALUE]
Check that inlet guide vanes are fully closed at start-up.
Check Motor Rated Load Amps in VFD_CONF screen. Reduce
unit pressure if possible.
204
FAILURE TO STOP
VFD SHUTDOWN
FAULT
204->VFD Shutdown Fault: Check
Inverter Power Unit
VFD Circuit Board malfunction.
Call Carrier Service.
205
PROTECTIVE LIMIT
HIGH DC BUS
VOLTAGE
205->High DC Bus Voltage: [VALUE]
exceeded limit of [LIMIT]*
Verify phase to phase and phase to ground line voltage. Monitor
AC line for high transient voltage conditions. VFD Circuit Board
malfunction. Call Carrier Service.
206
PROTECTIVE LIMIT
VFD FAULT
206->VFD Fault Code: [VALUE]; Check
VFD Fault Code List
See VFD Fault Code description and corrective action.
207
PROTECTIVE LIMIT
HIGH CONDENSER
PRESSURE
207->High Cond Pressure trip. [VALUE]
exceeded Switch Trippoint.
Check Compressor Discharge High Pressure switch wiring and
accuracy.
Check for high condenser water temperatures, low water flow,
fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables in refrigerant.
208
PROTECTIVE LIMIT
EXCESSIVE MOTOR
AMPS
208->Percent Load Current [VALUE]
exceeded limit of [LIMIT]*.
Check Motor Rated Load Amps in VFD_CONF screen. Percent
Load Current > 110%.
Check Motor Rated Load Amps setting.
209
PROTECTIVE LIMIT
LINE CURRENT
IMBALANCE
209->Line Current Imbalance: Check
VFD Fault History for Values.
Check phase to phase and phase to ground power distribution
bus voltage.
Check Line Current % Imbalance in VFD_CONF screen. Consult
power company.
210
PROTECTIVE LIMIT
LINE VOLTAGE
DROPOUT
210->Single Cycle Line Voltage Dropout Temporary loss of voltage. Disable Single Cycle Dropout in VFD_
CONF screen.
211
PROTECTIVE LIMIT
HIGH LINE VOLTAGE 211->High Percent Line Voltage
[VALUE]
Check phase to phase and phase to ground distribution bus
voltage. Consult power company.
212
PROTECTIVE LIMIT
LOW LINE VOLTAGE
212->Low Percent Line Voltage
[VALUE]
Check phase to phase and phase to ground distribution bus
voltage. Consult power company.
213
PROTECTIVE LIMIT
VFD MODULE RESET 213->VFD Module Power-On Reset
When Running
Temporary loss of VFD control voltage. Check VFD control
power breaker, transformer and fuses.
214
PROTECTIVE LIMIT
POWER LOSS
214->Control Power Loss When
Running
Check phase to phase and phase to ground distribution bus voltage.
Check VFD fuses.
Check 24 V a.c. power supply to ICVC.
Consult power company.
215
PROTECTIVE LIMIT
LOW DC BUS
VOLTAGE
215->Low DC Bus Voltage: [VALUE]
exceeded limit of [LIMIT]*
Verify phase-to-phase and phase-to-ground line voltage. VFD
Circuit Board malfunction.
Call Carrier Service.
216
PROTECTIVE LIMIT
LINE VOLTAGE
IMBALANCE
216->Line Voltage Imbalance; Check
VFD Fault History for Values.
Check phase-to-phase and phase-to-ground distribution bus
voltage. Increase Line Voltage % Imbalance in VFD_CONF screen.
217
PROTECTIVE LIMIT
MOTOR OVERLOAD
TRIP
217->Motor Overload Trip; Check VFD
configurations
Any phase current > 106% RLA. Can result from significant load
side current imbalance when running at full load.
Check entering condenser water temperature and water flow rate.
Check Motor Rated Load Amps in VFD_CONF screen.
218
PROTECTIVE LIMIT
VFD RECTIFIER
OVERTEMP
218->VFD Rectifier Temp Exceeded:
Check Cooling and VFD Config.
Check that VFD refrigerant isolation valves are open.
Check VFD refrigerant cooling solenoid and refrigerant strainer.
Check for proper VFD cooling fan operation and blockage.
219
PROTECTIVE LIMIT
VFD INVERTER
OVERTEMP
219->VFD Inverter Temp Exceeded:
Check Cooling and VFD Config.
Check that VFD refrigerant isolation valves are open.
Check VFD refrigerant cooling solenoid and refrigerant strainer.
Check for proper VFD cooling fan operation and blockage.
220
PROTECTIVE LIMIT
GROUND FAULT
220->Ground Fault Trip; Check Motor
and Current Sensors
Check for condensation on motor terminals. Check motor power
leads for phase to phase or phase to ground shorts. Disconnect
motor from VFD and megger motor.
Call Carrier Service.
221
PROTECTIVE LIMIT
UNUSED
UNUSDED
222
PROTECTIVE LIMIT
LINE FREQUENCY
TRIP
222->Line Frequency [VALUE]: exceeded
limit of [LIMIT]: Check Power Supply.
If operating from a generator, check generator size and speed.
Check utility power supply.
223
LOSS OF
COMMUNICATION
WITH VFD GATEWAY
MODULE
223->Loss of SIO Comm with VFD
Gateway: Check VFG Module and
Power
Check VFD communication wiring and connectors on VFD
Gateway and DPI board.
Check for compatibility between ICVC and Gateway software.
224
PROTECTIVE LIMIT
VFD
COMMUNICATIONS
FAULT
224->Loss of DPI Comm with VFD
Gateway: Check VFG to VFD Comm.
Check VFD communication wiring and connectors.
Check status lights on DPI Communications Interface Board.
Call Carrier Service.
225
PROTECTIVE LIMIT
MOTOR CURRENT
IMBALANCE
225->Motor Current Imbalance: Check
VFD Fault History for Values.
Check Motor Current % Imbalance in VFD_CONF screen.
226
PROTECTIVE LIMIT
LINE PHASE
REVERSAL
226->Line Phase Reversal: Check Line
Phases
Reverse connections of any two line conductors to circuit
breaker.
227
PROTECTIVE LIMIT
OIL PRESS SENSOR
FAULT
227->Oil Pressure Delta P [VALUE]
(Pump Off): Check Pump/Transducers
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check transducer calibration.
* [LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., setpoint predefined or selected by the operator as an override, alert, or alarm condition.
[VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.