4
Table 3 - ICVC display data (continued)
Example 6 - POWER display screen
To access this display from the ICVC default screen:
1. Press
MenU
.
. Press
StAtUS
.
3. Scroll down to highlight
poWeR
.
4. Press
SeLeCt
.
DESCRIPTION
STATUS
UNITS
POINT
Percent Line Current
Average Line Current
Percent Line Voltage
Average Line Voltage
Line Power Factor
Line Kilowatts
Percent Line Kilowatts
Percent Load Current
Average Load Current
Motor Power Factor
Motor Kilowatts
Percent Motor Kilowatts
Motor Kilowatt-Hours
Demand Kilowatts
Line Current Ph 1 (R)
Line Current Ph 2 (S)
Line Current Ph 3 (T)
Load Current Ph 1 (U)
Load Current Ph 2 (V)
Load Current Ph 3 (W)
Line Voltage Ph 1 (RS)
Line Voltage Ph 2 (ST)
Line Voltage Ph 3 (TR)
Ground Fault Current
Line Frequency
Rectifier Overload
Inverter Overload
Motor Overload
Line Current Imbalance
Motor Current Imbalance
Line Voltage Imbalance
Line Active Current
Line Reactive Current
Line Active Voltage
Line Reactive Voltage
DC Bus Voltage Reference
DC Bus Voltage
Flux Current
Torque Current
Inverter Temperature
Rectifier Temperature
VFD Enclosure Temp
VFD Cold Plate Temp
Humidity Sensor Input
Relative Humidity
VFD Coolant Flow
Actual VFD Speed
0 to 999
0 to 99999
0 to 999
0 to 99999
0.0 to 2.0
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0.0 to 2.0
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 999
0 to 99
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 149
0 to 149
0 to 149
0 to 149
0.0 to 5.0
0 to 100
0 to 100
0 to 100
%
A
%
V
kW
%
%
A
kW
%
kWh
kW
A
A
A
A
A
A
V
V
V
A
Hz
%
%
%
%
%
%
A
A
V
V
V
V
A
A
°C
°C
°C
°C
V
%
%
%
LNAMPS_P
LNAMPS_A
LNVOLT_P
LNVOLT_A
LINE_PF
LINE_KW
LINEKW_P
LDAMPS_P
LDAMPS_A
MOTOR_PF
MOTOR_KW
MOTORKWP
MOTORKWH
DEM_KW
LN_AMPS1
LN_AMPS2
LN_AMPS3
LD_AMPS1
LD_AMPS2
LD_AMPS3
LN_VOLT1
LN_VOLT2
LN_VOLT3
GF_AMPS
LINEFREQ
RECT_OV
INV_OV
MOTOR_OV
LN_IMB_I
MT_IMB_I
LN_IMB_V
AMPS_ACT
AMPS_RE
VOLT_ACT
VOLT_RE
BUS_REF
BUS_VOLT
FLUXAMPS
TORQAMPS
INV_TEMP
REC_TEMP
VFD_ENCL
CP_TEMP
HUMID_SR
HUMIDITY
VFD_FOUT
VFD_ACT
Note:
All variables with CAPITAL LETTER point names are available for CCN read operation.