AppController overview and specifications
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
3
Protection
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
Status indicators
LEDs indicate status of communications, running, errors, and power.
Environmental operating
range
0 to 130°F (-18 to 54°C), 0 to 90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged GE C2950HF Cycoloy plastic
Overall dimensions
A:
B:
5-5/8 in. (14.3 cm)
5-1/8 in. (13 cm)
Mounting dimensions
C:
D:
E:
5-1/4 in. (13.3 cm)
2-9/16 in. (6.5 cm)
3/16 in. (.5 cm)
Panel depth
2 in. (5.1 cm)
Weight
0.44 lbs. (0.20 kg)
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
Listed by
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
Safety considerations
WARNING
Disconnect electrical power to the AppController before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.