background image

of the unit sections be used for jacking or tracking the 
AHU. FOR HORIZONTAL TRANSPORT ALWAYS 
PROVIDE SUPPORT UNDER THE LIFTING POINTS. 
 
 
 
 
 
 
 
 

3 - AHU STORAGE REQUIREMENTS 

3.1 – Short Term Storage 

 

To properly store the AHU, it is critical to meeting the 
storage requirements as per the following;  
 
3.1.1  Indoor storage weather: < 70% RH, < 40º C,  all 
AHUs sections are clearly label with sticker mentioning 
“STORE INDOOR”  
 
3.1.2  Well  ventilated store room precaution to prevent 
internal condensation that can lead to rust.  
 
3.1.3 Clean and non-corrosive environment.  
 
3.1.4  Storage platform to be smooth, minimum 
vibration and level.  
 
3.1.5  Ensure properly packed or cover the AHU, 
ensure the openings of the AHUs like the damper, fan 
and coil opening are closed so that no dust, no 
external material or animal allow to enter the AHU.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3.2 – Long Term Storage 

 
Storage period that took longer than 6 months inside 
the controlled environment, as explained above in 
Normal storage, less than 6 months; still  require 
serious and proper preservation actions  during the 
storage period  
 
3.2.1  Belts to be removed and kept safe with proper 
tag of the AHU in conditioned space,  belts shipped 
loose,  as standard in production of 39HQM and 
packed in plastic bag placed inside fan section. 
 
3.2.2  Filters to be removed and stored  in a proper 
packed & conditioned space. 
 
3.2.3  Periodically check fan bearing to see if re-
lubricate is required 
 
3.2.4 Periodically unload the bearing by turning the fan 
wheel by hand.  This operation prevents bearing 
corrosion by redistributing the bearing grease. 
 
After long term storage, grease should be purged from 
the bearing and fresh grease injected prior to start-up.  
 
3.2.5  Motors should be stored in a clean, dry 
environment protected from moisture. 
  
3.2.6 Periodically check of the AHU packing to ensure 
no sand/dust accumulation.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

- The use of bars / tubes as rollers can result in damage to 
the installation frame. 
-  Roller should be adequate to support the weight of the 
AHU section 
-  The roller used for AHU horizontal transport MUST BE 
FREE ROLLING.  
- The rollers are not supplied by factory. 

 

 

 

 

Store Indoor before Installation 

6

Содержание AiroVision 39 HQM

Страница 1: ...39 HQM Central Station Air Handling Units Advance Installation Operation and Maintenance 1 ...

Страница 2: ... Short term storage 6 3 2 Long term storage 6 4 CHECKLIST OF START UP CHECK POINTS 7 4 1 Preliminary information 7 4 2 Pre Start Up 7 4 3 Start up 7 5 STARTUP INSTRUCTIONS 8 5 1 Casing 8 5 1 1 Casing panels 8 5 1 2 Doors and access panels 8 5 1 3 Flexible connections 8 5 1 4 Earthing 8 5 1 5 AHU installation and connection 8 5 2 Dampers 9 5 3 Air Filters 9 5 4 Electric Heaters 10 5 5 Cooling Coil ...

Страница 3: ...r each section to be moved Earthing This label indicates where the AHU must be earthed and is on one of the support beams beneath the casing in the fan section The electrical components in the AHU must be earthed except for components with double insulation and or components with a supply voltage below 50 V The electrical components must be installed in accordance with national and local regulatio...

Страница 4: ...is opened Caution All doors and access covers must be closed before starting up the AHU 1 4 Disposal of Parts Materials The packaging material must be disposed of in a responsible manner and in accordance with local regulations Components that are replaced must be disposed of as described above 2 TRANSPORT AND LIFTING INSTRUCTIONS 2 1 General Transport and lifting of the AHU must always be in acco...

Страница 5: ... sequence The weight is given on each transport section Each transport section is equipped with a sub frame with four lifting points These points are marked by the label shown below For offloading as well as hoisting lifting cables can be attached 1 Under the wooden skid OR 2 To the lifting bars Lifting bars are not supplied by factory Evenly positioned spacer bars should be used between the lifti...

Страница 6: ...han 6 months still require serious and proper preservation actions during the storage period 3 2 1 Belts to be removed and kept safe with proper tag of the AHU in conditioned space belts shipped loose as standard in production of 39HQM and packed in plastic bag placed inside fan section 3 2 2 Filters to be removed and stored in a proper packed conditioned space 3 2 3 Periodically check fan bearing...

Страница 7: ...ted to unit in proper way straight duct after fan discharge is 2 5 fan diameter Verify wiring is correct for application voltage etc per component label 4 3 START UP If this unit is used for construction conditioning without ductwork ensure balancing is redone and filters replaced once construction is complete Verify wiring is correct for application voltage etc per component label Ensure correct ...

Страница 8: ...accordance with local regulations A label on the support frame indicates where the unit should be earthed 5 1 5 AHU Installation and Connection The floor in the room where the AHU is installed must be level and flat to prevent connection problems In case of multi section unit It is highly recommended to install common single channel base through the AHU base channel underneath the AHU Rubber pads ...

Страница 9: ... If there are more than two sections repeat the procedure above For an outdoor installation all external joints should be sealed 5 2 Dampers Check if the actuator motor is installed in accordance with the supplier s instructions Check if the correct angle has been set Check if the dampers close properly Check if the damper can open to the required angle Check operation after the power has been res...

Страница 10: ...eat Recovery Wheel Check that the wheel is rotating in the correct direction This is indicated by an arrow on the casing Check if the wheel seals are fitting correctly Check if belt tension is correct Check if the motor has been correctly connected Check if the controller has been correctly connected and set in accordance with the instructions of the supplier if any Check if the rotor speed has be...

Страница 11: ...nd leave the grooves at an angle causing excessive belt and sheave wear 5 9 1 1 Shaft Alignment Shaft alignment can be checked by measuring the distance between the shafts at 3 or more locations If the distances are equal then the shafts are parallel 5 9 1 2 Sheave Alignment Fixed sheaves To check the location of the fixed sheaves on the shafts a straightedge or laser guide device Straightedge mus...

Страница 12: ...at sensors COIL Fins Contamination Clean dirt with compressed air Damage Check fin alignment and comb fins Coil Frames Air by pass Check gap and seal with silicon sealant to avoid fresh air by pass Headers Seal Water leakage Check gap and seal with silicon sealant to avoid fresh air by pass Incase tube leak braze leak point Eliminators Contamination Clean dirt with compressed air Drain pan Contami...

Страница 13: ...observed as irreparable damage of the panels might otherwise occur Clean the outside air intake well and repair damage as described in point 7 2 1 7 8 Filters The filters must be inspected once a month for excess pollution pressure loss damage and seating of the slide in filters or built in frames With slide in filters ensure that the filters have been correctly positioned and have been pushed wel...

Страница 14: ...ith a grease nipple The lubrication interval and type of lubricant are as above 7 13 3 Transmission After starting up the unit but also after replacing the belts the belt tension has to be checked within one week and then after two weeks and further tensioned if required After that check the belt tension and inspect the condition of the belts every three months The Correct Belt Tension depends on ...