AGATWNPME01B: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

17

CONNECT ELECTRICAL

COMPONENTS—COOLING 

NOTE: 

Cooling  units  used  with  twinned  furnaces  MUST  be

single-stage A/C units.  HEAT PUMPS CANNOT BE TWINNED with

gas furnaces.
When installing twinned outdoor units with twinned gas furnaces, it is

necessary  to  use  field-supplied  24-VAC  pilot-duty  relay(s)  and  a

field-supplied 24-VAC/115-VAC transformer as shown in the individual

wiring  diagrams  to  prevent  overloading  furnace  24-VAC/115-VAC

transformer.  Transformer  VA  rating  must  be  able  to  handle  the  load

imposed on it by the outdoor unit contactor(s).

1. Connect the L1 lead of the field-supplied transformer line voltage

lead to L1 on Main furnace control board.

2. Connect  the  Neutral  lead  of  the  field-supplied  transformer  to  an

open Neutral terminal on the Main furnace control board.

NOTE: 

If sufficient room is available in the control box of the outdoor

unit, a 24-VAC/240-VAC transformer may be used. Connect line voltage

leads of the transformer to the appropriate connection locations on the

outdoor  unit,  Refer  to  the  outdoor  unit  wiring  diagram  for  specific

details.

For Two-Stage A/C Operation with a Two-Stage 

Thermostat

See 

Fig. 23

In this configuration, the A/C unit(s) are staged on and run as controlled

by the thermostat. It will be necessary to supply two pilot duty relays for

staged A/C operation. One A/C unit will be the first stage unit, the other

A/C unit will be the second stage unit. Both furnaces come on in high

cooling airflow, regardless of A/C staging.

1. Connect one coil terminal of each of the pilot duty relay together.
2. Connect  these  two  terminals  to  the  “COM/24V”  terminal  of  the

furnace control board.

3. Select  one  of  the  relays  to  be  the  relay  for  first  stage  cooling.

Connect the coil terminal of this relay to the “Y/Y2” terminal of the

furnace control board.

4. The other relay is the second stage cooling relay. The coil terminal

of this relay will connect to the “Y/Y2” terminal of the thermostat.

Do  not  connect  the  terminal  to  the  Y1  terminal  on  the  furnace

control board.

5. Connect the R terminal of the field-supplied transformer to the open

contact of each pilot duty relay.

6. Connect the other open contact of the first stage cooling relay to the

wire for Y terminal of the first stage contactor.

7. Connect the other open contact of the first stage cooling relay to the

wire for Y terminal of the second stage contactor.

8. Connect the Common terminal of the contactor(s) to the C terminal

of the field supplied transformer. 

L14F004

Fig. 23 – Field-Installed A/C Wiring (when required)

For Single-Stage A/C Operation with a Single-Stage 

Thermostat

See 

Fig. 24

In  this  configuration,  the A/C  unit(s)  run  as  a  single  unit.  It  will  be

necessary to supply a pilot duty relay for A/C operation. 

1. Connect one coil terminal of the pilot duty relay to  “COM/24V” of

the furnace control board.

2. Connect the other coil terminal of this relay to the “Y/Y2” terminal

of the furnace control board.

3. Connect the R terminal of the field-supplied transformer to the open

contact of the pilot duty relay.

4. Connect the other open contact of the first stage cooling relay to the

wire for Y terminal of each outdoor unit contactor.

5. Connect the Common terminal of the contactor(s) to the C terminal

of the field supplied transformer. 

L14F005

Fig. 24 – Field-Installed A/C Wiring (when required)

THERMOSTAT CONNECTIONS

NOTE: 

All thermostat connections MUST be made at the Main furnace

control board. Do not make any thermostat connections to the Secondary

furnace control board.

WARNING

!

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death,

or property damage. 

Before  installing,  modifying,  or  servicing  system,  main  electrical

disconnect switch must be in the OFF position and install a lockout tag.

There may be more than one disconnect switch.  Check accessories and

cooling  unit  for  additional  electrical  supplies  that  must  be  shut  off

during  furnace  servicing.    Lock  out  and  tag  switch  with  a  suitable

warning label.  Verify proper operation after servicing. 

WARNING

!

UNIT DAMAGE AND FIRE HAZARD

Failure to follow this  warning  could result  in fire,  personal  injury or

death.

Make  no  connections  between  the  connector  in  one  furnace  and  the

connector in other furnace.

24 VAC

115 VAC

115 VAC

24 VAC

Содержание AGATWNPME01B

Страница 1: ...ODELS 3 ELECTROSTATIC DISCHARGE ESD PRECAUTION 5 SECTION 2 5 GENERAL ALL ORIENTATIONS 5 INSTALL FURNACES 5 UPFLOW INSTALLATION 5 DOWNFLOW INSTALLATIONS 6 HORIZONTAL INSTALLATION 6 General 6 Attic Platform Back to Back Installations Non Condensing and Condensing Furnaces 7 Horizontal Suspended Installation Condensing Models 7 Horizontal Suspended Installation Non Condensing Models 7 Horizontal Stac...

Страница 2: ...es to the furnace and install lockout tag before performing any installation or modification Follow the operating instructions on the label attached to the furnace CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicin...

Страница 3: ...ces through a common bottom plenum The bottom return air plenum shall be at least as high as the width of the furnace bottom return air opening For example if two 17 1 2 in 445 mm wide furnaces are twinned together the full height common return air plenum must be at least 17 1 2 in 445 mm tall When there are height limitations the bottom return air plenum height can be reduced to 8 in 203 mm minim...

Страница 4: ...TE Downflow Application Do not connect return air to any side of the furnace Connect return air plenum as shown NOTE Horizontal Application Do not connect return air to any side of the furnace Do not stack condensing furnaces on top of each other Horizontal stacking only permitted with mid efficiency furnaces Back to back installations platform or suspended is approved for all models For back to b...

Страница 5: ...bles and service as shown in the individual furnace installation instructions 1 Select two identical heating and airflow furnaces see Table 1 2 Remove bottom closure panels from both furnaces see Fig 6 a Remove main and blower access doors b Remove screws from front filler panel and bottom closure panel when used c Rotate front filler panel downward to remove d Remove bottom closure panel and set ...

Страница 6: ... of indoor coils and or common supply plenum If no approved cased indoor coil is used install the furnaces on accessory combustible floor bases For side by side installations adjust and shim each furnace to align unused 7 8 in 22 mm knockout in blower compartment which will be used for wire routing between furnaces 5 Drill two 1 8 in 3 mm holes approximately 1 in 25 mm below return air flange from...

Страница 7: ...spension rods as shown in Fig 14 5 Lay furnaces back to back on a flat surface with 7 8 in knock outs facing upward 6 Drill two 1 8 in 3 mm holes approximately 1 in 25 mm below return air flange from inside top of return air opening and through both furnaces see Fig 10 7 Drive one factory supplied No 6 x 3 4 in 19 mm LG screw through each hole and tighten until furnaces are secure and foam strips ...

Страница 8: ...l additional building codes 4 Long truss spans may require additional support along the bottom chord of the truss Consult the truss manufacturer s guidelines for engineering assistance 5 Long rafter or attic joist spans may require additional support along the bottom of the rafter or joist Consult local or regional building codes for design and loading requirements For suspended installations see ...

Страница 9: ...NSATE TRAP 2 ACCESS OPENING FOR TRAP 30 762mm MIN WORK AREA COMMON RETURN VENT COMBUSTION AIR INTAKE ROLLOUT PROTECTION REQUIRED INSTALL 12 X 22 305 X 559mm SHEET METAL IN FRONT OF BURNER COMPARTMENT AREA SEDIMENT TRAP SEDIMENT TRAP EXTENSION HARNESS GAS SUPPLY SHUT OFF GAS PIPE UNION GAS PIPE UNION GAS SUPPLY SHUT OFF SHEET METAL 22 556 mm 12 305 mm 4 3 4 121 mm 1 25 mm 17 3 4 451 mm OVER ALL 4 3...

Страница 10: ...Fig 14 Suspended Installation of a Condensing Furnace 1 4 1 4 ROLLOUT PROTECTION REQUIRED Install 12 x 22 204 x 559 mm sheet metal above the burner compartment area Sheet metal MUST extend above the furnace casing by 1 25 mm with door removed A 1 25 mm clearance minimum between top of furnace and combustible material is required Entire length of furnace must be supported with furnace is used in ho...

Страница 11: ...igns without notice and without obligations 11 A10276 Fig 15 Suspended Installation of a Non Condensing Furnace A10278 Fig 16 Suspended Installation of Stacked Non Condensing Furnaces 3 8 Flat Washer 3 8 Hex Nut 3 8 Flat Washer 11 2 x 11 2 x 1 4 Angle Iron 3 8 Lock Washer 3 8 Theaded Rod 3 8 Lock Washer 3 8 Hex Nut ...

Страница 12: ...e voltage potential between both furnaces will be ZERO If a Both LEDs are on continuously System phasing is okay b One or both LEDs are rapidly flashing 1 Line voltage polarity is reversed 2 Furnace s are not grounded 3 Transformer polarity is reversed c One LED is off one LED is on continuously 1 The 24 VAC circuit is inoperative on furnace with LED light off 2 Check transformers auxiliary limits...

Страница 13: ...l Secondary Twinning Harness Install Secondary Twinning Kit Harness The Secondary Twinning Kit harness is identified by a white label marked SECONDARY on the label near the two pin plug of the Auxiliary Limit Switch ALS S leads The Door Interlock Relay ILR and Secondary Auxiliary Limit Switch ALS M mount to the blower housing as shown in Fig 19 The individual leads are labeled on the harness see F...

Страница 14: ...talled Locate the green yellow and white wires from the extension harness and connect the wires to the Communication Connector as shown above L14F006A Fig 18 Twinning Communication Connection L12F009 NOTE a Mount Twinning Kit Relay TKR and Interlock Relay ILR on furnace blower housing as shown b Twining Kit Relay TKR mounts on LH Furnace blower housing c Interlock Relay ILR mounts on RH furnace bl...

Страница 15: ...CONNECTIONS 115 VAC L1 LINE VOLTAGE CONNECTIONS EAC 1 TERMINAL 115 VAC 1 0 AMP MAX PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR TRANSFORMER 24 VAC CONNECTIONS 3 AMP FUSE STATUS AND COMM LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR SW2 AIR CONDITIONING AC AIRFLOW SETUP SWITCHES 6 7 8 COMMUNICATION CONNECTOR WHEN USED SW2 CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES 3 4 5 HUMIDIFIER...

Страница 16: ...AGATWNPME01B Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 L14F007 Fig 22 Secondary Harness ...

Страница 17: ...terminal to the Y1 terminal on the furnace control board 5 Connect the R terminal of the field supplied transformer to the open contact of each pilot duty relay 6 Connect the other open contact of the first stage cooling relay to the wire for Y terminal of the first stage contactor 7 Connect the other open contact of the first stage cooling relay to the wire for Y terminal of the second stage cont...

Страница 18: ...e control 9 Connect thermostat C or COM lead to the COM 24V terminal on the Main furnace control board L14F010 Fig 26 Furnace Thermostat Switch A07907 Fig 27 Example of Setup Switch in OFF Position Single Stage Furnaces with Single Stage Thermostat Field Supplied See Fig 31 and Table 3 NOTE This application allows both furnaces to operate together as a single unit See furnace Installation Start Up...

Страница 19: ... Y2 None Thermostat Y2 wired directly to RH accessory relay to start RH A C for second stage cooling G G Starts both indoor fans on cooling speed with Y Y2 energized Dehum Dehum Reduces airflow in cooling mode to 90 of high cooling airflow when Dehum input is removed Table 4 Two Stage Furnace Thermostat Connections Two Stage Heating with Single Stage Thermostat Using Two Stage Furnaces C C Transfo...

Страница 20: ... the right to change at any time specifications and designs without notice and without obligations 20 A190208 Fig 29 Two Stage Furnace with Single or Two Stage Thermostat Field Supplied A200260 Fig 30 Single Stage Furnace with Two Stage Thermostat Field Supplied ...

Страница 21: ...ace Installation Start Up and Operating Instructions for details on relocating the condensate and attaching field drain connections Indoor coil condensate drains must not be hard piped to condensing furnace condensate drain Route indoor coil condensate drains separately to a code approved drain Indoor coil condensate drains may be combined with furnace condensate drains provided a stand pipe conne...

Страница 22: ...main limit or twinning kit auxiliary limit switch in which case both furnaces respond Before performing component test disconnect Communication PL7 Connector from LH furnace control After removing component test can be initiated on each furnace individually as stated in Installation Start Up and Operating Instructions SINGLE STAGE HEAT SINGLE STAGE FURNACES WITH SINGLE STAGE THERMOSTAT 1 Operation...

Отзывы: