background image

10. Isolate the hangar straps from the insulation by using metal sleeves bent to conform to the shape of the insulation.

If refrigerant tubes or indoor coil is exposed to atmospheric conditions for longer than 5 minutes, it must be evacuated to 500 microns to eliminate
contamination and moisture in the system.

CAUTION: DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT TUBING IN GROUND. If any section of tubing is

buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the recommended length
is buried, refrigerant may migrate to cooler buried section during extended periods of unit shutdown, causing refrigerant
slugging and possible compressor damage at start-up.

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

VAPOR

Connect Diameter

Tube Diameter

Connect Diameter

Tube Diameter

024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult your local distributor or the Long-Line Application Guideline.

B.

Outdoor Units Connected to Factory-Approved Indoor Units

Outdoor unit contains correct system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied
or factory accessory tubing. Check refrigerant charge for maximum efficiency. (See Procedure 9—Checking Charge.)

C.

Install Solenoid Valve in Liquid Tube

CAUTION: All models require liquid line solenoid for performance enhancement. Solenoid valve must be energized

during evacuation for complete removal.

Fig. 3—Piping Installation

A92469

OUTDOOR WALL

CAULK

INDOOR WALL

LIQUID LINE

VAPOR LINE

INSULATION

JOIST

INSULATION

HANGER  STRAP

(AROUND VAPOR 

LINE ONLY)

VAPOR  LINE

LIQUID

LINE 

THROUGH THE WALL

SUSPENSION

1

 

MIN

NOTE: 
AVOID CONTACT BETWEEN TUBING AND STRUCTURE

—3—

Содержание AC1B

Страница 1: ...nts Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal...

Страница 2: ...bing requirements beyond 50 ft consult Long Line Application Guideline which is available at your local distributor NOTE In some cases noise in the living area has been traced to gas pulsations from i...

Страница 3: ...er Connect Diameter Tube Diameter 024 3 8 3 8 5 8 5 8 030 036 3 8 3 8 3 4 3 4 042 048 3 8 3 8 7 8 7 8 060 3 8 3 8 7 8 1 1 8 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 5...

Страница 4: ...r brazing After wrapping the service valve with a wet cloth the tubing set can be brazed to the service valve using either silver bearing or non silver bearing brazing material Consult local code requ...

Страница 5: ...nd increase the transformer capacity or split the load with an accessory transformer as required PROCEDURE 6 COMPRESSOR CRANKCASE HEATER A crankcase heater is required if the refrigerant tubing is lon...

Страница 6: ...this information your dealer may be able to offer helpful suggestions over the telephone or save valuable time through knowledgeable preparation for the service call PROCEDURE 2 REGULAR DEALER MAINTE...

Страница 7: ...U BRN HC NOTES 1 REFER TO UNIT LABEL WIRING DIAGRAM FOR WIRE COLORS IFR IFM AND LLS ARE LOCATED INDOORS ON HEATING COOLING APPLICATIONS IF ACCESSORY IFR IS REQUIRED FOR COOLING ONLY APPLICATIONS LOCAT...

Страница 8: ...1993 RESCO P O Box 1667 Indianapolis IN 46206 13058r 8 1093 Catalog No 92 33AC 1B1...

Отзывы: