background image

B.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating label on unit service panel. (See
Fig. 2.) It contains information needed to properly install unit. Check rating label to be sure unit matches job specifications.

PROCEDURE 2—INSTALL ON A SOLID, LEVEL MOUNTING PAD

If conditions or local codes require the unit be attached to pad, tie-down bolts should be used and fastened through knockouts provided in unit
base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole locations.

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit
and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a
distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

On rooftop applications, locate unit at least 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from
structure.

Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop
applications.

PROCEDURE 3—REPLACE INDOOR REFRIGERANT FLOW CONTROL DEVICE, IF REQUIRED

Check indoor coil piston to see if it matches the required piston shown on unit rating label. If it does not match, replace indoor coil piston with
piston shipped with unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination.

PROCEDURE 4—MAKE PIPING CONNECTIONS

Outdoor units may be connected to indoor sections using accessory tubing package or field-supplied refrigerant grade tubing of correct size and
condition. For tubing requirements beyond 50 ft, consult Long-Line Application Guideline which is available at your local distributor.

NOTE:

In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.

A.

Installation Recommendations

1. Locate the unit away from windows.

2. Ensure that vapor and liquid line diameters are appropriate to the capacity of the unit. (See Table 1.)

3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.

4. Leave some slack between the structure and the unit to absorb vibration.

5. When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk. (See Fig. 3.)

6. Avoid direct lineset contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with the tubing. (See Fig.

3.)

8. Ensure that tubing insulation is pliable and completely surrounds the vapor line.

9. When necessary, use hangar straps which are 1 in. wide and conform to the shape of the tubing insulation. (See Fig. 3.)

Fig. 2—Unit Reference Drawing

UNIT SIZE

A

B

C

D

E

In.

In.

In.

In.

In.

024

30

23-1/2

6-1/2

10

5/8

030, 036

30

23-1/2

6-1/2

10

3/4

042–060

30

23-1/2

6-1/2

10

7/8

A92490

UNIT RATING

PLATE

INDIANAPOLIS IN

46206

313948-401

REV A

MAX CKT-BKR

MAX HACR CKT-BKR

MAX FUSE

TYPE

MINIMUM CIRCUIT AMPS

LO

HI

DESIGN/TEST PRESSURE GAGE

FLA

HZ

PH

VOLTS AC

LRA

RLA

HZ

PH

VOLTS AC

MAX

PH

LBS

PISTON

MODEL

PROD

SERIAL

N/A

USA

N/A

CANADA

MAX OVERCURRENT PROTECTIVE DEVICE

kPa

kPa

PSI

PSI

FAN MOTOR

COMPRESSOR

SUITABLE FOR OUTDOOR USE

MIN

HZ

Kg

VOLTS

POWER SUPPLY

ID

OD

FACTORY CHARGED R-22

®

®

PERMISSIBLE VOLTAGE AT UNIT

CARRIER CORP

AIR 

DISCHARGE

AIR 

DISCHARGE

AIR IN

AIR IN

B

AIR IN

D

C

AIR DISCHARGE

3

/

8

″  

DIA 

LIQUID TUBE CONN

FIELD POWER SUPPLY CONN

7

/

8

″ 

DIA HOLE WITH 

1

/

8

″ 

DIA KNOCKOUT

AND 1 

3

/

8

″ 

DIA KNOCKOUT

 

AIR IN

A

FIELD CONTROL POWER 
SUPPLY CONN

7

/

8

″ 

DIA HOLE

DIA SERVICE LINE CONN

TIEDOWN KNOCKOUTS

(2) PLACES

—2—

Содержание AC1B

Страница 1: ...nts Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal...

Страница 2: ...bing requirements beyond 50 ft consult Long Line Application Guideline which is available at your local distributor NOTE In some cases noise in the living area has been traced to gas pulsations from i...

Страница 3: ...er Connect Diameter Tube Diameter 024 3 8 3 8 5 8 5 8 030 036 3 8 3 8 3 4 3 4 042 048 3 8 3 8 7 8 7 8 060 3 8 3 8 7 8 1 1 8 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 5...

Страница 4: ...r brazing After wrapping the service valve with a wet cloth the tubing set can be brazed to the service valve using either silver bearing or non silver bearing brazing material Consult local code requ...

Страница 5: ...nd increase the transformer capacity or split the load with an accessory transformer as required PROCEDURE 6 COMPRESSOR CRANKCASE HEATER A crankcase heater is required if the refrigerant tubing is lon...

Страница 6: ...this information your dealer may be able to offer helpful suggestions over the telephone or save valuable time through knowledgeable preparation for the service call PROCEDURE 2 REGULAR DEALER MAINTE...

Страница 7: ...U BRN HC NOTES 1 REFER TO UNIT LABEL WIRING DIAGRAM FOR WIRE COLORS IFR IFM AND LLS ARE LOCATED INDOORS ON HEATING COOLING APPLICATIONS IF ACCESSORY IFR IS REQUIRED FOR COOLING ONLY APPLICATIONS LOCAT...

Страница 8: ...1993 RESCO P O Box 1667 Indianapolis IN 46206 13058r 8 1093 Catalog No 92 33AC 1B1...

Отзывы: