6 Controller Alarm Indications (Sheet 6 of 8)
Alarm Code
Cause
Components
Troubleshooting
Corrective Actions
AL56
Primary
Return Sensor
(RTS)
Invalid Return
Temperature Sensor
(RTS) reading.
Return
Temperature
Sensor (RTS)
Perform Pre-trip P5:
If P5 passes, no further
action is required.
If P5 fails, replace the
defective sensor as
determined by P5, refer
to TEMPERATURE
SENSOR Service
AL57
Ambient
Sensor
(AMBS)
Invalid Ambient
Temperature Sensor
(AMBS) reading.
Ambient
Temperature
Sensor (AMBS)
Test the AMBS, refer to
Sensor Checkout
Replace AMBS if
defective, refer to
TEMPERATURE
SENSOR Service
AL58
Compressor
High Pressure
Safety (HPS)
High pressure safety
switch remains open
for at least one minute.
High Pressure
Switch (HPS)
Test the HPS; refer to
Checking High Pressure
Switch, Section 6.9.1.
Replace HPS if
defective, refer to
Sensor Replacement,
Refrigeration
System
Check unit for air flow
restrictions.
Clean or remove any
debris from coils.
AL59
Heater
Termination
Thermostat
(HTT)
Heat Termination
Thermostat (HTT) is
open.
Heat Termination
Thermostat (HTT)
Check for 24 volts at test
point TP10, if no voltage at
TP10 after unit has
reached set point HTT is
open.
Replace HTT if
defective, refer to
Sensor Replacement
AL60
Defrost
Temperature
Sensor (DTS)
Failure of the Defrost
Temperature Sensor
(DTS) to open.
Defrost
Temperature
Sensor (DTS)
Test the DTS; refer to
Sensor Checkout Proced-
ure Section 6.22.1.
Replace the DTS if
defective, refer to
Sensor Replacement
AL61
Heater
Current Draw
Fault
Improper current draw
during heat or defrost
mode.
Heater(s)
While in heat or defrost
mode, check for proper
current draw at heater
contactors, refer to
ELECTRICAL DATA
Replace heater(s) if
defective, refer to
Evaporator Heater
Removal and
Replacement.
Contactor
Check voltage at heater
contactor on the heater
side. If no voltage present:
Replace heater contact-
or if defective.
AL63
Current Limit
Unit operating above
current limit.
Refrigeration
System
Check unit for air flow
restrictions.
Clean or remove any
debris from coils.
Check unit for proper
operation.
Repair as needed.
Power supply
Confirm supply voltage/fre-
quency is within specifica-
tion and balanced accord-
ing to ELECTRICAL DATA
Correct power supply.
Current limit set
too low.
Check current limit setting
Code Cd32.
The current limit can be
raised (maximum of 23
amps) using Cd32.
AL64
Discharge
Temperature
Sensor
(CPDS)
Discharge
Temperature sensor
out of range.
Discharge
temperature
sensor (CPDS).
Test the CPDS; refer to
Sensor Checkout
Procedure, Section
Replace the CPDS if
defective, refer to
Sensor Replacement
Содержание 69NT40-561-201
Страница 2: ......
Страница 11: ......
Страница 15: ......
Страница 29: ......
Страница 81: ......
Страница 108: ...7 2 T 364 Based on Drawing 62 11753 Figure 7 2 SCHEMATIC DIAGRAM ...
Страница 109: ...7 3 T 364 Based on Drawing 62 11753 Figure 7 3 UNIT WIRING DIAGRAM Sheet 1 of 2 ...
Страница 110: ...7 4 T 364 Based on Drawing 62 11753 Figure 7 3 UNIT WIRING DIAGRAM Sheet 2 of 2 ...
Страница 111: ......
Страница 115: ......
Страница 116: ......