GUIDE SPECIFICATIONS

General

System Description

Furnish a ______________________ 4--way multipoise gas--fired

condensing furnace for use with natural gas or propane (factory--
authorized conversion kit required for propane); furnish external

media cabinet for use with accessory media filter or standard filter.

Quality Assurance

Unit will be designed, tested and constructed to the current ANSI Z

21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit

will carry the CSA Blue Star

R

and Blue Flame

R

labels. Unit

efficiency testing will be performed per the current DOE test

procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and

handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only. Warranty certificate available upon request.

Equipment

Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be

permanently lubricated with sealed ball bearings, of _______hp,

and have multiple speeds from 600--1200 RPM operating only
when 24--VAC motor inputs are provided. Blower motor shall be

direct drive and soft mounted to the blower housing to reduce
vibration transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media

Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted

galvanized steel.
Draft Inducer Motor
Draft inducer motor shall be single--speed PSC design.

Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass corrosion--resistant

aluminized steel of fold--and--crimp sectional design and applied

operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under

negative pressure.
Controls
Controls shall include a micro--processor--based integrated

electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a

self--test feature that checks all major functions of the furnace, and

a replaceable automotive--type circuit protection fuse. Multiple
operational settings available, including blower speeds for high

heat, low cooling, high cooling and continuous fan. Continuous
fan speed may be adjusted from the thermostat. Features will also

include temporary reduced airflow in the cooling mode for
improved dehumidification when a TP--PRH edge

R

is selected as

the thermostat.

Operating Characteristics

Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions

shall

be:

depth_________in.

(mm);

width

__________in. (mm); height___________in. (mm) (casing only).

Height shall be_________in. (mm) with A/C coil and

_________________in. (mm) overall with plenum.

Electrical Requirements

Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).

Minimum wire size shall be ________AWG; maximum fuse size

of HACR--type designated circuit breaker shall be _________
amps.

Special Features

Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.

59SP5A

Содержание 59SP2A

Страница 1: ...tible humidity control system S ComfortFan technology allows control of continuous fan speed from a compatible thermostat S Ideal height 35 889 mm cabinet short enough for taller coils but still allows enough room for service S Silicon Nitride Power Heat Hot Surface Igniter S External Media Filter Cabinet included S 4 way multipoise design for upflow downflow or horizontal installation with unique...

Страница 2: ...nhancement for select Carrier air conditioner or heat pump systems It uses less electrical power than its PSC counterpart and also has a wider range of speeds Reliable Heat Exchanger Design The aluminized steel clam shell primary heat exchanger was re engineered to achieve greater efficiency out of a smaller size The first two passes of the heat exchanger are based on the current 80 product a desi...

Страница 3: ...r Certified Watt Data KGAWF1506UFR Electrical Data 040 10 040 12 060 12 060 14 080 16 080 20 100 20 120 22 Input Voltage Volts Hertz Phase 115 60 1 Operating Voltage Range Min Max 104 127 Maximum Input Amps Amps 7 4 7 4 7 5 9 1 9 1 11 6 11 7 11 7 Unit Ampacity Amps 10 3 10 3 10 4 12 4 12 4 15 5 15 6 15 6 Minimum Wire Size AWG 14 14 14 14 14 12 12 12 Maximum Wire Length Minimum Wire Size Feet 36 36...

Страница 4: ...20 120 000 BTU 140 140 000 BTU Not all familes have these models Example of Model Number 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE A12373 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS VALVE MAIN LIMIT SWITCH BEHIND GAS VALVE REPRESENTATIVE DRAWING ONLY SOME MODELS MAY VARY IN APPEARANCE ELECTRICAL JUNCTION BOX IF REQUIRED LOCATION MAY VARY MEDIA CABINET OPE...

Страница 5: ...N42011SP D D D D D D D D Gas Orifice Kit 42 Nat Gas LH32DB207 D D D D D D D D Gas Orifice Kit 43 Nat Gas LH32DB202 D D D D D D D D Gas Orifice Kit 44 Nat Gas LH32DB200 D D D D D D D D Gas Orifice Kit 45 Nat Gas LH32DB205 D D D D D D D D Gas Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D Gas Orifice Kit 47 Nat Gas LH32DB078 D D D D D D D D Gas Orifice Kit 48 Nat Gas LH32DB076 D D D D D D D D Gas ...

Страница 6: ...5 Yellow 1810 1760 1725 1685 1640 1600 1555 1520 1480 1415 Blue 1385 1340 1285 1240 1200 1140 1090 1050 995 950 Orange 1560 1520 1475 1430 1385 1335 1295 1240 1200 1150 Red 1055 985 910 860 795 750 680 615 565 495 100 20 BOTTOM or TWO SIDES 4 5 Gray 2340 2295 2250 2195 2110 2030 1935 1835 1725 1605 Yellow 1950 1900 1855 1800 1755 1705 1655 1605 1560 1485 Blue 1750 1700 1650 1605 1555 1500 1455 139...

Страница 7: ...A NA 60 000 23 7 0 119 36 3 210 64 0 235 71 6 NA 80 000 15 4 6 59 18 0 155 47 2 210 64 0 232 70 7 100 000 NA 19 5 8 98 29 9 211 64 3 236 71 9 120 000 NA NA 8 2 4 86 26 2 224 68 3 140 000 4 NA NA NA 79 24 1 158 48 2 4001 to 4500 1219 to 1370 40 000 36 11 0 177 53 9 205 62 5 NA NA 60 000 21 6 4 115 35 1 204 62 2 228 69 5 NA 80 000 14 4 3 56 17 1 150 45 7 202 61 6 224 68 3 100 000 NA 17 5 2 94 28 7 2...

Страница 8: ...nt Vent Length TEVL 112 ft Add all of the above lines Maximum Equivalent Vent Length MEVL 127 ft For 2 pipe from Table 1 Is TEVL less than MEVL YES Therefore 2 pipe may be used Example 2 A direct vent 60 000 Btuh furnace installed at 2100 ft 640 M Venting system includes FOR EACH PIPE 100 feet 30 M of vent pipe 95 feet 28 M of combustion air inlet pipe 3 90_ long radius elbows and a polypropylene ...

Страница 9: ...8 63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51 8 120 000 NA NA NA 56 17 1 164 50 0 140 000 4 NA NA NA 23 7 0 42 12 8 9001 to 10 000 2743 to 3048 40 000 5 1 5 110 33 5 115 35 1 NA NA 60 000 NA 76 23 2 142 43 3 156 47 5 NA 80 000 NA 31 9 4 103 31 4 1...

Страница 10: ...0 2 33 8 27 1 6 1 21 3 47 9 40 5 32 6 20 30 Ft 20 25 23 14 1 20 70 94 77 57 20 70 113 94 71 M 6 1 7 6 7 0 4 3 0 3 6 1 21 3 28 7 23 5 17 4 6 1 21 3 34 4 28 7 21 6 40 40 Ft 20 14 12 3 0 20 70 71 56 38 20 70 86 70 50 M 6 1 4 3 3 7 0 9 0 0 6 1 21 3 21 6 17 1 11 6 6 1 21 3 26 2 21 3 15 2 100000 20 10 Ft N A 25 99 89 78 N A 25 110 233 265 N A 25 110 235 229 M N A 7 6 30 2 27 1 23 8 N A 7 6 33 5 71 0 80 ...

Страница 11: ...PPLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sides of Supply Plenum 1 in 25 mm Sides 0 0 mm Vent 0 0 mm Top of Furnace 1 in 25 mm Recommended Consult your local building codes COMBUSTION AIR PIPE FOR NON DIRECT 1 PIPE VENT APPLICATION FIELD SUPPLI...

Страница 12: ... 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric Vent Kit A93086 A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the ot...

Страница 13: ...D SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y te...

Страница 14: ...NSIONS IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters a For 800 CFM 16 in 406 mm round or 14 1 2 x 12 in 368 x 305 mm rectangle b For 1200 CFM 20 in 508 mm round or 14 1 2 x 19 1 2 in 368 x 495 mm rectan...

Страница 15: ...e as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted galvanized steel Draft Inducer Motor Draft inducer motor shall be single speed PSC design Primary Heat Exchangers Primary heat exchangers shall be 3 Pass corrosion resistant aluminized steel of fold and crimp sectional design and applied operating under negative pressure Secondary Heat Exchange...

Страница 16: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 05 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 59SP5A 05PD Replaces 59SP5A 04PD 59SP5A ...

Отзывы: