background image

EXAMPLE: (0-2000 ft altitude)
Furnace input from rating plate is 100,000 Btuh.
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 975 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 16)
Btu heating input = 103 X 975 = 100,425 Btuh.
In this example, the orifice size and manifold
pressure adjustment is within ±2 percent of the
furnace input rate.

SET TEMPERATURE RISE

UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat exchanger
areas not designed for condensate.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.

Determine and adjust air temperature rise as follows:

1. Place thermometers in return and supply ducts as close to

furnace as possible. Be sure thermometers do not see heat
exchangers so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.

2. When thermometer readings stabilize, subtract return-air tem-

perature from supply-air temperature to determine air tem-
perature rise.

3. Adjust temperature rise by adjusting blower speed. Increase

blower speed to reduce temperature rise. Decrease blower
speed to increase temperature rise.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115-v electrical power before changing speed tap.

4. To change blower motor speed selections for heating mode,

remove blower motor lead from control HEAT terminal. (See
Fig. 36.) Select desired blower motor speed lead from 1 of the
other motor leads and relocate it to HEAT terminal. See Table
17 for lead color identification. Reconnect original lead on
SPARE terminal.

Follow this same procedure for proper selection of COOL
speed selection.

ADJUST BLOWER OFF DELAY (HEAT MODE)

The blower off delay has 4 adjustable settings from 90 sec to 180
sec. (See Table 18.) The blower off delay jumpers are located on
the furnace control (See Fig. 31). To change the blower off delay
setting, move the jumper from one set of pins on the control to the
pins used for the desired blower off delay. Factory blower off
delay setting is 120 sec.

SET THERMOSTAT HEAT ANTICIPATOR

When using a nonelectronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of the electrical
components in R-W circuit. Accurate amp draw readings can be
obtained at thermostat subbase terminals R and W. Fig. 58
illustrates the easy method of obtaining actual amp draw. The amp
reading should be taken after blower motor has started and furnace
is heating. Connect ammeter wires as shown in Fig. 58. The
thermostat anticipator should NOT be in the curcuit while mea-
suring current. If thermostat has no subbase, the thermostat must

Table 15–Altitude Derate Multipler for U.S.A.

ALTITUDE

(FT)

PERCENT

OF DERATE

DERATE MULTIPLIER

FACTOR*

0–2000

0

1.00

2001–3000

4–6

0.95

3001–4000

6–8

0.93

4001–5000

8–10

0.91

5001–6000

10–12

0.89

6001–7000

12–14

0.87

7001–8000

14–16

0.85

8001–9000

16–18

0.83

9001–10,000

18–20

0.81

* Derate multiplier factors are based on midpoint altitude for altitude range.

Table 16—Gas Rate (cu ft/hr)

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

Cu Ft

2

Cu Ft

5

Cu Ft

1

Cu Ft

2

Cu Ft

5

Cu Ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

124

29

58

145

55

Содержание 58MXB Series

Страница 1: ...ons 19 Air Ducts 21 General Requirements 21 Ductwork Acoustical Treatment 21 Supply Air Connections 21 Return Air Connections 21 Filter Arrangement 22 Bottom Closure Panel 23 Gas Piping 23 Electrical Connections 24 115 v Wiring 25 24 v Wiring 26 Accessories 26 Removal of Existing Furnaces from Common Vent Systems 27 Combustion Air and Vent Pipe Systems 27 Condensate Drain 41 General 41 Application...

Страница 2: ...nal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation The 58MXB Multipoise Condensing Gas Fired Furnaces are CSA formerly AGA and CGA design certified for natural and propane gases see furnace rating plate and ...

Страница 3: ...OTTOM INLET 18 1 4 22 11 16 CONDENSATE DRAIN TRAP LOCATION DOWNFLOW HORIZONTAL RIGHT OR ALTERNATE 1 2 IN DIA GAS CONN 2 IN COMBUSTION AIR CONN 1 2 IN DIA GAS CONN 7 8 IN DIA POWER CONN 1 2 IN DIA THERMOSTAT ENTRY 2 IN VENT CONN DIMPLE LOCATORS FOR HORIZONTAL HANGING 14 1 2 TYP SIDE INLET NOTES 1 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufactu...

Страница 4: ... to remove drywall dust and construction debris from all HVAC system components after construction is completed After construction is complete verify furnace operating condi tions including ignition input rate temperature rise and vent ing according to the manufacturer s instructions The furnace shall be installed so that the electrical components are protected by water These furnaces are shipped ...

Страница 5: ... This furnace is approved for UPFLOW DOWNFLOW and HORIZONTAL installations Cette fournaise est approuvée pour l installation HORIZONTALE et la circulation d air VERS LE HAUT et VERS LE BAS BOTTOM DESSOUS 0 Ø 3 0 0 TOP PLENUM DESSUS CHAMBRE D AIR 1 0 24 MIN ALL POSITIONS DOWNFLOW POSITIONS I HORIZONTAL POSITIONS S I DE C O T E S F R O N T A V A N T B C K A R R I E A E R S E R VI E C LÈNTR T E N E I...

Страница 6: ... condensing furnace is available in model sizes ranging from input capacities of 40 000 to 138 000 Btuh as direct vent 2 pipe application and in model sizes ranging from input capacity of 40 000 to 120 000 Btuh as non direct vent 1 pipe application APPLICATIONS Step 1 General Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig 1 All drain a...

Страница 7: ...Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room 4 Install condensate trap into left hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position 5 Fill unused condensate trap casing holes with plastic ...

Страница 8: ... Upper Inducer Housing Drain Connection Attached to the UPPER unused inducer housing drain connection is a cap and clamp This cap is used to prevent condensate leakage in this application Ensure this connection is capped NOTE See Fig 6 or 7 or tube routing label on main furnace door to check for proper connections CONDENSATE TRAP FREEZE PROTECTION Refer to Condensate Drain Protection section for r...

Страница 9: ...llector box drain tube blue and white striped label to condensate trap Tube does not need to be cut b Clamp tube to prevent any condensate leakage 2 Condensate Trap Located on Right Side of Casing a Install drain tube coupling factory supplied in loose parts bag into collector box drain tube blue and white striped label which was previ ously plugged b Connect larger diameter drain tube factory sup...

Страница 10: ...in Protection section for recommenda tions and procedures Step 4 Horizontal Left Supply Air Discharge Applications A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace and conditioned air is discharged to the left CONDENSATE TRAP LOCATION The condensate trap must be removed from the factory installed blower shelf locati...

Страница 11: ...enda tions and procedures CONSTRUCT A WORKING PLATFORM Construct working platform where all required furnace clearances are met See Fig 3 and 11 or 12 UNIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit operation The condensate trap MUST be installed below furnace See Fig 5 for dimensions The drain connection to condensate trap must also be properly sloped to an ope...

Страница 12: ... CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS Fig 12 Attic Location and Working Platform for Non Direct Vent 1 pipe Applications Sizes 040 Through 120 Only A96184 VENT MANUAL SHUTOFF GAS VALVE SEDIMENT TRAP CONDENSATE TRAP DRAIN ACCESS OPENING FOR TRAP 30 IN MIN WORK AREA A 12 IN MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT 5 TO 8 FT VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE ...

Страница 13: ... shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room 4 Install condensate trap into left hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position 5 Fill unused condensate trap casing holes with plastic filler caps factory supplied in loose parts bag CO...

Страница 14: ...and procedures CONSTRUCT A WORKING PLATFORM Construct working platform where all required furnace clearances are met See Fig 3 and 11 or 12 UNIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit operation The condensate trap MUST be installed below furnace See Fig 5 for dimensions The drain connection to condensate trap must also be properly sloped to an open drain NOT...

Страница 15: ...e ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed After construction is complete verify furnace operating conditions including ignition input rate temperature rise and venting according to the manufacturer s instructions UNIT DAMAGE HAZARD Failure to follow this caution may result in minor ...

Страница 16: ...al must be made between the furnace cabinet and the return air duct to prevent pulling air from the burner area and from draft safeguard opening CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in peronal injury or death The operation of exhaust fans kitchen ventilation fans clothes dryers attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at th...

Страница 17: ...the space Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223 1 2002 NFPA 54 2002 8 3 2 2 1 For other than fan assisted appliances such as a draft hood equipped water heater 2 For fan assisted appliances such as this furnace Table 1 Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors FURNACE INPUT BTUH ...

Страница 18: ...ngs exposed to the outdoors have a continu ous sealed vapor barrier Openings are gasketed or sealed and b Doors and openable windows are weatherstripped and c Other openings are caulked or sealed These include joints around window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines etc NOTE In determin...

Страница 19: ... dimensions specified in Table 3 and Fig 21 3 Construct plenum to dimensions specified in Table 3 and Fig 21 4 If downflow subbase KGASB is used install as shown in Fig 22 If Coil Assembly Part No CD5 or CK5 or Coil Box Part No KCAKC is used install as shown in Fig 20 NOTE Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase To remove...

Страница 20: ...plications on Combustible Flooring NOT Using KGASB Subbase Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box 19 19 20 20 24 1 2 Upflow Applications 23 24 1 8 23 5 8 24 3 4 Downflow Applications on Non Combustible Flooring 22 7 8 19 23 1 2 19 5 8 Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box 22 1 8 19 23 3 ...

Страница 21: ... air conditioning coil casing when used DO NOT cut main furnace casing to attach supply side air duct humidifier or other accessories All accessories MUST be connected external to furnace main casing Downflow Furnaces Connect supply air duct to supply air opening on furnace The supply air duct attachment must be connected to ONLY furnace supply outlet or air conditioning coil casing when used when...

Страница 22: ...Through 120 Only A05054 NOTES ANGLE IRON OR EQUIVALENT B A ROD LOCATION USING DIMPLE LOCATORS SEE DIMENSIONAL DWG FOR LOCATIONS 13 16 IN MAX ALTERNATE SUPPORT LOCATION FROM BACK ALTERNATE SUPPORT LOCATION 4 IN MIN 8 IN MAX 3 8 IN ROD A B A B B A 1 A 1 In clearance minimum between top of furnace and combustible material 2 The entire length of furnace must be supported when furnace is used in horizo...

Страница 23: ...re panel perform following 1 Tilt or raise furnace and remove 2 screws holding front filler panel See Fig 28 2 Rotate front filler panel downward to release holding tabs 3 Remove bottom closure panel 4 Reinstall front filler panel and screws Step 7 Gas Piping Gas piping must be installed in accordance with national and local codes Refer to current edition of NFGC in the United States Canadian inst...

Страница 24: ...ediately upstream of gas supply connection to furnace and downstream of manual shutoff valve Gas line grommet factory supplied loose parts bag should be used when installing gas piping Gas line entry hole filler plug should be installed in unused gas line entry hole See Fig 30 NOTE The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES ...

Страница 25: ...ust be located within sight from and readily accessible to furnace NOTE Proper polarity and proper grounding must be maintained for 115 v wiring If polarity is incorrect control LED status indicator will flash rapidly and furnace will NOT operate Fig 30 Typical Gas Pipe Arrangement A05057 COMBUSTION AIR PIPE GROMMETS GAS LINE GROMMET GAS LINE COMBUSTION AIR PIPE VENT PIPE VENT PIPE GROMMET UNUSED ...

Страница 26: ...ontains a 3 amp automotive type fuse located on furnace control See Fig 36 Any electrical shorts of 24 v wiring during installation service or maintenance may cause fuse to blow If fuse replace ment is required use only a fuse of identical size 3 amp and type The control will flash code 24 when fuse needs replacement NOTE Use AWG No 18 color coded copper thermostat wire for lengths up to 100 ft Fo...

Страница 27: ...ny other appliances when resizing vent systems or vent connectors system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSC NGPIC The 58MXB can be vented as either a direct vent all sizes or as a non direct vent except for 140 size application A direct vent system shall be installed in accordance with the direct vent 2 pipe procedures...

Страница 28: ...M 24VAC HUMIDIFIER CONNECTION 0 5 AMP MAX IDM INDUCED DRAFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PR...

Страница 29: ...ust conform to American National Standards Institute ANSI stan dards and American Society for Testing and Materials ASTM standards See Table 7 for approved materials for use in the U S A FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in fire property damage personal injury or death Solvent cements are combustible Keep away from heat sparks and open flame Use only in well ven...

Страница 30: ...ht portion of combustion air inlet pipe from Fig 38 3 Cut field supplied 2 in diameter PVC pipe to length as determined per Fig 38 4 Permanently attach elbow perforated disk assembly to straight portion of pipe using RTV or by cementing as shown in Fig 38 Assembly of Combustion Air Pipe Direct Vent 2 Pipe System ONLY 1 Using Table 11 determine the smallest combustion air diam eter permitted Pick t...

Страница 31: ...Table 8 Direct Vent Termination Clearance A05009 31 ...

Страница 32: ... Table 9 Other than Direct Vent Termination Clearance A05013 32 ...

Страница 33: ...g as a guide Install a field supplied No 6 or No 8 sheet metal screw NOTE DO NOT OVERTIGHTEN SCREW Breakage of intake housing or fitting may cause air leakage to occur A plugged drain connection has been provided on this fitting for use when moisture is found in combustion air intake pipe and combustion box If use of this drain connection is desired drill out fitting s tap plug with 3 16 in drill ...

Страница 34: ...nst inducer housing Clamp must be tightened to prevent any condensate leakage 4 Install pipe grommet factory supplied in loose parts bag into selected furnace casing vent pipe hole 5 Be certain that mating surfaces of inducer housing connection elastomeric rubber coupling and 2 in diameter vent pipe are clean and dry Assemble the elastomeric rubber vent cou pling with 2 loose clamps onto inducer h...

Страница 35: ... 70 70 70 70 70 60 000 2 Pipe or 2 in Concentric 1 1 2 1 1 2 17 12 7 NA NA NA 2 2 70 67 66 61 61 61 80 000 2 Pipe or 2 in Concentric 2 2 49 44 30 25 25 15 2 1 2 2 1 2 70 70 70 70 70 70 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 35 26 16 16 6 NA 3 3 70 70 70 70 66 61 120 000 2 Pipe or 3 in Concentric 3 NA 14 9 NA NA NA NA NA 3 63 62 62 61 61 61 3 no disk NA 70 70 63 56 50 43 4 no disk 4 no disk ...

Страница 36: ...0 70 70 70 70 70 60 000 2 Pipe or 2 in Concentric 1 1 2 1 1 2 14 9 NA NA NA NA 2 2 60 55 54 49 48 47 80 000 2 Pipe or 2 in Concentric 2 2 41 36 23 18 17 8 2 1 2 2 1 2 70 70 70 70 70 70 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 29 21 12 11 NA NA 3 3 70 67 62 57 52 47 120 000 2 Pipe or 3 in Concentric 3 no disk NA 42 35 29 22 15 9 NA 3 53 52 50 49 48 47 4 no disk 4 no disk 70 70 70 70 70 70 140 ...

Страница 37: ...UMBER OF 90 ELBOWS TERMINATION TYPE PIPE DIA IN PIPE DIA IN 1 2 3 4 5 6 9001 to 10 000 40 000 2 Pipe or 2 in Concentric 1 1 2 1 1 2 42 37 32 27 25 20 2 2 57 55 53 51 49 47 60 000 2 Pipe or 2 in Concentric 2 2 45 40 38 33 31 29 80 000 2 Pipe or 2 in Concentric 2 2 30 25 14 9 7 NA 2 1 2 2 1 2 57 55 53 51 49 47 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 21 13 5 NA NA NA 3 3 54 49 44 39 34 29 120 0...

Страница 38: ... PIPE COMBUSTION AIR PIPE NON DIRECT VENT 1 PIPE COMBUSTION AIR PIPE DIRECT VENT 2 PIPE COMBUSTION AIR PIPE NON DIRECT VENT 1 PIPE COMBUSTION AIR PIPE DIRECT VENT 2 PIPE COMBUSTION AIR PIPE NON DIRECT VENT 1 PIPE COMBUSTION AIR PIPE DIRECT VENT 2 PIPE Fig 39 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration A93034 FURNACE PIPE DIAMETER TRANSITION IN VERTICAL SECTION...

Страница 39: ...bottom of combustion air and bottom of vent Maintain 12 in min clearance above highest anticipated snow level or grade whichever is greater A At least 36 in A Maintain 12 in min clearance above highest anticipated snow level Maximum of 24 in above roof 90 Note A denotes 0 to 2 in Fig 43 Vent Pipe Termination for Non Direct Vent 1 pipe System Sizes 040 Through 120 Only A05091 Abandoned masonry used...

Страница 40: ... An 080 12 size furnace located in Indianapolis elevation 650 ft above sea level could be installed as either a direct vent 2 pipe system that requires 3 elbows and 32 ft of vent pipe along with 5 elbows and 34 ft of combustion air pipe OR a non direct vent 1 pipe system that requires 3 elbows and 32 ft vent pipe For a direct vent 2 pipe system Table 11 indicates this application would allow a 2 i...

Страница 41: ... in section Vent Termination General in this instruction 1 Cut 2 holes 1 for each pipe of appropriate size for pipe size being used 2 Loosely install elbow in bracket and place assembly on combustion air pipe Roof terminations Loosely install pipe coupling on prop erly cut vent pipe Coupling must be positioned so bracket will mount as shown in Fig 42 For applications using combustion air pipe opti...

Страница 42: ... tape in half and wrap on itself 3 times 2 Locate heat tape between sides of condensate trap back See Fig 45 3 Use wire ties to secure heat tape in place Wire ties can be positioned in notches of condensate trap sides See Fig 45 4 Wrap field drain pipe with remaining heat tape approximately 1 wrap per ft 5 When using field supplied heat tape follow heat tape manu facturer s instructions for all ot...

Страница 43: ...s leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all connections Step 4 Sequence of Operation FURNACE MAY NOT OPERATE Failure to follow this caution may result in furnace operation stopping and water pipes freezing during cold weather Furnace control must be grounded for proper operation or control will lock out Control is ...

Страница 44: ...he thermostat calls for cooling a Single Speed Cooling See Fig 27 50 52 and 54 for thermostat connections The thermostat closes the R to G and Y circuits The R to Y circuit starts the outdoor unit and the R to G and Y Y2 circuits start the furnace blower motor BLWM on COOL speed The electronic air cleaner terminal EAC 1 is energized with 115 vac when the blower motor BLWM is operating When the the...

Страница 45: ... Single Speed Air Conditioner Fig 49 Single Stage Furnace with Two Speed Air Conditioner A00269 A00270 Fig 50 Single Stage Furnace with Single Speed Heat Pump Dual Fuel A00271 Fig 51 Single Stage Furnace with Two Speed Heat Pump Dual Fuel 45 ...

Страница 46: ...Single Stage Furnace and Single Speed Heat Pump HUMIDFIER 24VAC A02103 Fig 53 Dual Fuel Thermostat with Single Stage Furnace and Two Speed Heat Pump HUMIDFIER 24VAC A02161 Fig 54 Two Stage Thermostat with Single Stage Furnace and Two Speed Air Conditioner 46 ...

Страница 47: ...d of the prepurge period then shut off for 24 seconds then come back on at HEAT speed When the W input signal disappears the furnace control begins a normal inducer post purge period and the blower remains running at HEAT speed for the selected blower OFF delay period then switches to low cool speed same speed as FAN If the R to W and Y1 and G signals disappear at the same time the blower motor BL...

Страница 48: ... No Manifold Pressure U S A and Canada U S A 775 43 3 8 42 3 2 42 3 3 42 3 4 42 3 5 Altitudes 800 43 3 5 43 3 7 43 3 8 42 3 2 42 3 3 2001 to 825 44 3 8 43 3 4 43 3 6 43 3 7 43 3 8 3000 850 44 3 6 44 3 7 44 3 8 43 3 5 43 3 6 or 875 44 3 4 44 3 5 44 3 6 44 3 7 43 3 4 Canada 900 44 3 2 44 3 3 44 3 4 44 3 5 44 3 6 Altitudes 925 45 3 7 45 3 8 44 3 2 44 3 3 44 3 4 2001 to 950 45 3 5 45 3 6 45 3 7 45 3 8...

Страница 49: ...5 3 6 45 3 7 44 3 2 44 3 3 44 3 4 to 850 45 3 4 45 3 5 45 3 6 45 3 8 44 3 2 875 45 3 2 45 3 3 45 3 4 45 3 6 45 3 7 6000 900 45 3 0 45 3 1 45 3 3 45 3 4 45 3 5 925 45 2 9 45 3 0 45 3 1 45 3 2 45 3 3 950 45 2 7 45 2 8 45 2 9 45 3 0 45 3 1 11 975 45 2 6 45 2 7 45 2 8 45 2 9 45 2 9 derate 1000 45 2 5 45 2 5 45 2 6 45 2 7 45 2 8 ALTITUDE RANGE Ft Avg GAS HEAT VALUE AT ALTITUDE Btu cu ft SPECIFIC GRAVIT...

Страница 50: ...o Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A Only 600 43 3 8 42 3 3 42 3 4 42 3 5 42 3 6 625 43 3 5 43 3 6 43 3 8 42 3 2 42 3 3 8001 650 44 3 7 43 3 4 43 3 5 43 3 6 43 3 7 675 44 3 5 44 3 6 44 3 7 44 3 8 43 3 4 to 700 44 3 2 44 3 3 44 3 4 44 3 6 44 3 7 725 45 3 6 45 3 8 44 3 2 44 3 3 44 3 4 9000 750 45 3 4 45 3 5 45 3 6 45 3 8 44 ...

Страница 51: ...ing plate adjusted for altitude 1 Determine natural gas orifice size and manifold pressure for correct input a Obtain average gas heat value at installed altitude from local gas supplier b Obtain average gas specific gravity from local gas supplier c Verify furnace model and size Table 13 can only be used for model 58MXB furnaces with rating plate heating inputs 1000 s Btuh of 040 through 120 Tabl...

Страница 52: ...fold Pressure U S A and Canada U S A 775 41 3 7 41 3 8 40 3 6 40 3 7 39 3 6 Altitudes 800 42 3 8 41 3 6 41 3 7 41 3 8 40 3 6 2001 to 825 42 3 6 42 3 7 41 3 5 41 3 6 41 3 7 3000 or 850 42 3 4 42 3 5 42 3 6 42 3 7 41 3 5 Canada 875 42 3 2 42 3 3 42 3 4 42 3 5 42 3 6 Altitudes 900 43 3 7 43 3 8 42 3 2 42 3 3 42 3 4 2001 to 925 43 3 5 43 3 6 43 3 7 42 3 2 42 3 3 4500 950 43 3 3 43 3 4 43 3 5 43 3 7 43...

Страница 53: ...ure U S A Only 700 41 3 5 41 3 7 41 3 8 40 3 6 40 3 7 725 42 3 7 42 3 8 41 3 5 41 3 6 41 3 8 750 42 3 4 42 3 5 42 3 7 42 3 8 41 3 5 775 42 3 2 42 3 3 42 3 4 42 3 5 42 3 7 5001 800 43 3 7 43 3 8 42 3 2 42 3 3 42 3 4 825 43 3 5 43 3 6 43 3 7 43 3 8 42 3 2 to 850 43 3 3 43 3 4 43 3 5 43 3 6 43 3 7 875 43 3 1 43 3 2 43 3 3 43 3 4 43 3 5 6000 900 43 2 9 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 7 43 2 8 43 ...

Страница 54: ...ve sea level See Table 15 for derate multiplier factor CANADA At installation altitudes between 2001 to 4500 ft this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer To determine correct input rate for altitude see example above and use 0 95 as derate multiplier factor b Reinstall burner box cover c Gas valve regulator seal cap MUST be on d Turn off all other gas...

Страница 55: ...s used for the desired blower off delay Factory blower off delay setting is 120 sec SET THERMOSTAT HEAT ANTICIPATOR When using a nonelectronic thermostat the thermostat heat anticipator must be set to match the amp draw of the electrical components in R W circuit Accurate amp draw readings can be obtained at thermostat subbase terminals R and W Fig 58 illustrates the easy method of obtaining actua...

Страница 56: ... 2 Remove outer furnace door and disconnect inducer motor from wire harness 3 Turn on 115 v power to furnace 4 Set thermostat to call for heat and wait 1 minute When pressure switch is functioning properly hot surface igniter should NOT glow and control status code LED flashes a Status Code 31 If hot surface igniter glows when inducer motor is disconnected shut furnace down immediately De termine ...

Страница 57: ...________ Pipe Sloped To Furnace Pipe Insulation ________ Over Ceilings ________ Low Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks and Traps ________ External Drain Connection Leak Tight and Sloped ________ Condensate Trap Primed before Start Up ________ Heat Tape Installed if Required CHECKLIST START UP ________ Gas...

Страница 58: ... ________ Low Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks and Traps ________ External Drain Connection Leak Tight and Sloped ________ Condensate Trap Primed before Start Up ________ Heat Tape Installed if Required CHECKLIST START UP ________ Gas Input Rate Set Within 2 percent of Rating Plate ________ Temperature ...

Страница 59: ...59 ...

Страница 60: ...s IN 46231 58mxb1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Printed in U S A Catalog No 58MXB 1SI Pg 60 8 05 Replaces 58MXA 18SI ...

Отзывы: