Circulation Air Blower Data -- 58HDV080
Cooling Adjustment
Heating Rise Adjustment
DIP Switch
(OFF = 0
ON = 1)
High Cool @ .50
in wc(125 Pa)
Low Cool (80%
of High Cool)
** Adjust
Jumper
Setting
DIP Switch
(OFF = 0
ON = 1)
High Heat
Rise
Change @
0.20 in wc
(50 Pa)
Low Heat
Rise
Change at
Resultant
Static
5 & 6
CFM
L/s
CFM
L/s
3 & 4
00
2146
1013
1717
1013
+
00
--3
--3
*00
2009
948
1607
948
*NOM
*00
0
0
00
1843
870
1474
870
--
00
5
5
01
1779
840
1423
840
+
01
3
3
01
1645
776
1316
776
NOM
01
6
8
01
1498
707
1198
707
--
01
11
11
10
1409
665
1127
665
+
10
0
0
10
1294
611
1035
611
NOM
10
6
4
10
1147
541
918
541
--
10
10
9
11
1005
474
804
474
+
11
--5
--6
11
887
419
710
419
NOM
11
--2
--2
11
757
357
606
357
--
11
3
2
Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is
present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory
default settings.
Table 2
Airflow
DIP Switch
(OFF = 0 / ON = 1)
Continuous Fan @
0.10 in wc (25 Pa) ESP
1 & 2
CFM
L/s
*00
1007
475
01
1742
822
10
2204
1040
11
2204
1040
* Factory Setting
Table 3
SW2 DIP Assignments
DIP Switch
Blower Parameter
1 & 2
Cont Fan Adj
3 & 4
Heat Speed Adj
5 & 6
Cool Speed Adj
7 & 8
Cool On/Off Delay
Table 4
Cooling Delay Options (SW2 -- 7, 8)
ON DELAY
OFF DELAY
DIP SW2 -- 7/8
(OFF = 0 / ON = 1)
Timed ON (sec)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
delay
*00
5
OFF
90
100%
01
5
OFF
0
OFF
10
30
50%
30
100%
11
30
50%
180
50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting
MAX CFM’s for Factory Washable Filters
Filter Size (in/mm)
CFM
L/s
14
″
X 25
″
/ 356 x 635
1400
661
16
″
X 25
″
/ 406 x 635
1600
755
20
″
X 25
″
/ 508 x 635
2000
944
24
″
X 25
″
/ 610 x 635
2500
1180
Max CFM based on 600 FPM (3.0 M/s)
NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).
These filters only allow half the airflow when compared to 600 FPM (3.0
M/s) filters.
EXAMPLE (approx.):
20in X 25in @ 600 FPM = 2000 CFM, @ 300 FPM = 1000 CFM
508mm x 635mm @ 3.0 M/s = 944 L/s, @ 1.5 M/s = 472 L/s