13
Table 4 – Opening Dimensions -- IN. (mm)
FURNACE
CASING
WIDTH
APPLICATION
PLENUM OPENING
FLOOR OPENING
A
B
C
D
14–3/16
(360)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
12---11/16
(322)
21---5/8
(549)
13---5/16
(338)
22---1/4
(565)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
12---9/16
(319)
19
(483)
13---3/16
(335)
19---5/8
(498)
Downflow applications on combustible flooring (KGASB sub-
base required)
11---13/16
(284)
19
(483)
13---7/16
(341)
20---5/8
(600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
12---5/16
(319)
19
(483)
13---5/16
(338)
20
(508)
17–1/2
(445)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
16
(406)
21---5/8
(549)
16---5/8
(422)
22---1/4
(565)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
15---7/8
(403)
19
(483)
16---1/2
(419)
19---5/8
(498)
Downflow applications on combustible flooring (KGASB sub-
base required)
15---1/8
(384)
19
(483)
16---3/4
(425)
20---5/8
(600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
15---1/2
(394)
19
(483)
16---1/2
(419)
20
(508)
21
(533)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
19---1/2
(495)
21---5/8
(549)
20---1/8
(511)
22---1/4
(565)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
19---3/8
(492)
19
(483)
20
(508)
19---5/8
(498)
Downflow applications on combustible flooring (KGASB sub-
base required)
18---5/8
(473)
19
(483)
20---1/4
(514)
20---5/8
(600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
19
(483)
19
(483)
20
(508)
20
(508)
24---1/2
(622)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
23
(584)
21---1/8
(537)
23---5/8
(600)
22---1/4
(565)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
22---7/8
(581)
19
(483)
23---1/2
(597)
19---5/8
(498)
Downflow applications on Combustible flooring (KGASB sub-
base required)
22---1/8
(562)
19
(483)
23---3/4
(603)
20---5/8
(600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
22---1/2
(572)
19
(483)
23---1/2
(597)
20
(508)
HORIZONTAL INSTALLATION
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward.
Safety control
operation will be adversely affected.
Never connect
return--air ducts to the back of the furnace.
!
WARNING
The furnace can be installed horizontally in an attic or crawl space
on either the left--hand (LH) or right--hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
non--combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod,
angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown.
Heavy--gauge sheet metal straps (plumber’s straps) may be used
to suspend the furnace from each bottom corner. To prevent
screws from pulling out, use 2 #8 x 3/4--in. screws into the side
and 2 #8 x 3/4--in. screws in the bottom of the furnace casing for
each strap. (See Fig. 15 and 16.) If the screws are attached to
ONLY the furnace sides and not the bottom, the straps must be
vertical against the furnace sides and not pull away from the
furnace sides, so that the strap attachment screws are not in
tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.
clearance requirement on side, set furnace on noncombustible
blocks, bricks or angle iron. For crawl space installations, if the
furnace is not suspended from the floor joists, the ground
underneath furnace must be level and the furnace set on blocks or
bricks.
Roll--Out Protection
Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for
flame roll--out protection in front of burner area for furnaces
closer than 12--in. (305 mm) above the combustible deck or
suspended furnaces closer than 12--in. (305 mm) to joists. The
sheet metal MUST extend underneath the furnace casing by 1--in.
(25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17--1/2 in. (445
mm) and larger may be used for flame roll--out protection when
bottom of furnace is used for return air connection. See Fig. 17
for proper orientation of roll--out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove two screws holding bot-
tom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
58D
L