53DFS250-HW
9
69-2565—05
Installer setup
Setup
Number
Setup Name
Settings & Options (factory default in bold)
0695
Recovery Cool Ramp Rate
3
3°F (1.7°C)/hour
[Options: 0–20°F (0–11°C)]
0700
Temperature Display Offset
0
0°F (0.0°C)
[Options: -3–3°F (-1.5–3°C)]
0710
Restore Factory Defaults
0
No
1 Yes
0720
Screen Display
2
Display Both
0 Display Room Temperature
1 Display Setpoint
View
Clock & More
Next
Go Back
AM
Done
M32498
View
Clock & More
Next
Go Back
AM
Done
TEST1
During installer setup, press
NEXT
repeatedly until “Test” appears.
Test
number
System
status
Press
NEXT
to
select test
Press
st
to
change status
Press
DONE
to terminate testing.
1
Installer Test Cool
0 Off
1 Cool Stage 1 On
2
Installer Test Fan
0 Off
1 Low
2 Med
3 High
3
Installer Test Heat
0 Off
1 Heat Stage 1 On
2 Heat Stage 2 On
4
Installer Test EM Heat
0 Off
1 EM Heat On
System test
System status
CAUTION: EQUIPMENT
DAMAGE HAZARD.
Compressor protection is
bypassed during testing.
To prevent equipment
damage, avoid cycling
the compressor quickly.
Installer system test