![Carrier 538FEQ009RBGA Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/carrier/538feq009rbga/538feq009rbga_service-manual_2561763007.webp)
7
CLEARANCES -- INDOOR
6" (0.15m) min.
5"
(0.13m)
min.
6'
5"
(0.13m)
min.
(1.8m)
CEILING
FLOOR
Fig. 7 – Indoor Unit Clearance
CLEARANCES -- OUTDOOR
A
D
B
Air-outlet
Air-inlet
C
E
Fig. 8 – Outdoor Unit Clearance
UNIT
Minimum Value
in. (mm)
A
24 (609)
B
24 (609)
C
24 (609)
D
4 (101)
E
4 (101)
ELECTRICAL DATA
UNIT
SIZE
OPERVOLTAGE
-
MAX / MIN*
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
MCA
MAX FUSE
CB AMP
V/PH/HZ
RLA
LRA
V/PH/HZ
FLA
HP
W
V/PH/HZ
FLA
HP
W
9K
253 / 187
208-230/1/60
8.5
35
208-230/1/60
0.37
0.04
30
208-230/1/60
0.1
0.027
20
12
15
12K
9.5
40
0.37
0.04
30
0.1
0.027
20
13
20
18K
14.5
30
0.48
0.12
90
0.1
0.027
20
19
30
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
Содержание 538FEQ009RBGA
Страница 6: ...6 DIMENSIONS OUTDOOR Fig 3 Dimensions Fig 4 Dimensions Fig 5 Dimensions Fig 6 Dimensions...
Страница 10: ...10 Outdoor Unit Fig 11 Sizes 09 12...
Страница 47: ...47 Shut off power hold both ends of horizontal...
Страница 48: ...48...
Страница 49: ...49...
Страница 50: ...50 ziptie side cutters...
Страница 51: ...51...
Страница 52: ...52...
Страница 53: ...53...
Страница 54: ...54...
Страница 67: ...67 6 7 8...
Страница 68: ...68 9 Remove electric box 10 Remove evaporator...
Страница 69: ...69...
Страница 70: ...70 11 Remove swing blade...
Страница 71: ...71 12 Remove cross flow blade and motor...
Страница 72: ...72 13 Remove drive box...
Страница 84: ...84 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Страница 89: ...89 UNIT BREAKDOWNS a b c d e...
Страница 90: ...90 f g h...
Страница 91: ...91...
Страница 92: ...92...
Страница 93: ...93...