3. High temperature and overload protection (E8) (AP1 below means control board of outdoor unit)
Main detection points:
S
Is the outdoor ambient temperature in normal range?
S
Is the indoor and outdoor fan running normally?
S
Is the condensing unit blocked with dirt and debris?
E8 is displayed
If the outdoor
ambient temperature is higher
than 127°F?
Normal protection, unit starts
when ambient temperature
lowers.
Unit restarts
normally
Unit restarts
normally
Is the unit clear of debris
and the coil is clean?
Clean the heat exchanger
and remove surrounding obstacles
Are the indoor and outdoor
fan running normally?
Are the connections
tight?
Adjust the
connection
Replace outdoor
mainboard
Replace mainboard
Replace Motor
Replace Fan
capacitor
Fan capacitor is broken?
Motor is broken?
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Fig. 32 – Troubleshooting
Содержание 538FEQ009RBGA
Страница 6: ...6 DIMENSIONS OUTDOOR Fig 3 Dimensions Fig 4 Dimensions Fig 5 Dimensions Fig 6 Dimensions...
Страница 10: ...10 Outdoor Unit Fig 11 Sizes 09 12...
Страница 47: ...47 Shut off power hold both ends of horizontal...
Страница 48: ...48...
Страница 49: ...49...
Страница 50: ...50 ziptie side cutters...
Страница 51: ...51...
Страница 52: ...52...
Страница 53: ...53...
Страница 54: ...54...
Страница 67: ...67 6 7 8...
Страница 68: ...68 9 Remove electric box 10 Remove evaporator...
Страница 69: ...69...
Страница 70: ...70 11 Remove swing blade...
Страница 71: ...71 12 Remove cross flow blade and motor...
Страница 72: ...72 13 Remove drive box...
Страница 84: ...84 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Страница 89: ...89 UNIT BREAKDOWNS a b c d e...
Страница 90: ...90 f g h...
Страница 91: ...91...
Страница 92: ...92...
Страница 93: ...93...