52
INDOOR-FAN MOTOR PERFORMANCE
LEGEND
BHP —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using your fan motors
up to the horsepower ratings shown in this table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
†Single-phase/three-phase.
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
UNIT
50TFQ
INDOOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
004
Standard
208/230
0.34
440
3.3
460
1.8
575
1.8
Alternate
208/230
1.00
1000
5.1
460
2.2
575
2.2
High Static
208/230
2.40
2120
6.1
460
2.7
575
2.7
005
Standard
208/230
0.75
850
3.1
460
1.9
575
1.9
Alternate
208/230
1.00
1000
5.1
460
2.2
575
2.2
High Static
208/230
2.40
2120
6.1
460
2.7
575
2.7
006
Standard
208/230
1.20
1340
6.2
460
3.4
575
3.4
Alternate
208/230
1.30/2.40†
2120
9.2/6.1†
460
2.7
575
2.7
High Static
208/230
2.90
2562
6.1
460
2.7
575
2.7
007
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
High Static
208/230
2.90
2562
7.9
460
3.6
575
3.6
008
Standard,
Alternate
208/230
2.40
2120
6.1
460
2.7
575
2.7
High Static
208/230
3.70
3313
11.1
460
5.0
575
5.0
009
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
High Static
208/230
3.70
3313
11.1
460
5.0
575
5.0
012
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
Alternate
208/230
2.90
2615
7.9
460
3.6
575
3.6
High Static
208/230
5.25
4400
15.0
460
7.4
575
7.4
Performance data (cont)