51
ELECTRIC HEATING CAPACITIES
*Two heater packages required to provide kW indicated.
NOTES:
1. The kW ratings shown above are at 240, 480, and 575 v. Use the Multiplication Factors table below
to determine heater capacity for your particular voltage.
2. Heaters are not available for size 004-007, 575-v units.
MULTIPLICATION FACTORS
EXAMPLE: 32.0 kW (at 240 v) heater on 208 v
= 32.0 (.75 mult factor)
= 24.0 kW capacity at 208 v.
UNIT
50TFQ
VOLTAGE
(60 Hz)
ACCESSORY
kW
004
208/230
(single phase)
4.4
6.5
8.7
10.5
13.0*
208/230
(3 phase)
4.4
6.5
8.7
10.5
16.0
460
(3 phase)
6.0
8.8
11.5
14.0
005
208/230
(single phase)
4.4
8.7
13.0*
17.4*
21.0*
208/230
(3 phase)
6.5
8.7
16.0
21.0*
460
(3 phase)
6.0
11.5
14.0
23.0*
006
208/230
(single phase)
6.5
8.7
13.0*
17.4*
21.0*
208/230
(3 phase)
6.5
10.5
16.0
21.0*
26.5*
460
(3 phase)
6.0
11.5
14.0
23.0*
25.5*
UNIT
50TFQ
UNIT
VOLTAGE
(60 Hz)
ACCESSORY
kW
007
208/230
(3 phase)
6.5
10.5
16.0
21.0*
26.5*
460
(3 phase)
6.0
11.5
14.0
23.0*
25.5*
008,009
208/230
(3 phase)
10.5
16.0
24.8
32.0*
42.4*
460
(3 phase)
14.0
16.5
27.8
33.0
41.7*
575
(3 phase)
17.0
34.0
012
208/230
(3 phase)
10.4
16.0
32.0
42.4*
50.0*
460
(3 phase)
16.5
27.8
33.0
41.7*
50.0*
575
(3 phase)
17.0
34.0
51.0*
HEATER RATING
VOLTAGE
VOLTAGE
DISTRIBUTION
V-3-60
MULTIPLICATION
FACTOR
240
200
0.69
208
0.75
230
0.92
240
1.00
480
440
0.84
460
0.92
480
1.00
575
545
0.90
575
1.00
600
1.09