IMPORTANT

: The gasketing of the unit to the roof curb is critical

for a watertight seal. Install gasket with the roof curb as shown in
Fig. 1. Improperly applied gasket can also result in air leaks and
poor unit performance. Do not slide unit to position on roof curb.

Alternate Unit Support

When a curb cannot be used, install unit on a noncombustible

surface. Support unit with sleepers, using unit curb support area. If
sleepers cannot be used, support long sides of unit with a minimum

of 3 equally spaced 4-in. x 4-in. pads on each side.

Step 2 — Rig and Place Unit

Inspect unit for transportation damage. See Table 1 for physical
data. File any claim with transportation agency.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
All panels must be in place when rigging.

CAUTION

!

Do not drop unit; keep upright. Use spreader bars or top crating
over unit to prevent sling or cable damage. Rollers may be used to

move unit across a roof. Level by using unit rail as a reference;
leveling tolerance is

±

1

/

16

in. per linear ft in any direction. See Fig.

2 for additional information. Unit rigging weight is shown in Fig.

2.
Rigging holes are provided in the unit base rails as shown in Fig. 2.

Refer to rigging instructions on unit.

Positioning

Maintain clearance, per Fig. 3, around and above unit to provide
minimum distance from combustible materials, proper airflow, and

service access.
Do not install unit in an indoor location. Do not locate air inlets

near exhaust vents or other sources of contaminated air.
After unit is in position, remove top crating and polyethylene
sheet.

Roof Mount

Check building codes for weight distribution requirements. Unit

operating weight is shown in Table 1.

Installation Onto Curb

The 50PG units are designed to fit on the accessory full perimeter

curb. Correct placement of the unit onto the curb is critical to
operating performance. To aid in correct positioning, place unit on

roof curb to maintain

1

/

4

-in. gap between the inside of rail and roof

curb on long sides and a

1

/

2

-in. gap between the inside of rail and

roof curb on both duct and condenser ends. Refer to Fig. 1 and 3,

to assure proper duct opening alignment.

NOTE

: Before positioning unit on curb make sure bottom drain

connection plug is tight. See Step 6 — Install External Trap for
Condensate Drain for details.

Hook rigging shackles through holes in base rail, as shown in 
Detail A.  Holes in base rails are centered around the unit 
center of gravity.  Use wooden top skid, when rigging, to 
prevent rigging straps from damaging unit.

CAU

O

TI

ACCESS PANEL MUST BE IN PLACE WHEN RIGGING.

N - NOTICE  TO  R GGERS:

I

UNIT

SIZE

A

B

C

D

E

MAX. WEIGHT

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

lb

kg

16

100.4

2550

36-54

914-1371

52.4

1331

51.0

1295

35.0

889

1959

890

C06253

Fig. 2 -- 50PG Rigging Label

50PG16

Содержание 50PG16 series

Страница 1: ...tions Have fire extinguishers available for all brazing operations ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintena...

Страница 2: ...2 C06310 Fig 1 Base Unit Dimensions 50PG16...

Страница 3: ...d and above unit to provide minimum distance from combustible materials proper airflow and service access Do not install unit in an indoor location Do not locate air inlets near exhaust vents or other...

Страница 4: ...Aluminum Lanced Fins Face Split Condenser A Outer Rows Fins in 2 17 Face Area sq ft 26 6 Condenser B Inner Rows Fins in 2 17 Face Area sq ft 30 2 Humidi MiZer Coil Enhanced Copper Tubes Aluminum Lanc...

Страница 5: ...47 8 High 43 8 Belt Type Low AX Mid Low BX High BX Pulley Center Line Distance Min in Low 14 2 Mid Low 10 8 High 8 6 Pulley Center Line Distance Max in Low 10 8 Mid Low 14 2 High 12 Speed Change rpm L...

Страница 6: ...6 C06306 Fig 3 Roof Curb Details 50PG16...

Страница 7: ...turn AIR OUT AIR IN AIR OUT ECONOMIZER C06308 Fig 5 Air Distribution Concentric Duct Horizontal Applications Horizontal units are shipped with an outer panel that allows for side by side horizontal du...

Страница 8: ...TRICAL OPTIONS PANEL BASEPAN CONNECTIONS ACCESS PANEL CONTROL BOX AND COMPRESSOR ACCESS DOOR FILTER ACCESS DOOR ELECTRIC HEAT ACCESS PANEL CONDENSER COIL ACCESS PANEL C06309 Fig 6 Panel and Filter Loc...

Страница 9: ...tails refer to the Controls Start up Operation and Troubleshooting manual All 208 230 v units are factory wired for 230 v power supply If the 208 230 v unit is to be connected to a 208 v power supply...

Страница 10: ...4 95 533 533 20 256A00 104 2 120 3 37 6 50 0 158 3 148 3 175 175 034 146 164 533 533 20 257A00 156 3 180 4 56 3 75 0 184 3 208 4 200 250 034 206 233 533 533 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1...

Страница 11: ...538 20 256A00 104 2 120 3 37 6 50 0 164 3 153 7 175 175 034 151 170 538 538 20 257A00 156 3 180 4 56 3 75 0 190 4 213 9 200 250 034 211 239 538 538 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1 0 Low 4...

Страница 12: ...e unit shall be fuse or HACR breaker 2 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the pe...

Страница 13: ...or wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into...

Страница 14: ...g 11 13 NOTE For wire runs up to 50 ft use no 18 AWG American Wire Gauge insulated wire 35 C minimum For 50 to 75 ft use no 16 AWG insulated wire 35 C minimum For over 75 ft use no 14 AWG insulated wi...

Страница 15: ...must be configured correctly refer to the Controls Start up Operation and Troubleshooting manual for details If the customer also wishes to install a smoke detector into a Humidi MiZer equipped 50PG...

Страница 16: ...ic relief hoods Repeat for second hood Install baffle between the outdoor air hoods with the screws saved from item 1 See Fig 17 Step 8 Install All Accessories After all of the factory installed optio...

Отзывы: