50PG16
Single Package Rooftop Units
Electric Cooling with PURON
R
(R---410A) Refrigerant
and
COMFORT
Link
t
Controls
Installation Instructions
IMPORTANT
: This installation instruction contains basic unit
installation information including installation of field control
devices. For information on unit start-up, service, and operation,
refer to the unit Controls, Start-Up, Operation, Service, and
Troubleshooting Instructions also enclosed in the unit literature
packet.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION
1-16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 -- Provide Unit Support
1
. . . . . . . . . . . . . . . . . . . . . . . . .
Step 2 -- Rig and Place Unit
3
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 3 -- Field Fabricate Ductwork
7
. . . . . . . . . . . . . . . . . . . . . .
Step 4 -- Make Unit Duct Connections
7
. . . . . . . . . . . . . . . . . . .
Step 5 -- Install External Trap for Condensate Drain
7
. . . . . . . .
Step 6 -- Make Electrical Connections
9
. . . . . . . . . . . . . . . . . . .
Step 7 -- Install Outdoor--Air Hoods
(Units with Economizer)
15
. . . . . . . . . . . . . . . . . . . . .
Step 8 -- Install All Accessories
16
. . . . . . . . . . . . . . . . . . . . . . .
Step 9 -- Configure Controls
16
. . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions
of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions
in the literature, tags and labels attached to the unit, and other
safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. There may be
more than one disconnect switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury
or equipment damage.
Puron
r
(R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron
r
refrigerant
equipment.
CAUTION
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
!
WARNING
IMPORTANT
: Units have high ambient operating limits. If limits
are exceeded, the units will automatically lock the compressor out
of operation.
Manual reset will be required to restart the
compressor.
INSTALLATION
Step 1 — Provide Unit Support
Roof Curb
Assemble or install accessory roof curb in accordance with
instructions shipped with this accessory. See Fig. 1. Install
insulation, cant strips, roofing, and counter flashing as shown.
Ductwork can be installed to roof curb before unit is set in place.
Ductwork must be attached to curb and not to the unit. Curb must
be level. This is necessary to permit unit drain to function properly.
Unit leveling tolerance is
±
1
/
16
in. per linear ft in any direction.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required. When accessory roof curb is
used, unit may be installed on class A, B, or C roof covering
material. Carrier roof curb accessories are for flat roofs or slab
mounting.