13
Table 2 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts-Ph-Hz
VOLTAGE
RANGE
COMPRESSOR
(Each)
OFM
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRIC HEAT
POWER SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
Qty FLA
FLA
Nominal
kW*
MCA
MOCP†
FLA
LRA
12
208/230-3-60
187
253
17.6
123
2
1.9
—
Low
7.5
—
—
50.9/ 50.9
60/ 60
53/ 53 310/310
20.0/ 23.1
7.5/10.0
50.9/ 50.9
60/ 60
53/ 53 310/310
30.0/ 34.6
11.3/15.0
50.9/ 52.6
60/ 60
53/ 53 310/310
50.0/ 57.7
18.8/25.0
71.9/ 81.5
80/ 90
66/ 75 310/310
70.0/ 80.8
26.3/35.0
96.9/110.4 100/125
89/102 310/310
80.0/ 92.4
30.0/40.0
109.4/124.9 110/125 101/115 310/310
100.1/115.5
37.6/50.0
134.5/124.9 150/150 124/141 310/310
High
10.2
—
—
53.6/ 53.6
60/ 60
57/ 57 327/327
20.0/ 23.1
7.5/10.0
53.6/ 53.6
60/ 60
57/ 57 327/327
30.0/ 34.6
11.3/15.0
53.6/ 56.0
60/ 60
57/ 57 327/327
50.0/ 57.7
18.8/25.0
75.3/ 84.9
80/ 90
69/ 78 327/327
70.0/ 80.8
26.3/35.0
100.3/113.8 110/125
92/105 327/327
80.0/ 92.4
30.0/40.0
112.8/128.3 125/150 104/118 327/327
100.1/115.5
37.6/50.0
137.9/128.3 150/150 127/145 327/327
3.0
Low
7.5
—
—
53.9/ 53.9
60/ 60
57/ 57 314/314
20.0/ 23.1
7.5/10.0
53.9/ 53.9
60/ 60
57/ 57 314/314
30.0/ 34.6
11.3/15.0
53.9/ 56.4
60/ 60
57/ 57 314/314
50.0/ 57.7
18.8/25.0
75.6/ 85.3
80/ 90
70/ 78 314/314
70.0/ 80.8
26.3/35.0
100.6/114.1 110/125
93/105 314/314
80.0/ 92.4
30.0/40.0
113.1/128.6 125/150 104/118 314/314
100.1/115.5
37.6/50.0
138.3/128.6 150/150 127/145 314/314
High
10.2
—
—
56.6/ 56.6
60/ 60
60/ 60 331/331
20.0/ 23.1
7.5/10.0
56.6/ 56.6
60/ 60
60/ 60 331/331
30.0/ 34.6
11.3/15.0
56.6/ 59.8
60/ 60
60/ 60 331/331
50.0/ 57.7
18.8/25.0
79.0/ 88.6
80/ 90
73/ 82 331/331
70.0/ 80.8
26.3/35.0
104.0/117.5 110/125
96/108 331/331
80.0/ 92.4
30.0/40.0
116.5/132.0 125/150 107/121 331/331
100.1/115.5
37.6/50.0
141.6/132.0 150/150 130/148 331/331
460-3-60
414
506
7.7
50
2
1.0
—
Low
3.4
—
—
22.7
25
24
132
11.5
10.0
22.7
25
24
132
17.3
15.0
25.9
30
24
132
28.9
25.0
40.4
45
37
132
40.4
35.0
54.8
60
50
132
46.2
40.0
62.0
70
57
132
57.7
50.0
62.0
70
70
132
High
4.8
—
—
24.1
25
26
141
11.5
10.0
24.1
25
26
141
17.3
15.0
27.6
30
26
141
28.9
25.0
42.1
45
39
141
40.4
35.0
56.5
60
52
141
46.2
40.0
63.8
70
59
141
57.7
50.0
63.7
70
72
141
1.2
Low
3.4
—
—
23.9
25
25
135
11.5
10.0
23.9
25
25
135
17.3
15.0
27.4
30
25
135
28.9
25.0
41.9
45
39
135
40.4
35.0
56.3
60
52
135
46.2
40.0
63.5
70
58
135
57.7
50.0
63.5
70
72
135
High
4.8
—
—
25.3
30
27
144
11.5
10.0
25.3
30
27
144
17.3
15.0
29.1
30
27
144
28.9
25.0
43.6
45
40
144
40.4
35.0
58.0
60
53
144
46.2
40.0
65.3
70
60
144
57.7
50.0
65.2
70
73
144
575-3-60
518
633
6.1
40
2
0.8
—
Low
2.8
—
—
18.1
20
19
106
13.9
15.0
20.9
25
19
106
23.1
25.0
32.4
35
30
106
32.3
35.0
43.9
45
40
106
37.0
40.0
49.8
50
46
106
46.2
50.0
49.7
60
56
106
High
—
—
18.1
20
19
106
13.9
15.0
20.9
25
19
106
23.1
25.0
32.4
35
30
106
32.3
35.0
43.9
45
40
106
37.0
40.0
49.8
50
46
106
46.2
50.0
49.7
60
56
106
LEGEND
FLA
--- Full Load Amps
HACR
--- Heating, Air Conditioning and Refrigeration
IFM
--- Indoor (Evaporator) Fan Motor
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
MOCP
--- Maximum Overcurrent Protection
NEC
--- National Electrical Code
OFM
--- Outdoor (Condenser) Fan Motor
RLA
--- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
{
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%
. Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230---3---60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage = 224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT
: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE031A00 are not required if field---supplied
pressure connectors are used. Factory---installed heaters contain terminal blocks when
combined MOCP is greater than 60 amps.
50PG08
--
14