background image

11

NOTE: The gasketing of the unit to the roof curb is critical for a

watertight seal. Install gasket supplied with the roof curb as shown

in Fig. 7. Improperly applied gasket can also result in air leaks and

poor unit performance.
SLAB MOUNT (HORIZONTAL UNITS ONLY) 
Provide  a  level  concrete  slab  that  extends  a  minimum  of  6-in.

(150 mm) beyond unit cabinet. Install a gravel apron in front of

condenser coil air inlet to prevent grass and foliage from obstruct

-

ing airflow.

NOTE:  Horizontal  units  may  be  installed  on  a  roof  curb  if

required.
ALTERNATE  UNIT  SUPPORT  (IN  LIEU  OF  CURB  OR

SLAB MOUNT) 
A non-combustible sleeper rail can be used in the unit curb sup

-

port area. If sleeper rails cannot be used, support the long sides of

the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm

x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not

exceed 0.35 in. wg (87 Pa) with economizer or 0.4-in. wg (112 Pa)

without economizer.

For vertical ducted applications, secure all ducts to roof curb and

building structure. 

Do not connect ductwork to unit.

Fabricate supply ductwork so that the cross sectional dimensions

are equal to or greater than the unit supply duct opening dimen

-

sions for the first 18 in. (458 mm) of duct length from the unit

basepan.

Insulate and weatherproof all external ductwork, joints, and roof

openings with counter flashing and mastic in accordance with ap

-

plicable codes.

Ducts  passing  through  unconditioned  spaces  must  be  insulated

and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be

ducted through the roof deck to comply with applicable fire codes.

FOR UNITS WITH ACCESSORY ELECTRIC HEATERS 
All installations require a minimum clearance to combustible sur

-

faces of 1 in. (25 mm) from duct for the first 12-in. (305 mm)

away from unit.

Outlet grilles must not lie directly below unit discharge.

NOTE: A 90 degree elbow must be provided in the ductwork to

comply with UL (Underwriters Laboratories) code for use with

electric heat.

Step 6 — Rig and Place Unit

Keep unit upright and do  not drop. Spreader  bars are required.

Rollers may be used to move unit across a roof. Level by using

unit frame as a reference. See Table 2 and Fig. 9 for additional in

-

formation.

Lifting holes are provided in base rails as shown in Fig. 9. Refer to

rigging instructions on unit.

Before setting the unit onto the curb, recheck gasketing on curb.

Rigging materials under unit (cardboard or wood to prevent base

pan damage) must be removed PRIOR to placing the unit on the

roof curb.

When  using  the  standard  side  drain  connection,  ensure  the  red

plug in the alternate bottom connection is tight. Do this before set

-

ting the unit in place. The red drain pan plug can be tightened with

1

/

2

-in. square socket drive extension. For further details see “Step

10 — Install External Condensate Trap and Line” on page 14.

POSITIONING ON CURB
Position  unit  on  roof  curb  so  that  the  following  clearances  are

maintained: 

1

/

4

-in. (6.4 mm) clearance between the roof curb and

the base rail inside the front and rear, 0.0-in. clearance between the

roof curb and the base rail inside on the duct end of the unit. This

will result in the distance between the roof curb and the base rail

inside on the condenser end of the unit being approximately 

1

/

4

-in.

(6.4 mm).

Although unit is weatherproof, guard against water from higher

level runoff and overhangs.

After  unit  is  in  position,  remove  rigging  skids  and  shipping

materials.

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in damage to roofing

materials.

Membrane roofs can be cut by sharp sheet metal edges. Be

careful when placing any sheet metal parts on such roof.

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could cause personal injury.

For vertical supply and return units, tools or parts could drop

into ductwork and cause an injury. Install a 90 degree turn in

the  return  ductwork  between  the  unit  and  the  conditioned

space. If a 90 degree elbow cannot be installed, then a grille of

sufficient strength and density should be installed to prevent

objects from falling into the conditioned space. Due to electric

heater, supply duct will require 90 degree elbow.

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

All panels must be in place when rigging. Unit is not designed

for handling by fork truck when packaging is removed.

If using top crate as spreader bar, once unit is set, carefully

lower wooden crate off building roof top to ground. Ensure

that no people or obstructions are below prior to lowering the

crate.

Содержание 50KC04

Страница 1: ...NTERFACE OVERVIEW SETUP AND CONFIGURATION ENTHALPY SETTINGS CHECKOUT TROUBLESHOOTING Control and Power Wiring Diagrams 34 Smoke Detectors 42 ADDITIONAL APPLICATION DATA PremierLink Controller Factory...

Страница 2: ...unit rating plate Unit may have more than one power switch WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and or equipment damage R 410A refr...

Страница 3: ...tric Relief F Enthalpy Economizer w Barometric Relief K 2 Position Damper U Temp Ultra Low Leak Economizer w Baro Relief W Enthalpy Ultra Low Leak Econo w Baro Relief Base unit controls 0 Electro mech...

Страница 4: ...4 Fig 2 Unit Dimensional Drawing of Units Built On and After 4 15 19...

Страница 5: ...5 Fig 3 Unit Dimensional Drawing of Units Built on and Prior to 4 15 19...

Страница 6: ...6 Fig 4 Unit Corner Weights and Clearances...

Страница 7: ...7 Fig 5 Base Rail Details...

Страница 8: ...8 Fig 6 Thru the Base Charts...

Страница 9: ...F CARRIER CORPORATION 1 DEC 2 DEC 3 DEC ANG MATERIAL AUTHORIZATION NUMBER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING 004 007 ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRA...

Страница 10: ...ng refer to Step 10 for details 5 Rig and place unit 6 Install outdoor air hood 7 Install condensate line trap and piping 8 Make electrical connections 9 Install other accessories PAD MOUNTED INSTALLA...

Страница 11: ...frame as a reference See Table 2 and Fig 9 for additional in formation Lifting holes are provided in base rails as shown in Fig 9 Refer to rigging instructions on unit Before setting the unit onto th...

Страница 12: ...e covered by the tape used to secure the insulation to the basepan and are not easily seen See Fig 11 for position of the notches in the basepan Seals around duct openings must be tight Secure with sc...

Страница 13: ...pan and remove Locate and cut the 2 plastic tie wraps securing the assembly to the damper See Fig 14 Be careful to not dam age any wiring or cut tie wraps securing any wiring Fig 14 Economizer Hood Pa...

Страница 14: ...anels Only Relocate latch shipped inside the compressor compartment behind the hinged compressor door to location shown in Fig 18 after unit installation If the unit does not have hinged panels skip t...

Страница 15: ...nnection points on contactor C or op tional disconnect switch These leads are for factory run test pur poses only remove and discard before connecting field power wires to unit connection points Make...

Страница 16: ...abel diagram for power wir ing connections to the unit power terminal blocks and equipment ground Maximum wire size is 2 ga AWG copper only per pole on contactors Provide a ground fault and short circ...

Страница 17: ...fuse lo cated in a utility box and mounted on a bracket behind the conve nience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet tra...

Страница 18: ...e the L bracket assembly from the unit 2 Remove connector plate assembly from the L bracket and discard the L bracket but retain the washer head screws and the gasket located between the L bracket and...

Страница 19: ...ructions If the thermostat contains a logic circuit requiring 24 v power use a thermostat cable or equivalent single leads of different colors with minimum of seven leads If the thermostat does not re...

Страница 20: ...ingle point box also includes a set of power taps and pigtails to complete the wiring between the single point box and the unit s main control box terminals Refer to the accessory heater and single po...

Страница 21: ...trol To connect the Carrier humidistat HL38MG029 1 Route the humidistat 2 conductor cable field supplied through the hole provided in the unit corner post 2 Feed wires through the raceway built into t...

Страница 22: ...iring Fig 42 Typical Rooftop Unit with Humidi MiZer Adaptive Dehumidification System with EDGE Pro Thermidistat Device Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R EDGE Pr...

Страница 23: ...ce Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keypad Electrical Rated Voltage 20 to 30 v...

Страница 24: ...Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output C...

Страница 25: ...220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests andAlarms 1 Navigate to the desired menu 2 Press the Enter button to displa...

Страница 26: ...lled system The setup process uses a hierarchical menu structure that is easy to use Press the and arrow buttons to move forward and back ward through the menus and press the button to select and conf...

Страница 27: ...nd displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F or _ _ _ C 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP D...

Страница 28: ...isplays only if CO2 sensor is connected Set point for Demand Controlled Ventilation of space Above the set point the OA dampers will modulate open to bring in additional OA to maintain a space ppm lev...

Страница 29: ...ON Damper position when freeze protection is active closed or MIN POS CO2 ZERO 0ppm 0 to 500 ppm Increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000ppm 1000 to 3000 ppm Increme...

Страница 30: ...nge or become disconnected check wiring then replace sensor if the alarm continues OA SYLK T ERR N A N A OUTSIDE AIR S BUS SENSOR ERROR Outdoor air enthalpy sensor has failed or become disconnected ch...

Страница 31: ...or 2 Speed unit operation EQUIPMENT CONV AUX2 I W FAN SPEED 2SPEED For damper minimum position settings and checkout menu read ings see Table 8 For dry bulb operation with or without DCV see Tables 9...

Страница 32: ...High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Of...

Страница 33: ...sion of the software appears on the first line and the second line will be blank Power Loss Outage or Brownout All set points and advanced settings are restored after any power loss or interruption NO...

Страница 34: ...g Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to t...

Страница 35: ...35 Fig 49 Electro Mechanical Control Wiring Diagram...

Страница 36: ...36 Fig 50 Electro Mechanical Control Wiring Diagram with Humidi MiZer System...

Страница 37: ...37 Fig 51 Electro Mechanical Power Wiring...

Страница 38: ...38 Fig 52 PremierLink Wiring Schematic...

Страница 39: ...39 Fig 53 PremierLink Wiring Schematic with Humidi MiZer System...

Страница 40: ...40 Fig 54 RTU Open System Control Wiring Diagram...

Страница 41: ...41 Fig 55 RTU Open System Control Wiring Diagram with Humidi MiZer System...

Страница 42: ...See Fig 57 Step 3 4 Connect the flexible tube on the sampling inlet to the sam pling tube on the basepan ADDITIONAL APPLICATION DATA Refer to the application data document Factory Installed Smoke Dete...

Страница 43: ...CO2 sensor DDC interface PremierLink Louvered hail guard Motormaster head pressure controls Phase monitor control Refer to separate installation instructions for information on in stalling these acces...

Страница 44: ...and Maintenance Instructions Pre Start and Start Up This completes the mechanical installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instruc tions Downloa...

Страница 45: ...45 Fig 61 50KC A B Sizes 04 05 Metering Devices ACCUTROL NOTE Each feeder tube in the liquid header has a metering device...

Страница 46: ...46 Fig 62 50KC A B Sizes 06 Dual Metering Devices ACCUTROL ACCURATER NOTE Each feeder tube in the liquid header has a metering device...

Страница 47: ...47 Fig 63 TXV Metering Device Position in Reheat Coil Typical Diagram for Sizes 04 06 TXV...

Страница 48: ......

Страница 49: ......

Страница 50: ...o discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500239 01 Printed in U S A Form 50KC 4 6 03SI Pg 50 3 2020 Replaces 50KC...

Страница 51: ...location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotating in the co...

Страница 52: ...fan motor as condenser coil warms Y N _____ 4 Check unit charge per charging chart Y N _____ Jumper 32L Motormaster temperature sensor during this check Remove jumper when complete 5 Switch unit to hi...

Отзывы: