background image

10

INSTALLATION

Jobsite Survey

Complete the following checks before installation:

1. Consult local building codes and the NEC (National Electri

-

cal  Code) ANSI/NFPA  70  for  special  installation  require

-

ments.

2. Determine  unit  location  (from  project  plans)  or  select  unit

location.

3. Check for possible overhead obstructions which may inter

-

fere with unit lifting or rigging.

Step 1 — Plan for Unit Location

NOTE: Select a location for the unit and its support system (curb

or other) that provides for minimum clearances required for safety

(including clearance to  combustible surfaces), unit  performance

and service access below, around and above unit as specified in

unit  drawings.  See  Fig.  4.  Consider  also  the  effect  of  adjacent

units.

Unit may be installed directly on wood flooring or on Class A, B,

or C roof-covering material when roof curb is used. Do not install

unit in an indoor location. Do not locate air inlets near exhaust

vents or other sources of contaminated air.

Although unit is weatherproof, avoid locations that permit water

from higher level runoff and overhangs to fall onto unit.

Select a unit mounting system that provides adequate height to al

-

low installation of condensate trap per requirements. Refer to Step

10 — Install External Condensate Trap and Line – for required

trap dimensions.
ROOF MOUNT 
Check building codes for weight distribution requirements. Unit

operating weight is shown in Table 2.

Step 2 — Plan for Sequence of Unit Installation

The support  method used for this unit will  dictate different  se

-

quences for the steps of unit installation. For example, on curb-

mounted units, some accessories must be installed on the unit be

-

fore the unit is placed on the curb. Review the following for rec

-

ommended sequences for installation steps.

CURB-MOUNTED INSTALLATION 
1. Install curb

2. Install field-fabricated ductwork inside curb
3. Install  accessory  thru-base  service  connection  package

(affects curb and unit) (refer to accessory installation instruc

-

tions for details)

4. Prepare bottom condensate drain connection to suit planned

condensate line routing (refer to Step 10 for details)

5. Rig and place unit
6. Install outdoor air hood
7. Install condensate line trap and piping

8. Make electrical connections
9. Install other accessories
PAD-MOUNTED INSTALLATION 
1. Prepare pad and unit supports

2. Check and tighten the bottom condensate drain connection

plug

3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
FRAME-MOUNTED INSTALLATION 
Frame-mounted applications generally follow the sequence for a

curb  installation. Adapt  as  required  to  suit  specific  installation

plan.

Step 3 — Inspect Unit

Inspect unit for transportation damage. File any claim with trans

-

portation agency.

Confirm before installation of unit that voltage, amperage and cir

-

cuit protection requirements listed on unit data plate agree with

power supply provided.

Step 4 — Provide Unit Support

ROOF CURB MOUNT 
Accessory roof curb details and dimensions are shown in Fig. 7.

Assemble and install accessory roof curb in accordance with in

-

structions shipped with the curb.

Curb should be level. This is necessary for unit drain to function

properly. Unit leveling tolerances  are shown in  Fig. 8.  Refer to

Accessory Roof Curb Installation Instructions for additional infor

-

mation as required.

   

Fig. 8 — Unit Leveling Tolerances

Install insulation, cant strips, roofing felt, and counter flashing as

shown. 

Ductwork must be attached to curb and not to the unit. The

accessory thru-the-base power package must be installed before

the unit is set on the roof curb.

If electric and control wiring is to be routed through the basepan,

attach the accessory thru-the-base service connections to the base

-

pan in accordance with the accessory installation instructions.

Table 2 — Operating Weights

50KC

UNITS LB (KG) 

04 

05 

06

Base Unit 

445 (201) 

499 (226)  552 (250)

Economizer

Vertical 

Horizontal 

50 (23) 

80 (36) 

50 (23) 

80 (36) 

50 (23)

80 (36)

Humidi-MiZer

®

 System 

50 (23) 

50 (23) 

50 (23)

Cu Fins 

25 (11) 

43 (20) 

56 (25)

Powered Outlet 

35 (16) 

35 (16) 

35 (16)

Curb

14-in./356 mm 

24-in./610 mm 

115 (52) 

197 (89) 

115 (52) 

197 (89) 

115 (52)

197 (89)

A

B

C

MAXIMUM ALLOWABLE 

DIFFERENCE in. (mm)

A-B

B-C

A-C

0.5 (13)

1.0 (25)

1.0 (25)

Содержание 50KC04

Страница 1: ...NTERFACE OVERVIEW SETUP AND CONFIGURATION ENTHALPY SETTINGS CHECKOUT TROUBLESHOOTING Control and Power Wiring Diagrams 34 Smoke Detectors 42 ADDITIONAL APPLICATION DATA PremierLink Controller Factory...

Страница 2: ...unit rating plate Unit may have more than one power switch WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and or equipment damage R 410A refr...

Страница 3: ...tric Relief F Enthalpy Economizer w Barometric Relief K 2 Position Damper U Temp Ultra Low Leak Economizer w Baro Relief W Enthalpy Ultra Low Leak Econo w Baro Relief Base unit controls 0 Electro mech...

Страница 4: ...4 Fig 2 Unit Dimensional Drawing of Units Built On and After 4 15 19...

Страница 5: ...5 Fig 3 Unit Dimensional Drawing of Units Built on and Prior to 4 15 19...

Страница 6: ...6 Fig 4 Unit Corner Weights and Clearances...

Страница 7: ...7 Fig 5 Base Rail Details...

Страница 8: ...8 Fig 6 Thru the Base Charts...

Страница 9: ...F CARRIER CORPORATION 1 DEC 2 DEC 3 DEC ANG MATERIAL AUTHORIZATION NUMBER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING 004 007 ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRA...

Страница 10: ...ng refer to Step 10 for details 5 Rig and place unit 6 Install outdoor air hood 7 Install condensate line trap and piping 8 Make electrical connections 9 Install other accessories PAD MOUNTED INSTALLA...

Страница 11: ...frame as a reference See Table 2 and Fig 9 for additional in formation Lifting holes are provided in base rails as shown in Fig 9 Refer to rigging instructions on unit Before setting the unit onto th...

Страница 12: ...e covered by the tape used to secure the insulation to the basepan and are not easily seen See Fig 11 for position of the notches in the basepan Seals around duct openings must be tight Secure with sc...

Страница 13: ...pan and remove Locate and cut the 2 plastic tie wraps securing the assembly to the damper See Fig 14 Be careful to not dam age any wiring or cut tie wraps securing any wiring Fig 14 Economizer Hood Pa...

Страница 14: ...anels Only Relocate latch shipped inside the compressor compartment behind the hinged compressor door to location shown in Fig 18 after unit installation If the unit does not have hinged panels skip t...

Страница 15: ...nnection points on contactor C or op tional disconnect switch These leads are for factory run test pur poses only remove and discard before connecting field power wires to unit connection points Make...

Страница 16: ...abel diagram for power wir ing connections to the unit power terminal blocks and equipment ground Maximum wire size is 2 ga AWG copper only per pole on contactors Provide a ground fault and short circ...

Страница 17: ...fuse lo cated in a utility box and mounted on a bracket behind the conve nience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet tra...

Страница 18: ...e the L bracket assembly from the unit 2 Remove connector plate assembly from the L bracket and discard the L bracket but retain the washer head screws and the gasket located between the L bracket and...

Страница 19: ...ructions If the thermostat contains a logic circuit requiring 24 v power use a thermostat cable or equivalent single leads of different colors with minimum of seven leads If the thermostat does not re...

Страница 20: ...ingle point box also includes a set of power taps and pigtails to complete the wiring between the single point box and the unit s main control box terminals Refer to the accessory heater and single po...

Страница 21: ...trol To connect the Carrier humidistat HL38MG029 1 Route the humidistat 2 conductor cable field supplied through the hole provided in the unit corner post 2 Feed wires through the raceway built into t...

Страница 22: ...iring Fig 42 Typical Rooftop Unit with Humidi MiZer Adaptive Dehumidification System with EDGE Pro Thermidistat Device Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R EDGE Pr...

Страница 23: ...ce Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keypad Electrical Rated Voltage 20 to 30 v...

Страница 24: ...Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output C...

Страница 25: ...220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests andAlarms 1 Navigate to the desired menu 2 Press the Enter button to displa...

Страница 26: ...lled system The setup process uses a hierarchical menu structure that is easy to use Press the and arrow buttons to move forward and back ward through the menus and press the button to select and conf...

Страница 27: ...nd displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F or _ _ _ C 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP D...

Страница 28: ...isplays only if CO2 sensor is connected Set point for Demand Controlled Ventilation of space Above the set point the OA dampers will modulate open to bring in additional OA to maintain a space ppm lev...

Страница 29: ...ON Damper position when freeze protection is active closed or MIN POS CO2 ZERO 0ppm 0 to 500 ppm Increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000ppm 1000 to 3000 ppm Increme...

Страница 30: ...nge or become disconnected check wiring then replace sensor if the alarm continues OA SYLK T ERR N A N A OUTSIDE AIR S BUS SENSOR ERROR Outdoor air enthalpy sensor has failed or become disconnected ch...

Страница 31: ...or 2 Speed unit operation EQUIPMENT CONV AUX2 I W FAN SPEED 2SPEED For damper minimum position settings and checkout menu read ings see Table 8 For dry bulb operation with or without DCV see Tables 9...

Страница 32: ...High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Of...

Страница 33: ...sion of the software appears on the first line and the second line will be blank Power Loss Outage or Brownout All set points and advanced settings are restored after any power loss or interruption NO...

Страница 34: ...g Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to t...

Страница 35: ...35 Fig 49 Electro Mechanical Control Wiring Diagram...

Страница 36: ...36 Fig 50 Electro Mechanical Control Wiring Diagram with Humidi MiZer System...

Страница 37: ...37 Fig 51 Electro Mechanical Power Wiring...

Страница 38: ...38 Fig 52 PremierLink Wiring Schematic...

Страница 39: ...39 Fig 53 PremierLink Wiring Schematic with Humidi MiZer System...

Страница 40: ...40 Fig 54 RTU Open System Control Wiring Diagram...

Страница 41: ...41 Fig 55 RTU Open System Control Wiring Diagram with Humidi MiZer System...

Страница 42: ...See Fig 57 Step 3 4 Connect the flexible tube on the sampling inlet to the sam pling tube on the basepan ADDITIONAL APPLICATION DATA Refer to the application data document Factory Installed Smoke Dete...

Страница 43: ...CO2 sensor DDC interface PremierLink Louvered hail guard Motormaster head pressure controls Phase monitor control Refer to separate installation instructions for information on in stalling these acces...

Страница 44: ...and Maintenance Instructions Pre Start and Start Up This completes the mechanical installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instruc tions Downloa...

Страница 45: ...45 Fig 61 50KC A B Sizes 04 05 Metering Devices ACCUTROL NOTE Each feeder tube in the liquid header has a metering device...

Страница 46: ...46 Fig 62 50KC A B Sizes 06 Dual Metering Devices ACCUTROL ACCURATER NOTE Each feeder tube in the liquid header has a metering device...

Страница 47: ...47 Fig 63 TXV Metering Device Position in Reheat Coil Typical Diagram for Sizes 04 06 TXV...

Страница 48: ......

Страница 49: ......

Страница 50: ...o discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500239 01 Printed in U S A Form 50KC 4 6 03SI Pg 50 3 2020 Replaces 50KC...

Страница 51: ...location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotating in the co...

Страница 52: ...fan motor as condenser coil warms Y N _____ 4 Check unit charge per charging chart Y N _____ Jumper 32L Motormaster temperature sensor during this check Remove jumper when complete 5 Switch unit to hi...

Отзывы: