9
Fig. 7 — Roof Curb Details
E
E
7/16"
[11]
4 9/16"
[115.5]
1/4"
[7.0]
5' 7-3/8"
[1711.3]
1' 4-13/16"
[427] INSIDE
1-3/4"
[44.4]
2-3/8"
[61]
1-3/4"
[44.5]
1.00"
[25.4]
"A"
1-3/4"
[44.4]
21.74"
[552.2]
5.42"
[137.7]
11.96"
[303.8]
4.96"
[126.0]
70.87"
[1800.2]
40.69"
[1033.5]
21.84"
[554.7]
16.03"
[407.2]
1.75"
[44.5]
20.41"
[518.3]
3.00"
[76.2]
13.78"
[350.0]
14.00"
[355.6]
3.00"
[76.2]
15.19"
[385.8]
32.19"
[817.6]
3'-1 3/16"
[944.6]
"A"
1-3/4"
[44.5]
CRBTMPWR001A01
3/4" [19] NPT
3/4" [19] NPT
1/2" [12.7] NPT
CRRFCURB002A01
CONNECTOR PKG. ACC.
GAS CONNECTION TYPE
GAS FITTING
POWER WIRING
FITTING
CONTROL WIRING
FITTING
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
THRU THE CURB
1/2" [12.7] NPT
1/2" [12.7] NPT
CRBTMPWR003A01
THRU THE BOTTOM
ROOF CURB
ACCESSORY #
A
CRRFCURB001A01
14"
[356]
24"
[610]
ECN NO.
APP'D
CHK'D
BY
DATE
REVISION RECORD
REV
1067898
-
-
MMC
04/22/13
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
A
DRAWING RELEASE LEVEL:
PRODUCTION
THIRD ANGLE
PROJECTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCES ON:
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1 DEC
2 DEC
3 DEC
ANG
MATERIAL
-
-
-
-
-
-
-
AUTHORIZATION NUMBER
TITLE
1041738
CURB ASY, ROOF
ENGINEERING
MANUFACTURING
(004-007)
ENGINEERING REQUIREMENTS
-
- -
-
SIZE
DRAWING NUMBER
REV
T-005, Y-002
DRAFTER
CHECKER
D
48TC400427
B
WEIGHT:
-
MMC
06/17/11 -
-
SHEET 5 OF 5
SURFACE FINISH
MFG/PURCH
MODEL (INTERNAL USE ONLY)
NEXT DRAWING
SCALE
DISTRIBUTION
-
PURCH
-
N/A
MMC
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
TYPICAL (4) SIDES
SUPPLY AIR
RETURN AIR
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
UNIT
GASKET
(SUPPLIED WITH CURB)
RIGID INSULATION
(FIELD SUPPLIED)
DUCT
(FIELD SUPPLIED)
NAIL (FIELD SUPPLIED)
CERTIFIED DRAWING
VIEW "B"
CORNER DETAIL
SEE VIEW "B"
RETURN AIR
SUPPLY AIR
SUPPLY AIR
OPENING
RETURN AIR
OPENING
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SEE NOTE #2
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1/3/4"[44.5]
SCALE 0.250
E-E
SECTION
Содержание 50KC04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing of Units Built On and After 4 15 19...
Страница 5: ...5 Fig 3 Unit Dimensional Drawing of Units Built on and Prior to 4 15 19...
Страница 6: ...6 Fig 4 Unit Corner Weights and Clearances...
Страница 7: ...7 Fig 5 Base Rail Details...
Страница 8: ...8 Fig 6 Thru the Base Charts...
Страница 35: ...35 Fig 49 Electro Mechanical Control Wiring Diagram...
Страница 36: ...36 Fig 50 Electro Mechanical Control Wiring Diagram with Humidi MiZer System...
Страница 37: ...37 Fig 51 Electro Mechanical Power Wiring...
Страница 38: ...38 Fig 52 PremierLink Wiring Schematic...
Страница 39: ...39 Fig 53 PremierLink Wiring Schematic with Humidi MiZer System...
Страница 40: ...40 Fig 54 RTU Open System Control Wiring Diagram...
Страница 41: ...41 Fig 55 RTU Open System Control Wiring Diagram with Humidi MiZer System...
Страница 47: ...47 Fig 63 TXV Metering Device Position in Reheat Coil Typical Diagram for Sizes 04 06 TXV...
Страница 48: ......
Страница 49: ......