Fig. 3 — Dimensions; Sizes 048,060
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT
CORNER WT (Kg/Lb)
Kg
Lb
A
B
C
D
50HS048
400-3-50
165
363
38/83
43/95
54/118
30/67
50HS060
400-3-50
168
370
40/89
42/92
48/105
38/84
REQ’D CLEARANCES FOR SERVICING — mm (in.)
Indoor Coil Access Side . . . . . . . . . . . . . . . . . . . 762 (30)
Control Box Access Side . . . . . . . . . . . . . . . . . . 762 (30)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . 914 (36)
Side Opposite Ducts
. . . . . . . . . . . . . . . . . . . . 762 (30)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — mm (in.)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge, First 305 mm (12 in.) of Supply Duct . . . 25 (1)
UNIT
CENTER OF GRAVITY (mm/in.)
X
Y
Z
50HS048
543/21.4
540/21.3
440/17.3
50HS060
493/19.4
539/21.2
440/17.3
LEGEND
CG
— Center of Gravity
MAT’L
— Material
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in (
) are in millimeters unless otherwise noted.
4