Carrier 50HJ008-014 Скачать руководство пользователя страница 27

Cooling —

To start unit, turn on main power supply. Set

system selector switch at COOL position and fan switch at
AUTO position. Adjust thermostat to a setting below room
temperature. Compressor starts on closure of contactor.

Check unit charge. Refer to Refrigerant Charge section on

page 30.

Reset thermostat at a position above room temperature.

Compressor will shut off.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature
exceeds thermostat setting. Units are equipped with Cycle-
LOC™ protection device. Unit shuts down on any safety trip
and remains off; an indicator light on the thermostat comes
on. Check reason for safety trip.

Compressor restart is accomplished by manual reset at the

thermostat by turning the selector switch to OFF position
and then ON position.

Heating (If Accessory Heater is Installed) —

To

start unit, turn on main power supply.

Set thermostat at HEAT position and a setting above room

temperature, and set fan at AUTO position.

First stage of thermostat energizes the first-stage electric

heater elements; second stage energizes second-stage elec-
tric heater elements. Check heating effects at air supply grille(s).

If accessory electric heaters do not energize, reset limit

switch (located on evaporator-fan scroll) by pressing button
located between terminals on the switch.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting heating selector lever below room tem-
perature temporarily shuts unit off until space temperature
falls below thermostat setting.

Safety Relief —

A soft solder joint in the suction line

at the loss-of-charge/low-pressure switch fitting provides
pressure relief under abnormal temperature and pressure
conditions.

Ventilation (Continuous Fan) —

Set fan and sys-

tem selector switches at ON and OFF positions, respec-
tively. Evaporator fan operates continuously to provide
constant air circulation.

Operating Sequence

COOLING, UNITS WITHOUT ECONOMIZER — When
the thermostat calls for cooling, terminals G and Y1 are en-
ergized. The indoor (evaporator) fan contactor (IFC), and com-
pressor contactor no. 1 (C1) are energized and the evaporator-
fan motor, compressor no. 1, and condenser fans start. The
condenser-fan motors run continuously while unit is in
cooling. If the thermostat calls for a second stage of cooling
by energizing Y2, compressor contactor no. 2 (C2) is ener-
gized and compressor no. 2 starts.
HEATING, UNITS WITHOUT ECONOMIZER (If Acces-
sory Heater is Installed) — Upon a call for heating through
terminal W1, IFC and heater contactor no. 1 (HC1) are en-
ergized. On units equipped for 2 stages of heat, when ad-
ditional heat is needed, HC2 is energized through W2.
COOLING, UNITS WITH DURABLADE ECONOMIZER
— When the outdoor-air temperature is above the OAT set-
ting and the room thermostat calls for cooling, the compres-
sor contactor no. 1 is energized to start compressor no. 1 and
outdoor (condenser) fan motor. The indoor (evaporator) fan
motor (IFM) is energized and the economizer damper moves
to the minimum position. Upon a further call for cooling,
compressor contactor no. 2 will be energized, starting com-
pressor no. 2. After the thermostat is satisfied and the IFM

is deenergized, the damper moves to the fully closed
position.

When the outdoor-air temperature is below the OAT set-

ting and the thermostat calls for Y1 and G, the economizer
damper moves to the minimum position when the indoor
(evaporator) fan starts. The first stage of cooling is provided
by the economizer. If the supply-air temperature is above
57 F, a switch on the supply-air thermostat is closed between
the T2 terminal and the 24 vac terminal. This causes the damper
to continue to modulate open until the supply-air tempera-
ture falls below 55 F or the damper reaches the fully open
position.

When the supply-air temperature is between 55 F and

52 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals and between the T1 and 24 vac
terminals. This causes the economizer damper to remain in
an intermediate open position.

If the supply-air temperature falls below 52 F, a switch on

the supply-air thermostat is closed between the T1 terminal
and the 24 vac terminal. This causes the damper to modulate
closed until the supply-air temperature rises above 55 F or
the damper reaches the minimum position.

When the supply-air temperature is between 55 F and

57 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals. This causes the economizer damper
to remain in an intermediate open position.

If the outdoor air alone cannot satisfy the cooling require-

ments of the conditioned space, economizer cooling is in-
tegrated with mechanical cooling, providing second stage
cooling. Compressor no. 1 and condenser fans will be en-
ergized, and the position of the economizer damper will be
determined by the supply-air temperature. Compressor no. 2
is locked out.

When the second stage of cooling is satisfied, the com-

pressor and condenser-fan motor will be deenergized. The
damper position will be determined by the supply-air
temperature.

When the first stage of cooling is satisfied, the damper

will move to fully closed position.

COOLING, UNITS WITH PARABLADE ECONOMIZER
— When the outdoor air is above the enthalpy control set-
ting, and the room thermostat calls for cooling, the compres-
sor contactor no. 1 is energized to start compressor no. 1 and
the condenser-fan motors. The evaporator-fan motor is en-
ergized and the economizer damper moves to the minimum
position. Upon further call for cooling, compressor contac-
tor no. 2 is energized, starting compressor no. 2. After the
room thermostat is satisfied the damper will spring return to
the fully closed position.

When the outdoor air is below the enthalpy control setting

and the thermostat calls for cooling, the economizer outdoor-
air damper is opened proportionally to maintain between
50 and 56 F at the mixed-air sensor. If outdoor air alone can-
not satisfy the cooling requirements, economizer cooling is
integrated with mechanical cooling and the second compres-
sor is locked out. When the room thermostat is satisfied, the
damper will spring return to the fully closed position.
HEATING, UNITS WITH ECONOMIZER (If Accessory
Heater is Installed) — When the room thermostat calls for
heat through terminal W1, the evaporator-fan contactor and
heater contactor no. 1 are energized. On units equipped for
2 stages of heat, when additional heat is needed, heater
contactor no. 2 is energized through W2. The evaporator-
fan motor is energized, and the economizer damper moves
to the minimum position. If the two-position damper is used,
the outdoor-air damper opens to the minimum position
whenever the evaporator fan opens. When the thermostat is
satisfied, the damper moves to the fully closed position.

27

Содержание 50HJ008-014

Страница 1: ...curb in accordance with instructions shipped with curb See Fig 1 Install insulation cant strips roofing felt and counter flash ing as shown Ductwork must be attached to curb If electric or control pow...

Страница 2: ...ttom UNIT SIZE 50HJ A ROOF CURB ACCESSORY 008 014 18 29 356 CRRFCURB003A00 28 09 610 CRRFCURB004A00 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millime...

Страница 3: ...of run Do not use a pipe size smaller than the unit connection Step 4 Rig and Place Unit Inspect unit for trans portation damage File any claim with transportation agency Keep unit upright and do not...

Страница 4: ...ng to prevent rigging straps from damaging unit 3 Unit weights do not include economizer See Table 1 for econo mizer weights All panels must be in place when rigging 50HJ MAX WEIGHT A B C lb kg in mm...

Страница 5: ...20 Motor Frame 56 56 56 56 Fan Rpm Range Std 840 1085 840 1085 860 1080 900 1260 Alt 860 1080 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter A...

Страница 6: ...ow 4 Ductwork to be attached to accessory roof curb only 5 Minimum clearance local codes or jurisdiction may prevail a Bottom to combustible surfaces when not using curb 0 in on horizontal discharge u...

Страница 7: ...ing units provide a disconnect per the NEC All field wiring must comply with the NEC and local re quirements In Canada electrical connections must be made in accordance with CSA Canadian Standards Ass...

Страница 8: ...0 21 7 25 0 33 3 38 5 66 6 77 0 88 4 102 0 104 4 120 3 55 9 55 9 55 9 55 9 55 9 61 4 96 6 109 5 123 7 140 8 143 5 133 5 60 60 60 60 70 70 100 110 125 150 150 150 59 59 59 59 59 59 89 101 114 129 132...

Страница 9: ...0 21 7 25 0 33 3 38 5 66 6 77 0 88 4 102 0 104 4 120 3 61 9 61 9 61 9 61 9 61 9 66 4 101 5 114 5 128 7 145 8 148 5 138 5 70 70 70 70 70 70 110 125 150 150 150 150 64 64 64 64 64 64 94 106 119 135 138...

Страница 10: ...n Table 3 FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor Evaporator Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection NEC Nati...

Страница 11: ...with the air hood package If unit is to be used for vertical dis charge application discard this plate Assembly 1 Determine if ventilation air is required in building If so determine the minimum amoun...

Страница 12: ...lenoid Valve S LPS Low Pressure Switch Subcooler only TRAN Transformer Factory Wiring Accessory or Optional Wiring Fig 11 Typical MoistureMiser Dehumidification Package Humidistat Wiring 208 230 V Uni...

Страница 13: ...s 9 Remove tape from outdoor air thermostat OAT Fas ten OAT to inside of hood using screws and speed clips provided See Fig 21 Make sure OAT terminals are po sitioned up 10 Replace outdoor air opening...

Страница 14: ...Put aside screen retainer and retainer screw for later as sembly Do not attach hood to unit at this time 4 On 012 and 014 units install vertical discharge block off plate over duct openings See Fig 1...

Страница 15: ...N 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOOR TEMP F REV 97 3672 CW SETPOINTS CCW CONTACTS S...

Страница 16: ...s provided and in stall bottom stop 11 Slide outdoor air inlet screens into screen track on hood side plate While holding screens in place fasten screen retainer to hood using screws provided See Fig...

Страница 17: ...pulley hub and tighten setscrew See Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fan shaft 3 Make...

Страница 18: ...12 1 88 862 2 15 911 2 46 3100 646 1 15 709 1 39 772 1 70 825 1 99 875 2 28 923 2 58 3200 662 1 25 724 1 50 785 1 80 840 2 11 887 2 41 934 2 71 3300 679 1 35 740 1 61 798 1 91 854 2 24 900 2 54 946 2...

Страница 19: ...813 2 39 867 2 74 915 3 06 960 3 40 4200 830 2 55 883 2 91 931 3 24 4250 839 2 63 892 3 00 939 3 34 AIRFLOW Cfm EXTERNAL STATIC PRESSURE in wg 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 908...

Страница 20: ...3000 886 1 73 943 1 88 988 1 91 995 1 95 3100 892 1 78 947 2 00 995 2 05 1008 2 07 3200 899 1 85 951 2 06 1000 2 17 1021 2 20 3300 907 1 93 959 2 10 1004 2 33 1036 2 36 3400 915 2 01 966 2 17 1009 2...

Страница 21: ...2 3800 959 2 38 1001 2 58 1040 2 78 1075 2 96 3900 969 2 50 1010 2 70 1049 2 91 1085 3 11 4000 979 2 62 1020 2 83 1059 3 04 1095 3 25 4100 989 2 74 1029 2 96 1068 3 18 1105 3 39 4200 1000 2 86 1039 3...

Страница 22: ...2300 816 1 65 859 1 94 888 2 24 903 2 55 911 2 85 2400 824 1 72 872 2 01 909 2 32 931 2 64 935 2 96 2500 832 1 79 882 2 09 925 2 40 955 2 72 972 3 06 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11...

Страница 23: ...SSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11 2660 839 1 87 891 2 17 936 2 49 973 2 82 999 3 16 2700 846 1 95 898 2 26 946 2...

Страница 24: ...7 2 10 988 2 05 995 2 20 3400 853 1 71 899 1 93 951 2 17 995 2 17 1008 2 32 3500 862 1 78 907 2 01 959 2 24 1000 2 33 1021 2 47 3600 871 1 86 915 2 09 965 2 32 1005 2 46 1036 2 59 3700 879 1 95 927 2...

Страница 25: ...3 03 1058 3 29 1100 3 53 4400 945 2 68 988 2 89 1028 3 14 1066 3 41 1106 3 67 4500 955 2 82 996 3 02 1037 3 25 1074 3 54 1113 3 81 4600 967 2 96 1005 3 16 1046 3 38 1084 3 66 1121 3 95 4700 980 3 11 1...

Страница 26: ...es a re frigerant leak Leak test all refrigerant tubing connec tions using electronic leak detector halide torch or liquid soap solution c Inspect all field and factory wiring connections Be sure that...

Страница 27: ...emperature is below the OAT set ting and the thermostat calls for Y1 and G the economizer damper moves to the minimum position when the indoor evaporator fan starts The first stage of cooling is provi...

Страница 28: ...witch has closed and a new call for cooling exists The crankcase heaters on the scroll compressors provide additional protec tion for the compressors due to the additional refrigerant charge in the su...

Страница 29: ...Fig 33 MoistureMiser Option Operation 29...

Страница 30: ...ting dur ing charging procedure NO CHARGE Use standard evacuating techniques After evacuating system weigh in the specified amount of refrigerant refer to Table 1 LOW CHARGE COOLING Use Cooling Chargi...

Страница 31: ...harts Fig 38 41 for units with MoistureMiser option and DO NOT use Fig 42 45 for standard units TO USE COOLING CHARGING CHARTS STANDARD UNITS Take the outdoor ambient temperature and read the suction...

Страница 32: ...Fig 39 Cooling Charging Chart Standard 50HJ009 Fig 40 Cooling Charging Charts Standard 50HJ012 32...

Страница 33: ...harging Charts Standard 50HJ014 Fig 42 Cooling Charging Chart 50HJ008 with Optional MoistureMiser Dehumidification Package Fig 43 Cooling Charging Chart 50HJ009 with Optional MoistureMiser Dehumidific...

Страница 34: ...quid line solenoid valve will not operate 1 Solenoid coil defective replace 2 Solenoid valve stuck open replace Subcooler will not deenergize Liquid line solenoid valve will not open Valve is stuck cl...

Страница 35: ...Locate restriction and remove Compressor s operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Lo...

Страница 36: ...nomizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired properly and no 24 vac exists c...

Страница 37: ...hese actions do not occur replace economizer control module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to economizer 1 Disconnect power at TR and...

Страница 38: ...programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 96...

Страница 39: ......

Страница 40: ...LTAGE L1 L2 L2 L3 L3 L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 EVAPORATOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING...

Отзывы: