Table 4 shows evaporator-fan motor data. Table 5 shows fan
rpm at motor pulley settings for standard and alternate mo-
tors. Refer to Tables 6-13 to determine fan speed settings,
and see Tables 14 and 15 for accessory and option static pres-
sure drops. Fan motor pulleys are factory set for speed shown
in Table 1.
To change fan speeds:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts. See
Fig. 30 and 31.
3. Loosen movable pulley flange setscrew (see Fig. 32).
4. Screw movable flange toward fixed flange to increase speed
or away from fixed flange to decrease speed. Increasing
fan speed increases load on motor. Do not exceed maxi-
mum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mount-
ing plate.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Sizes 008,009 — Slide motor mounting plate away from
fan scroll for proper belt tension (
1
⁄
2
-in. deflection with
one finger) and tighten mounting nuts (see Fig. 30).
Sizes 012,014 — Slide motor mounting plate downward
to tighten belt tension. Secure motor mounting plate nuts.
See Fig. 31.
3. Adjust bolt and nut on mounting plate to secure motor in
fixed position.
Fig. 29 — Parablade Economizer Barometric Relief
Damper Characteristics
MOTOR MOUNTING
PLATE NUTS
Fig. 30 — Typical Belt-Drive Motor Mounting for
Sizes 008,009
Fig. 31 — Typical Belt-Drive Motor Mounting for
Sizes 012,014
Fig. 32 — Evaporator-Fan Pulley Adjustment
17
Содержание 50HJ008-014
Страница 29: ...Fig 33 MoistureMiser Option Operation 29...
Страница 32: ...Fig 39 Cooling Charging Chart Standard 50HJ009 Fig 40 Cooling Charging Charts Standard 50HJ012 32...
Страница 39: ......