27
the sensor housing using four captive screws and forms an air-
tight chamber around the sensing electronics. Each sensor in-
cludes a harness with an RJ45 terminal for connecting to the
controller. Each sensor has four LEDs (for Power, Trouble,
Alarm and Dirty) and a manual test/reset button (on the left-
side of the housing).
Fig. 47 — Controller Assembly
Air is introduced to the duct smoke detector sensor’s sensing
chamber through a sampling tube that extends into the HVAC
duct and is directed back into the ventilation system through a
(shorter) exhaust tube.
The difference in air pressure between the two tubes pulls the
sampled air through the sensing chamber. When a sufficient
amount of smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically takes the
appropriate action to shut down fans and blowers, change over
air handling systems, notify the fire alarm control panel, etc.
The sensor uses a process called differential sensing to prevent
gradual environmental changes from triggering false alarms. A
rapid change in environmental conditions, such as smoke from
a fire, causes the sensor to signal an alarm state but dust and
debris accumulated over time does not.
For installations using two sensors, the duct smoke detector
does not differentiate which sensor signals an alarm or trouble
condition.
Fig. 48 — Smoke Detector Sensor
Smoke Detector Locations
SUPPLY AIR
The Supply Air Smoke Detector Sensor is located to the left of
the unit’s indoor (supply) fan. See Fig. 49. Access is through
the fan access panel. There is no sampling tube used at this lo-
cation. The sampling tube inlet extends through the side plate
of the fan housing (into a high pressure area). The controller is
located on a bracket to the right of the return filter, accessed
through the lift-off filter panel.
Fig. 49 — Typical Supply Air Smoke Detector Sensor
Location
RETURN AIR SMOKE DETECTOR SENSOR WITHOUT
ECONOMIZER
The sampling tube is located across the return air opening on
the unit basepan. See Fig. 50. The holes in the sampling tube
face downward, into the return air stream. The sampling tube is
connected through tubing to the return air sensor that is mount-
ed on a bracket high on the partition between return filter and
controller location. (This sensor is shipped in a flat-mounting
location. Installation requires that this sensor be relocated to its
operating location and the tubing to the sampling tube be con-
nected. See “Completing Installation of Return Air Smoke
Sensor” for installation steps.)
DUCT
S
MOKE
S
EN
S
OR
CONTROLLER
CONDUIT NUT
S
(
S
UPPLIED BY IN
S
TALLER)
CONDUIT
S
UPPORT PLATE
TERMINAL BLOCK COVER
COVER GA
S
KET
(ORDERING OPTION)
CONTROLLER
COVER
FA
S
TENER (2X)
CONDUIT COUPLING
S
(
S
UPPLIED BY IN
S
TALLER)
CONTROLLER HOU
S
ING
AND ELECTRONIC
S
ALARM
TROUBLE
POWER
TE
S
T/RE
S
ET
S
WITCH
SEE DETAIL
A
DETAIL
A
PLUG
SAMPLING TUBE
(ORDERED SEPARATELY)
COUPLING
MAGNETIC
TEST/RESET
SWITCH
ALARM
TROUBLE
POWER
DIRTY
SENSOR
COVER
COVER GASKET
(ORDERING OPTION)
SENSOR HOUSING
AND ELECTRONICS
EXHAUST GASKET
EXHAUST TUBE
DUCT SMOKE SENSOR
INTAKE
GASKET
TSD-CO2
(ORDERING OPTION)
SUPPLY AIR
SMOKE DETECTOR
Содержание 50HCQ04---12
Страница 85: ...85 APPENDIX E WIRING DIAGRAMS cont Fig B 50HCQA04 A05 Control Wiring Diagram 208 230 1 60 208 230 3 60 460 3 60...
Страница 86: ...86 APPENDIX E WIRING DIAGRAMS cont Fig C 50HCQA04 A05 Control Wiring Diagram 575 3 60...
Страница 87: ...87 APPENDIX E WIRING DIAGRAMS cont Fig D 50HCQ 06 Control Wiring Diagram 208 230 1 60 208 230 3 60 460 3 60...
Страница 88: ...88 APPENDIX E WIRING DIAGRAMS cont Fig E 50HCQ 06 Control Wiring Diagram 575 3 60...
Страница 93: ...93 APPENDIX E WIRING DIAGRAMS cont Fig J 50HCQ 04 05 06 Power Wiring Diagram 208 230 1 60...
Страница 94: ...94 APPENDIX E WIRING DIAGRAMS cont Fig K 50HCQ 04 05 06 Power Wiring Diagram 208 230 3 60...
Страница 95: ...95 APPENDIX E WIRING DIAGRAMS cont Fig L 50HCQ 04 05 06 Power Wiring Diagram 460 3 60...
Страница 96: ...96 APPENDIX E WIRING DIAGRAMS cont Fig M 50HCQ 04 05 06 Power Wiring Diagram 575 3 60...
Страница 97: ...97 APPENDIX E WIRING DIAGRAMS cont Fig N 50HCQA07 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60...
Страница 98: ...98 APPENDIX E WIRING DIAGRAMS cont Fig O 50HCQD07 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60...
Страница 99: ...99 APPENDIX E WIRING DIAGRAMS cont Fig P 50HCQ 08 09 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60...
Страница 100: ...100 APPENDIX E WIRING DIAGRAMS cont Fig Q 50HCQ 12 Power Wiring Diagram 208 230 3 60...
Страница 101: ...101 APPENDIX E WIRING DIAGRAMS cont Fig R 50HCQ 12 Power Wiring Diagram 460 3 60 575 3 60...
Страница 102: ...102 APPENDIX E WIRING DIAGRAMS cont Fig S 50HCQ PremierLink Control Diagram...
Страница 103: ...103 APPENDIX E WIRING DIAGRAMS cont Fig T 50HCQ RTU Open Control Diagram...