![Carrier 50GL030 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/carrier/50gl030/50gl030_installation-start-up-and-operating-instructions-manual_2561565003.webp)
UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
"A"
CENTER OF GRAVITY
IN. [MM]
lb
kg
X
Y
Z
50GL030
208/230-3-60
291
132.0
39.02 [991.1]
19.5 [495.3]
15.5 [393.7]
17.6 [447.0]
50GL036
208/230-3-60, 460-3-60
299
135.6
35.02 [889.5]
19.5 [495.3]
15.3 [387.4]
16.5 [419.1]
Fig. 2—50GL030-036 Unit Dimensions
C00064
REQ’D CLEARANCES FOR OPERATION AND SERVICING. IN. (MM)
EVAPORATOR COIL ACCESS SIDE . . . . . . . . . . . . .
36 (914)
POWER ENTRY SIDE (EXCEPT FOR NEC REQUIREMENTS) . . 36 (914)
UNIT TOP. . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
SIDE OPPOSITE DUCTS . . . . . . . . . . . . . . . . . . . 36 (914)
DUCT PANEL . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12 IN. (304.8 MM) FROM
WALL SYSTEM, THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED.
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. IN. (MM)
TOP OF UNIT . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
DUCT SIDE OF UNIT. . . . . . . . . . . . . . . . . . . . . 2 (50.8)
SIDE OPPOSITE DUCTS . . . . . . . . . . . . . . . . . . 14 (355.6)
BOTTOM OF UNIT . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
ELECTRIC HEAT PANEL . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ’D CLEARANCES. IN. (MM)
BETWEEN UNITS, POWER ENTRY SIDE
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE
UNIT AND BLOCK OF CONCRETE WALLS AND OTHER
GROUNDED SURFACES, CONTROL BOX SIDE
. . . . . . . . . . 42 (1066.8)
. . 36 (914)
. . . . . . . 42 (1066.8)
LEGEND
CG - CENTER OF GRAVITY
COND - CONDENSER
EVAP - EVAPORATOR
NEC - NATIONAL ELECTRICAL CODE
REQ'D - REQUIRED
NOTE: DIMENSIONS ARE IN IN. (MM)
4 4 . 5 [ 1 . 7 5 ]
3