CL-3
IAQ / VENTILATION ALARM
Occ High CO
2
Alarm Limit
0-9999 ppm
1200
SERVICE CONFIGURATION
Compressor Stages
9
N/A
Three Stages
Economizer Exists
10
N/A
Yes (FIOP)
VFD Input
0-10Vdc/2-10Vdc
2-10Vdc
Max VFD Output
15-100%
100
Min VFD Output
15-100%
25
Heat Type
0 = Electric (50 series units)
1 = Gas (48 series units)
Gas
Number of Heat Stages
1 = 1 stage (All 50LC*B07-09 units,
50LC*B12-14 lo heat)
2 = 2 stages (All 48LC*B07-26 units,
50LC*B12 hi heat, 50LC*B14
med/hi heat, All 50LC*B17-26 units)
2
SA Tempering
Disabled/Enabled
Disable
Continuous Occupied Exhaust
No/Yes
No
DCV Control
Disable/Enable
Disable
Indoor CO
2
Sensor Value @ Min mA
11
0-9999ppm
0
Indoor CO
2
Sensor Value @ Max mA
11
0-9999ppm
2000
Outdoor CO
2
Sensor Value @ Min mA
12
0-9999ppm
0
Outdoor CO
2
Sensor Value @ Max mA
12
0-9999ppm
2000
Static Pressure Sensor Value @ Min mA
0
Static Pressure Sensor Value @ Max
mA
2.5
System Space RH
N/A
-999.0
System Space AQ
N/A
-999.0
System Cool Demand Level
0-3
0
System Heat Demand Level
0-3
0
System Outdoor Air Temperature
N/A
-999.0
System Outdoor AQ
N/A
-999.0
System Fire / Smoke
Off/On
Off
Network Heat Interlock
Off/On
Off
SERVICE TEST
Service Test Mode
Disable/Enable
Service Test
Disable/Enable
Disable
Fan Test
Disable/Enable
Disable
Compressor 1 Test
Disable/Enable
Disable
Compressor 2 Test
Disable/Enable
Disable
Heat 1 Test
Disable/Enable
Disable
Heat 2 Test
Disable/Enable
Disable
Heat Interlock Relay Test
Disable/Enable
Disable
Power Exhaust Test
Disable/Enable
Disable
Economizer Test
0-100 %Open
0
VFD Speed Test
0-100%
0
LINKAGE
Linkage Collector
13
Airside Linkage Status
Active/Not Active
Occupancy Status
Unoccupied/Occupied
Space Temperature
xxx °F
Occupied Cooling Setpoint
xxx °F
Occupied Heating Setpoint
xxx °F
Unoccupied Cooling Setpoint
xxx °F
Unoccupied Heating Setpoint
xxx °F
Indoor Air CO
2
xxxx ppm
Space Relative Humidity
xxx %
Linkage Optimal Start
Inactive/Active
Air Source Mode
Air Source Supply Air Temp
xxx °F
Air Source Static Pressure
"wc
Air Source Outdoor Air Temp
xxx °F
POINT NAME
RANGE
DEFAULT
ENTRY
Содержание 48LCB07
Страница 4: ...4 Fig 2 VAV RTU Open Control Module ...
Страница 8: ...8 Fig 5 VAV RTU Open Control Wiring Diagram 48LC B07 ...
Страница 9: ...9 Fig 6 VAV RTU Open Control Wiring Diagram 48LC B08 12 ...
Страница 10: ...10 Fig 7 VAV RTU Open Control Wiring Diagram 48LC B14 26 ...
Страница 11: ...11 Fig 8 VAV RTU Open Control Wiring Diagram 50LC B07 ...
Страница 12: ...12 Fig 9 VAV RTU Open Control Wiring Diagram 50LC B08 12 ...
Страница 13: ...13 Fig 10 VAV RTU Open Control Wiring Diagram 50LC B14 26 ...
Страница 55: ......