Occupancy Status
R
occ_status
BV:2008
Occupied Heating
R/W
Inactive (0)
occ_heat
BV:2031
Outdoor Air Quality CO2 (ppm)
R
ppm
oaq
AV:1012
Outdoor Air Quality Sensor
R
oaq_fail
BV:7006
Outdoor Air Temp Sensor
R
oat_fail
BV:7029
Outdoor Air Temperature
R
°F
oa_temp
AV:1003
Override Time Remaining
R
min
ovrde_time
AV:2016
Password Protected Output Variable
R/W
no units
0
ppo
AV:90000
Power Exhaust Relay State
R
pexh
BV:2010
Power Exhaust Setpoint
R/W
%Open
50
pexh_stpt
AV:3010
Power Exhaust Test
R/W
Inactive (0)
pexh_test
BV:81008
Power Fail Restart Delay
R/W
seconds
5
start_delay
AV:9007
RAT Sensor
R
°F
ai_11
AI:1011
RAT Source
R
rat_src
MSV:2015
Reset Calculated Max Heat Limit
R/W
Inactive (0)
calc_limit_reset
BV:9003
Reset Comp 1 Runtime Alarm
R/W
Inactive (0)
comp1_rntm_clr
BV:7514
Reset Comp 2 Runtime Alarm
R/W
Inactive (0)
comp2_rntm_clr
BV:7515
Reset Filter Alarm
R/W
Inactive (0)
filter_rntm_clr
BV:7517
Reset Heat 1 Runtime Alarm
R/W
Inactive (0)
heat1_rntm_clr
BV:7518
Reset Heat 2 Runtime Alarm
R/W
Inactive (0)
heat2_rntm_clr
BV:7519
Reset High Static Trip
R/W
Inactive (0)
hsl_reset
BV:1908
Reset Maximum Limit
R/W
°^F
10
sat_cl_stpt_reset_max
AV:9040
Reset Ratio
R/W
no units
3
sat_cl_stpt_reset
AV:9041
Reset Supply Fan Runtime Alarm
R/W
Inactive (0)
sfan_rntm_clr
BV:7510
Return Air Temp Sensor
R
rat_fail
BV:7052
Return Air Temperature
R
°F
ra_temp
AV:1010
Return Air Temperature
R
rat_alarm
BV:7035
SA Reset Humidity Override
R/W
Inactive (0)
rh_enable
BV:1025
SA Tempering
R/W
Inactive (0)
sa_tempering_en
BV:83016
SA Tempering Setpoint
R/W
°F
55
tempering_stpt
AV:3032
Safety Chain
R
safety_alarm
BV:7024
Safety Chain Feedback
R
safety_status
BV:1009
SAT Reset Source
R
sat_reset_source
MSV:2016
SAT Sensor
R
°F
ai_6
AI:1006
Service Test
R/W
Inactive (0)
test_enable
BV:81000
Setpoint
R/W
°F
occ_cl_stpt
AV:3001
Setpoint
R/W
°F
occ_ht_stpt
AV:3002
Setpoint
R/W
°F
unocc_cl_stpt
AV:3003
Setpoint
R/W
°F
unocc_ht_stpt
AV:3004
Shutdown
R/W
Inactive (0)
shutdown
BV:9001
SP Proof
R
sp_proof_alm
MSV:7068
SP Reset Demand Level
R/W
1
sp_reset_dmd_lvl
MSV:9033
Space Relative Humidity
R
%rh
space_rh
AV:1011
Space Relative Humidity
R
sprh_hi_alarm
BV:7018
Space Relative Humidity Sensor
R
sprh_sensor_fail
BV:7022
Space Temp Sensor
R
°F
ai_10
AI:1010
Space Temp Sensor
R
spt_fail
BV:7001
Space Temp Source
R
spt_source
MSV:2014
Space Temperature
R
°F
spt_temp
AV:1032
Static Pressure
R
in H2O
static_press
AV:2028
Static Pressure Sensor
R
mA
ai_1
AI:1001
Static Pressure Sensor
R
sp_fail
BV:7061
Static Pressure Setpoint
R/W
in H2O
0.5
sa_static_stpt
AV:3030
Supply Air Setpoint
R/W
°F
53
sat_cl_stpt
AV:3029
Supply Air Setpoint
R
°F
sasp
AV:2031
Supply Air Temp Reset
R/W
Inactive (0)
sa_reset_en
BV:9004
Supply Air Temp Sensor
R
loc_sat_sensor_fail
BV:7020
Supply Air Temperature
R
sat_alarm
BV:7004
Supply Air Temperature - Prime Variable
R
°F
sa_temp
AV:1008
Supply Fan Failure
R
sfan_fail_alarm
BV:7008
Supply Fan in Hand
R
sfan_hand_alarm
BV:7009
Table C — VAV-RTU Open Protocol Maps (cont)
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet
Object ID
APPENDIX D — BACNET POINTS LIST (CONT)
Содержание 48LCB07
Страница 4: ...4 Fig 2 VAV RTU Open Control Module ...
Страница 8: ...8 Fig 5 VAV RTU Open Control Wiring Diagram 48LC B07 ...
Страница 9: ...9 Fig 6 VAV RTU Open Control Wiring Diagram 48LC B08 12 ...
Страница 10: ...10 Fig 7 VAV RTU Open Control Wiring Diagram 48LC B14 26 ...
Страница 11: ...11 Fig 8 VAV RTU Open Control Wiring Diagram 50LC B07 ...
Страница 12: ...12 Fig 9 VAV RTU Open Control Wiring Diagram 50LC B08 12 ...
Страница 13: ...13 Fig 10 VAV RTU Open Control Wiring Diagram 50LC B14 26 ...
Страница 55: ......