31
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
NOTICE
Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
S
The sensor’s Dirty LED flashing.
S
The controller’s Trouble LED flashing.
S
The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so
that the controller’s supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,
notify
the
proper
authorities
before
performing the test.
NOTICE
SD--TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 42 and configured to operate the controller’s
supervision relay. For more information, see “Changing
sensor dirty test operation.”
1
12
14
13
19
15
2
20
3
Reset/Test
Trouble
Power
Alarm
Supervision relay
contacts [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 Vdc ( )
+
18 Vdc ( )
−
Auxiliary
equipment
+
−
Wire must be
added by installer
Smoke Detector Controller
C08247
Fig. 42 -- Remote Test/Reset Station Connections
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
NOTICE
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
NOTICE
Dirty Sensor Test Using an SD--TRK4
1. Turn the key switch to the RESET/TEST position for
two seconds.
48H
C
Содержание 48HC*04-14
Страница 91: ...91 APPENDIX IV WIRING DIAGRAMS C14015 Fig 77 48HC A07 YAC Control Diagram 208 230 3 60 460 575 3 60 48HC ...
Страница 92: ...92 APPENDIX IV WIRING DIAGRAMS C14021 Fig 78 48HC D08 D09 YAC Control Diagram 208 230 3060 460 575 3 60 48HC ...
Страница 93: ...93 APPENDIX IV WIRING DIAGRAMS C14026 Fig 79 48HC D12 YAC Control Diagram 208 230 3060 460 575 3 60 48HC ...
Страница 94: ...94 APPENDIX IV WIRING DIAGRAMS C14007 Fig 80 48HC A04 A06 YAC Power Diagram 230 1 60 48HC ...
Страница 95: ...95 APPENDIX IV WIRING DIAGRAMS C14010 Fig 81 48HC A04 A06 YAC Power Diagram 208 230 3 60 460 3 60 48HC ...
Страница 96: ...96 APPENDIX IV WIRING DIAGRAMS C14013 Fig 82 48HC A04 A06 YAC Power Diagram 575 3 60 48HC ...
Страница 97: ...97 APPENDIX IV WIRING DIAGRAMS C14018 48HC ...
Страница 98: ...98 APPENDIX IV WIRING DIAGRAMS C14019 48HC ...
Страница 99: ...99 APPENDIX IV WIRING DIAGRAMS C13484 Fig 83 48HC D08 D09 YAC Power Diagram 230 460 3 60 48HC ...
Страница 100: ...100 APPENDIX IV WIRING DIAGRAMS C14024 Fig 84 48HC D08 D09 YAC Power Diagram 575 3 60 48HC ...
Страница 101: ...101 APPENDIX IV WIRING DIAGRAMS C14027 Fig 85 48HC D12 YAC Power Diagram 230 460 3 60 48HC ...
Страница 102: ...102 APPENDIX IV WIRING DIAGRAMS C14029 Fig 86 48HC D12 YAC Power Diagram 575 3 60 48HC ...
Страница 103: ...103 APPENDIX IV WIRING DIAGRAMS C14031 Fig 87 48HC D14 YAC Control Diagram 208 230 3 60 460 575 3 60 48HC ...
Страница 104: ...104 APPENDIX IV WIRING DIAGRAMS C14032 Fig 88 48HC D14 YAC Power Diagram 230 460 3 60 48HC ...
Страница 105: ...105 APPENDIX IV WIRING DIAGRAMS C12462 Fig 89 48HC D14 YAC Power Diagram 575 3 60 48HC ...
Страница 108: ...108 APPENDIX IV WIRING DIAGRAMS C14022 Fig 92 48HC D08 D09 YAC Control Diagram 230 460 575 3 60 with Humidi MiZer 48HC ...
Страница 109: ...109 APPENDIX IV WIRING DIAGRAMS C14028 Fig 93 48HC D12 YAC Control Diagram 230 460 575 3 60 with Humidi MiZer 48HC ...
Страница 110: ...110 APPENDIX IV WIRING DIAGRAMS C14009 Fig 94 48HC A04 A06 YAC Power Diagram 230 1 60 with Humidi MiZer 48HC ...
Страница 111: ...111 APPENDIX IV WIRING DIAGRAMS C14012 Fig 95 48HC A04 A06 YAC Power Diagram 230 460 3 60 with Humidi MiZer 48HC ...
Страница 112: ...112 APPENDIX IV WIRING DIAGRAMS C14014 Fig 96 48HC A04 A06 YAC Power Diagram 575 3 60 with Humidi MiZer 48HC ...
Страница 113: ...113 APPENDIX IV WIRING DIAGRAMS C14017 Fig 97 48HC A07 YAC Power Diagram 230 460 3 60 with Humidi MiZer 48HC ...
Страница 114: ...114 APPENDIX IV WIRING DIAGRAMS C14020 Fig 98 48HC A07 YAC Power Diagram 575 3 60 with Humidi MiZer 48HC ...
Страница 115: ...115 APPENDIX IV WIRING DIAGRAMS C14023 Fig 99 48HC D08 D09 YAC Power Diagram 230 460 3 60 with Humidi MiZer 48HC ...
Страница 116: ...116 APPENDIX IV WIRING DIAGRAMS C14025 Fig 100 48HC D08 D09 YAC Power Diagram 575 3 60 with Humidi MiZer 48HC ...
Страница 117: ...117 APPENDIX IV WIRING DIAGRAMS C14030 Fig 101 48HC D12 YAC Power Diagram 230 460 3 60 with Humidi MiZer 48HC ...
Страница 118: ...118 APPENDIX IV WIRING DIAGRAMS C14046 Fig 102 48HC D12 YAC Power Diagram 575 3 60 with Humidi MiZer 48HC ...
Страница 119: ...119 APPENDIX IV WIRING DIAGRAMS C14033 Fig 103 48HC D14 YAC Control Diagram 230 460 575 3 60 with Humidi MiZer 48HC ...
Страница 120: ...120 APPENDIX IV WIRING DIAGRAMS C12464 Fig 104 48HC D14 YAC Power Diagram 230 460 3 60 with Humidi MiZer 48HC ...
Страница 121: ...121 APPENDIX IV WIRING DIAGRAMS C12465 Fig 105 48HC D14 YAC Power Diagram 575 3 60 with Humidi MiZer 48HC ...
Страница 122: ...122 APPENDIX IV WIRING DIAGRAMS 50HE500891 F 50HE500751 J C12263 Fig 106 PremierLink System Control Wiring Diagram 48HC ...
Страница 123: ...123 APPENDIX IV WIRING DIAGRAMS C12690 Fig 107 PremierLink System Control Wiring Diagram 48HC ...
Страница 124: ...124 APPENDIX IV WIRING DIAGRAMS C14035 Fig 108 PremierLink System Control Wiring Diagram with Humidi MiZer 48HC ...
Страница 125: ...125 APPENDIX IV WIRING DIAGRAMS C14034 Fig 109 RTU Open Wiring Diagram 48HC ...