NOTE: On retrofit jobs, ductwork may be attached to old unit
instead of roof curb. Be careful not to damage ductwork when
removing old unit. Attach existing ductwork to roof curb
instead of unit.

Four lifting lugs are provided on the unit base rails as shown

in Fig. 5-10. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 5-10, around
and above unit to provide minimum distance from combustible
materials, proper airflow, and service access.

Do not install unit in an indoor location. Do not locate unit

air inlets near exhaust vents or other sources of contaminated
air. 

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribu-
tion requirements. See Fig. 11. Unit operating weight is shown
in Table 2.

Step 3 — Field Fabricate Ductwork — 

Secure all

ducts to building structure. Use flexible duct connectors be-
tween unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
NOTE: Due to width of the horizontal supply/return ductwork,
provisions should be made for servicing of the outdoor air fil-
ters (i.e., catwalk over ductwork).

Ducts passing through an unconditioned space must be in-

sulated and covered with a vapor barrier. Outlet grilles must not
lie directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if the
unit is equipped with power exhaust.

To attach ductwork to roof curb, insert duct approximately

10 to 11 in. up into roof curb. Connect ductwork to 14-gage
roof curb material with sheet metal screws driven from inside
the duct.

Step 4 — Make Unit Duct Connections

50AJ AND AK UNITS — Unit  is  shipped  for  through-the-
bottom duct connections. Field-fabricated ductwork should be
attached to the roof curb. Supply and return duct dimensions
are shown in Fig. 5-7. Air distribution is shown in Fig. 12.
Refer to installation instructions shipped with roof curb for
more information.
50AW AND AY UNITS — Remove  shipping  covers  from
supply and return air openings. Attach field-supplied ductwork
to unit. Connect to the unit with a single duct for all  supply
openings and with a single duct for all return openings.
Splitting of the airflow into branch ducts should not be done at
the unit. Sufficient duct length should be used prior to branch-
ing to ensure the air temperatures are well mixed within the
ductwork. See Fig. 8-10 for duct opening dimensions. Secure
all ducts to building structure. Air distribution is shown in
Fig. 8-10 and Fig. 13.

Install accessory barometric relief or power exhaust in the

field-fabricated return ductwork. Refer to Step 8 — Position
Power Exhaust/Barometric Relief Damper Hood section on
page 44 for more information.

Instructions continued on page 18.

For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow turn in the supply and return ductwork between the
unit and the conditioned space. If a 90-degree elbow cannot
be installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space.

Содержание 48AJ/AK/AMD020

Страница 1: ...e level This is necessary to permit unit drain to func tion properly Unit leveling tolerance is shown in Fig 1 4 Refer to Accessory Roof Curb Installation Instructions for additional information as re...

Страница 2: ...wer exhaust To attach ductwork to roof curb insert duct approximately 10 to 11 in up into roof curb Connect ductwork to 14 gage roof curb material with sheet metal screws driven from inside the duct S...

Страница 3: ...3 Fig 1 Roof Curb 50AJ AK020 035 Units...

Страница 4: ...4 Fig 2 Roof Curb 50AJ AK040 050 Units...

Страница 5: ...5 Fig 3 Roof Curb 50AJ AK060 Units...

Страница 6: ...6 Fig 4 Reduced Supply Duct Opening Roof Curb 50AJ AK060 Units...

Страница 7: ...7 Fig 5 Base Unit Dimensions 50AJ AK020 035...

Страница 8: ...8 Fig 6 Base Unit Dimensions 50AJ AK040 050...

Страница 9: ...lication Engineering Department 5 Bottom ducts designed to be attached to accessory roof curb If unit is mounted on dunnage it is recom mended the ducts must be supported by cross braces as done on ac...

Страница 10: ...10 Fig 8 Base Unit Dimensions 50AW AY020 035...

Страница 11: ...11 Fig 9 Base Unit Dimensions 50AW AY040 050...

Страница 12: ...y roof curb 6 Base unit weights include outdoor air hoods and filters indoor fan motor is not included Add indoor motor FIOPs and accessories for total operating weight 7 VAV motor weights include ind...

Страница 13: ...Nominal Cfm 8 000 10 000 11 000 12 000 Motor Hp 5 10 15 5 10 15 10 15 20 10 15 20 Motor Frame Size 184T 215T 254T 184T 215T 254T 215T 254T 256T 215T 254T 256T Motor Bearing Type Ball Ball Ball Ball Ma...

Страница 14: ...16 000 18 000 24 000 Motor Hp 15 20 25 15 20 25 20 25 30 25 30 40 Motor Frame Size 254T 256T 284T 254T 256T 284T 256T 284T 286T 284T 286T 324T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable...

Страница 15: ...25 48AW AY AXE027 5083 2306 87 7 2227 69 6 1768 44 6 1133 50AJ AK AM030 5023 2278 87 7 2227 68 0 1727 43 6 1107 48AJ AK AMD030 5113 2319 87 7 2227 69 1 1755 44 0 1118 48AJ AK AME030 5193 2356 87 7 222...

Страница 16: ...er Coil 220 220 220 220 285 285 380 651 Outdoor Air Hood Crate and Packaging Less Hoods Weight 45 45 45 45 45 45 45 45 Packaging Only Packaging Only Outdoor Air Hoods Filters 170 170 170 170 170 170 1...

Страница 17: ...0 1 625 1187 2B5V58 5 9 B 1 625 2B5V86 8 7 B 1 9375 2 5VX530 11 030 10 1 375 884 2BK50 4 4 H 1 375 2B5V94 9 5 B 1 9375 2 BX50 8 15 1 625 1096 2B5V56 5 7 B 1 625 2B5V90 9 1 B 1 9375 2 5VX530 9 20 1 625...

Страница 18: ...PT coupling for 24 v control wiring are provided in basepan In the side post there are two 21 2 in 50A020 035 or 3 in 50A040 060 knockouts for the field power wiring See Fig 5 10 If control wiring is...

Страница 19: ...ation from average voltage AB 457 452 5 v BC 464 457 7 v AC 457 455 2 v Maximum deviation is 7 v Determine percent of voltage imbalance Voltage Imbalance 100 x 1 53 This amount of phase imbalance is s...

Страница 20: ...2 103 2 125 86 6 36 127 3 150 173 2 72 192 2 200 23 6 126 8 150 86 6 36 156 8 175 173 2 72 221 7 225 10 28 0 117 2 125 86 6 36 143 3 150 173 2 72 208 2 225 23 6 140 8 150 86 6 36 172 8 175 173 2 72 2...

Страница 21: ...ea 5 15 2 107 8 125 86 6 36 127 3 150 173 2 72 192 2 200 23 6 131 4 150 86 6 36 156 8 175 173 2 72 221 7 225 10 28 0 121 2 125 86 6 36 143 3 150 173 2 72 208 2 225 23 6 144 8 150 86 6 36 172 8 175 173...

Страница 22: ...125 0 150 86 6 36 143 3 150 173 2 72 208 2 225 23 6 148 6 150 86 6 36 172 8 175 173 2 72 237 7 250 15 42 0 142 5 175 86 6 36 160 8 175 173 2 72 225 7 250 23 6 166 1 200 86 6 36 190 3 200 173 2 72 255...

Страница 23: ...a 10 28 0 137 8 150 86 6 36 143 3 150 173 2 72 208 2 225 23 6 161 4 175 86 6 36 172 8 175 173 2 72 237 7 250 15 42 0 155 3 175 86 6 36 160 8 175 173 2 72 225 7 250 23 6 178 9 200 86 6 36 190 3 200 173...

Страница 24: ...200 86 6 36 164 3 200 173 2 72 225 7 250 23 6 187 9 225 86 6 36 190 3 225 173 2 72 255 2 300 20 54 0 179 3 225 86 6 36 179 3 225 173 2 72 240 7 250 23 6 202 9 250 86 6 36 205 3 250 173 2 72 270 2 300...

Страница 25: ...6 36 198 7 225 173 2 72 225 7 250 23 6 222 3 250 86 6 36 222 3 250 173 2 72 255 2 300 20 54 0 213 7 250 86 6 36 213 7 250 173 2 72 240 7 250 23 6 237 3 250 86 6 36 237 3 250 173 2 72 270 2 300 25 68 0...

Страница 26: ...243 8 250 173 2 72 243 8 250 23 6 267 4 300 86 6 36 267 4 300 173 2 72 270 2 300 25 68 261 3 300 86 6 36 261 3 300 173 2 72 261 3 300 23 6 284 9 350 86 6 36 284 9 350 173 2 72 287 7 350 30 80 276 3 35...

Страница 27: ...44 8 400 35 4 335 6 400 129 9 54 335 6 400 259 8 108 389 1 400 30 80 315 2 350 129 9 54 315 2 350 259 8 108 359 8 400 35 4 350 6 400 129 9 54 350 6 400 259 8 108 404 1 450 40 104 345 2 400 129 9 54 34...

Страница 28: ...ttings as follows Settings may be changed slightly to provide a greater degree of comfort for a particular installation SPT Space Temperature Sensor For constant volume ap plications the ComfortLink c...

Страница 29: ...f power to the control box 2 Cut the CCN wire and strip the ends of the red white ground and black conductors If a different net work color scheme is used substitute appropriate colors 3 Remove the 3...

Страница 30: ...onnected to TB6 terminals 1 and 2 Note that the controls also support integrated economizer changeover using outdoor dry bulb differential dry bulb out door enthalpy and differential enthalpy See Fig...

Страница 31: ...Economizer Control Board EDT Evaporator Discharge Sensor EMM Energy Management Board FIOP Factory Installed Option GND Ground HC Heat Contactor HGBP Hot Gas Bypass HIR Heat Interlock Relay HPS High Pr...

Страница 32: ...32 CONTROLS OPTION BOARD Fig 19 Small Chassis Component Location Size 020 035 Units...

Страница 33: ...33 CONTROLS OPTION BOARD Fig 20 Large Chassis Component Locations Size 040 060 Units...

Страница 34: ...34 Fig 21 Typical Main Control Box Wiring Schematic TO NEXT PAGE TO NEXT PAGE...

Страница 35: ...35 FROM PREVIOUS PAGE FROM PREVIOUS PAGE Fig 21 Typical Main Control Box Wiring Schematic cont...

Страница 36: ...36 TO NEXT PAGE TO NEXT PAGE Fig 22 Auxiliary Control Box Wiring Schematic...

Страница 37: ...37 FROM PREVIOUS PAGE FROM PREVIOUS PAGE FROM PREVIOUS PAGE Fig 22 Auxiliary Control Box Wiring Schematic cont...

Страница 38: ...38 Fig 23 Typical Power Schematic Size 060 Unit Shown...

Страница 39: ...39 Fig 23 Typical Power Schematic Size 060 Unit Shown cont...

Страница 40: ...40 Fig 24 Controls Option Wiring Schematic...

Страница 41: ...41 Fig 25 Electric Heat Control Circuit Size 060 Unit Shown...

Страница 42: ...p to overhang 1 8 in past the end opposite the mounting flange See Fig 26 2 Assemble hood sides top and cross member with gasketed screws provided See Fig 27 3 Attach 15 green speed clips provided to...

Страница 43: ...filters are installed with the airflow in the correct direction NOTE Tabs from both filter tracks will be in the same space After one filter track has been inserted into hood side bend the tabs so th...

Страница 44: ...4 50AJ AK AW AY020 050 units or 6 50AJ AK AW AY060 units power exhaust blowers and motors or 4 50AJ AK AW AY020 050 units or 6 50AJ AK AW AY060 units barometric relief dampers MOUNTING ANGLE WITHOUT T...

Страница 45: ...to route tubing The low pressure tap is factory routed to the atmosphere For a positive pressure building route the high tap to building air and low tap to atmosphere For a negative pressure building...

Страница 46: ...020 050 units There are 3 panels on 50AJ AK060 and units These openings are normally used for power exhaust or barometric relief 3 Run the return air ductwork up to the openings One single duct is rec...

Страница 47: ......

Страница 48: ...ntinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00075 Printed in U S A Form 50A 1SI Pg 48 8 03A 7 03 Replaces New Book 1 T...

Отзывы: