Carrier 48/50Z030-105 Скачать руководство пользователя страница 3

3

8. Insert tube end plug into sampling tube and slide sam-

pling tube into bottom hole of smoke detector.

9. Remove the unit side panel at the return end of the unit

(downshot units only). Save screws for use later.

10. Mount the sampling tube support bracket to the cross

member with two 

1

/

AB-14 

5

/

8

-in. screws as shown in

Fig. 4. Insert snap bushing into hole in bracket.

11. Slide sampling tube into bracket, making sure that the

sampling holes point in the opposite direction of the re-
turn air flow. Insert the sampling tube all the way into the
smoke detector.

12. Return to the auxiliary control box and secure sampling

tube to smoke detector with two no. 6 self-tapping
screws.

13. Attach smoke detector to partition using two, 8-18 

3

/

4

-in.

pan head screws. See Fig. 4.

14. Return to side panel and insert tube end plug into

sampling tube.

15. Replace the unit side panel.
16. Return to auxiliary control box section and insert sam-

pling tube filters into both sampling tube holders. (See
Fig. 1.)

17. Connect harness PL13 as shown in Fig. 3.
18. Restore power to the unit.
19. Configure  ComfortLink™ controller as specified in

Controls and Troubleshooting Guide.

20. Perform Standby, Alarm, and Sensitivity Tests on page 6.

At a minimum, the Magnet test should be performed to
verify smoke detector wiring.

21. Replace smoke detector cover.
22. Check for alarms. Correct any problems.
23. Close and secure auxiliary control box door.

48/50Z Units — 

The return air smoke detector is to be

installed on the upright in the power exhaust section. See
Fig. 5-10.
NOTE: For size 075-105 units with return fan option, the
smoke detector should be installed in the return duct. Do not
use the bracket provided in this accessory kit.

1. Open the power exhaust section doors/panels on both

sides of the unit to gain access.

2. Find plug 13 in the power exhaust section.
3. Remove cover from smoke detector. The screws will re-

main captured in the cover.

4. Place foam gaskets over each sampling tube on smoke

detector. See Fig. 1.

5. Remove one knockout from top of smoke detector.
6. Insert stripped ends of wire harness through knockout and

wire to smoke detector as shown in Fig. 3. Use ground
screw in the smoke detector to secure a wire tie. Use wire
tie to provide strain relief for the wire harness.

7. Mount the smoke detector bracket 50ZZ500420 on the

upright. 
See Fig. 5 for size 030-050 units without economizer.
See Fig. 6 for size 030-050 units with economizer only
option.
See Fig. 7 for size 030-050 units with economizer and
power exhaust option.
See Fig. 8 for size 055-105 units without economizer.
See Fig. 9 for size 055-105 units with economizer only
option.
See Fig. 10 for size 055-105 units with economizer and
power exhaust option.

8. Slide smoke detector into holes in bracket. Do not secure

at this time.

9. Insert tube end plug into sampling tube and slide

sampling tube into bottom hole of smoke detector.

10. Mount the sampling tube bracket to the bottom of the

power exhaust section using two 

1

/

4

 AB-14-

5

/

8

-in. screws.

For size 030-050 units with power exhaust, use bracket
50ZZ500431 as shown on Fig. 7. For all other units
use bracket 50ZZ500421, as shown on Fig. 5 and 6 for
size 030-050 units, Fig. 8-10 for size 055-105 units.

Do not overtighten the screws. Damage to smoke detector
may result.

GROUND
SCREW

SMOKE
DETECTOR

PL13

SAMPLING
TUBE 
FILTERS

WIRE HARNESS

Fig. 3 — Smoke Detector Wiring Connections

SMOKE
DETECTOR

WIRE
HARNESS

SAMPLING
TUBE
SUPPORT
BRACKET

SAMPLING
TUBE

Fig. 4 — Smoke Detector Installed (48/50A020-060)

Содержание 48/50Z030-105

Страница 1: ...y trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and...

Страница 2: ...ugh knockout and wire to smoke detector as shown in Fig 3 Use ground screw in the smoke detector to secure a wire tie Use wire tie to provide strain relief for the wire harness 7 Slide smoke detector...

Страница 3: ...ot use the bracket provided in this accessory kit 1 Open the power exhaust section doors panels on both sides of the unit to gain access 2 Find plug 13 in the power exhaust section 3 Remove cover from...

Страница 4: ...r 48 50Z030 050 Economizer Only Fig 7 Smoke Detector for 48 50Z030 050 Economizer with Power Exhaust SAMPLING TUBE BRACKET SMOKE DETECTOR SAMPLING TUBE BRACKET SMOKE DETECTOR SAMPLING TUBE BRACKET SMO...

Страница 5: ...d air nozzle to remove dust then reinstall the filters PHOTO DETECTOR BOARD 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Va...

Страница 6: ...ing green LED The LED should flash approximately every 10 seconds Trouble If the detector LED does not flash then the detec tor lacks power the detector board is missing replace the cover has been mis...

Страница 7: ......

Страница 8: ...tinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80157 Printed in U S A Form 48 50A 5SI Pg 8 9 03 Replaces New Book 1 1 Tab...

Отзывы: