INSTALLATION

Check Package Contents — 

Remove accessory pack-

aging and inspect shipment for damage. If any damage is
found, file a claim with the shipping agent immediately. If any
item is missing or any part does not assemble properly, notify
your Carrier distributor. 

Table 1 lists the accessory package contents. Figure 1 shows

the smoke detector.

Table 1 — Accessory Package Contents — Return 

Air Smoke Detector (CRSMKDET002C00)

Return Air Smoke Detector Installation

NOTE: For horizontal applications it is easiest to install the
smoke detector prior to making duct connections.

48/50A Units — 

The return air smoke detector is to be

installed in the predrilled holes located in the indoor section
above the auxiliary control box.

1. Open the hinged auxiliary control box access door and

secure.

2. Find the 2 plugs located in the partition above the control

box, remove and discard. See Fig. 2.

3. Remove cover from smoke detector. The screws will

remain captured in the cover.

4. Place foam gaskets over each sampling tube on smoke

detector. See Fig. 1.

5. Remove one knockout from top of smoke detector.
6. Insert stripped ends of wire harness through knockout and

wire to smoke detector as shown in Fig. 3. Use ground
screw in the smoke detector to secure a wire tie. Use wire
tie to provide strain relief for the wire harness.

7. Slide smoke detector into holes in partition. Do not secure

at this time.

When installing the smoke detector in the unit, follow all
local codes. Damage to unit may result.

ITEM

QUANTITY

Smoke Detector with Cover

1

Sampling Tube (long)

1

Sampling Tube Filters

2

Test Magnet

1

Foam Gaskets

2

Screw, no. 6 Self Tapping

2

Tube End Plug (large)

1

Sampling Tube Support Bracket

1

Screw, 8-18 

3

/

4

-in. Pan Head

2

Screw, 

1

/

AB-14 

5

/

8

-in.

2

Snap Bushing

1

Harness Assembly

1

Smoke detector bracket 50ZZ500420

1

Sampling tube bracket 50ZZ500421 

1

Sampling tube bracket 50ZZ500431 

(48/50Z030-050 with Power Exhaust)

1

Prior to installation of this accessory, make sure all power
is disconnected to the unit and locked out. Failure to dis-
connect power supply prior to servicing may result in seri-
ous injury.

FOAM

GASKETS

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

POWER BOARD

COVER MOUNTING

SCREWS

FILTERS

SAMPLING TUBE

DETECTOR BOARD

DETECTOR COVER

PLASTIC
SAMPLING TUBE

PLASTIC SAMPLING TUBE
SELF-TAPPING SCREW

PHOTO

Fig. 1 — Smoke Detector

SMOKE DETECTOR
MOUNTING  PLUGS

PARTITION

PL13

AUXILIARY 
CONTROL PANEL

Fig. 2 — Smoke Detector Mounting Location for 

48/50A020-060

Содержание 48/50Z030-105

Страница 1: ...y trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and...

Страница 2: ...ugh knockout and wire to smoke detector as shown in Fig 3 Use ground screw in the smoke detector to secure a wire tie Use wire tie to provide strain relief for the wire harness 7 Slide smoke detector...

Страница 3: ...ot use the bracket provided in this accessory kit 1 Open the power exhaust section doors panels on both sides of the unit to gain access 2 Find plug 13 in the power exhaust section 3 Remove cover from...

Страница 4: ...r 48 50Z030 050 Economizer Only Fig 7 Smoke Detector for 48 50Z030 050 Economizer with Power Exhaust SAMPLING TUBE BRACKET SMOKE DETECTOR SAMPLING TUBE BRACKET SMOKE DETECTOR SAMPLING TUBE BRACKET SMO...

Страница 5: ...d air nozzle to remove dust then reinstall the filters PHOTO DETECTOR BOARD 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Va...

Страница 6: ...ing green LED The LED should flash approximately every 10 seconds Trouble If the detector LED does not flash then the detec tor lacks power the detector board is missing replace the cover has been mis...

Страница 7: ......

Страница 8: ...tinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80157 Printed in U S A Form 48 50A 5SI Pg 8 9 03 Replaces New Book 1 1 Tab...

Отзывы: