2 - INSTALLATION
2.10 - Condensation discharge
The condensation discharge network must be suitably sized (minimum inside pipe diameter 16 mm) and the pipeline positioned so
that it keeps a constant inclination, never less than 1%. In the vertical installation, the discharge pipe is connected directly to the
discharge tray, positioned at the bottom of the side shoulder underneath the hydraulic fixtures. In a horizontal installation the discharge
tube is connected to the one already present on the machine.
For installation of the 42SIC versions in a horizontal position, horizontal condensation collection basin
accessory kits are available GB0520/GB0524.
-
If possible, make the condensation liquid flow directly in a gutter or a “rainwater” discharge.
-
When discharging directly into the main drains, it is advisable to make a siphon to prevent bad smells returning up the pipe towards
the room. The curve of the siphon must be lower than the condensation collection bowl.
-
If the condensation needs to be discharged into a container, it must be open to the atmosphere and the tube must not be immerged
in water to avoid problems of adhesiveness and counter-pressure that would interfere with the normal outflow.
-
If there is a height difference that could interfere with the outflow of the condensation, a pump must be mounted:
-
in a vertical installation mount the pump under the lateral drainage tray;
-
in a horizontal installation the pump position must be decided according to the specific requirements.
Such pumps are commonly found in commerce.
However, on completion of the installation it is advisable to check the correct outflow of the condensation liquid by slowly pouring about
½ l of water into the collection tray in about 5-10 minutes.
Mounting the condensation discharge pipe in the vertical version
Connect to the condensation collection tray discharge union a pipe for the outflow of the liquid blocking it adequately. Check that the
drip-collector extension is present and correctly installed.
C
ø14mm
B
D
B
discharge fitting
C
tube for the outflow of the liquid
D
extension drip
Mounting the condensation discharge pipe in the horizontal version (42SIC, 42SIN)
To mount the horizontal bowl on the 42SIC versions refer to the instructions in kits GB0520/GB0524.
-
check that the “L” pipe and the flexible rubber hose are correctly connected to the bowl.
-
slide in the side of the machine keeping the pipe in position up against the front grill.
-
fully close the side checking that the pipe remains blocked in the special grove on the side.