Содержание 42PHQ007

Страница 1: ...42PHW 42PHQ 42PHQ K INSTALLATION MANUAL...

Страница 2: ...learances 3 Material supplied 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 Check 9 Electrical connection 10 11 Operating test 12 Address switch 12 Guide for the...

Страница 3: ...and delay type fuses refer to the outdoor unit installation instructions Mod 42PHW 42PHQ007 42PHW 42PHQ009 012 014 42PHW 42PHQ 018 024 42PHQ007K 42PHQ009K 012K 014K 42PHQ018K 024K A mm 790 790 1080 B...

Страница 4: ...F or higher Electrical connecting cable Cable type A07 RN F synthetic rubber insulation with Neoprene coating between indoor and outdoor unit according to EN IEC 60335 2 40 and HD277 S1 standards Tabl...

Страница 5: ...stem consisting of two units manufactured by Carrier Consult the factory or a qualified system engineer prior to connecting this unit to any other manufacturer s outdoor unit Coupling units which have...

Страница 6: ...will cause condensate dripping Flattening or kinking the refrigerant pipes or condensate pipes Excessive height difference between outdoor and indoor units see installation manual of outdoor unit Unn...

Страница 7: ...ging bracket so that it is level Use a plumb line if necessary Be sure to leave the clearance spaces Refer to page 3 If the wall hanging bracket is not level water may drip onto the floor Install the...

Страница 8: ...ch as a screwdriver set between the middle area of the body and bottom right of the wall hanging bracket Connecting the pipe can be done more easily if the unit is inclined Fix the bottom part of the...

Страница 9: ...ttings will damage the tube flaring and cause gas leaks Tubing diameter Torque mm inches Nm 6 35 1 4 18 9 52 3 8 42 12 70 1 2 55 15 87 5 8 65 Once all connections have been completed check for leaks b...

Страница 10: ...of additional screws After installation if there is a significant gap between the unit and wall it can be adjusted by securing the body to the wall hanging bracket using 2 screws Screw holes can be on...

Страница 11: ...ects all poles with contact gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type or higher with synthetic rubber insulation with Neoprene coating according to EN 60335 2...

Страница 12: ...unit Main switch Time delay fuse or circuit breaker see outdoor unit installation manual Heat pump 42PHQ007 007K 009 009K Heat pump 42PHQ012 012K 014 014K Heat pump 42PHQ 018 018K 024 024K R C Y W2 S...

Страница 13: ...t operation The swing motor will operate when the indoor fan is operated Operate the unit in accordance with the Owner s Manual and check the following a Indoor unit Do all switches operate normally D...

Страница 14: ...tted value Example 1 Step Enter configuration mode Press MODE and FLAP buttons together for 7 seconds 2 Step Unit configuration Display CFG Default Value HP Available Value HP Heat Pump AC Cool Only 3...

Страница 15: ...9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 14487 November 2001 Supersedes Order No new Printed in Kore...