7.3 Checks in plug-fans (optional)

-  Electronic plug-fans with variable speed and fl ow sensor that 

can be incorporated in supply (models 90 to 360) and return 
(models 420 to 600).

-  The coupling of characteristic curves of the fan and the room 

is very important, so that the fl ows and pressures provided to 
the duct network are as required.

-  The variable-speed plug-fans have a fl ow control pressostat. 

This  pressostat  comes  from  the  factory  adjusted  to  the 
indicated fl ow.

-  It is possible to readjust the fl ow for diff erent conditions, on 

site, by means of the on the pGD1 terminal (see the specifi c 
brochure of the CARRIERrtc control, mandatory with this type 
of fans).

Motor output up to 15 kW

Motor greater than 15 kW

7 - CHECKING BEFORE COMMISSIONING

For  motors  up  to  15kW  it  is  installed  in  the  factory  in  the 
auxiliary electric panel. For larger motors it is installed next 
to the ventilation group.

Pulley and belt calibration 

Belt tension:

After fi xing the pulleys on the same plane, the belt tension is 
made by tightening the tensor screw.

Excessive tension on the belt can lead to premature wear on 
the  assembly.  Insuffi  cient  belt  tension  can  cause  slippage, 
overheating and premature wear of the belt.

Pulleys must stay on the same plane

Tensor
screw

Pulley
screws

Taper pin

The centrifugal motorfans are coupled through pulleys and belts. 
In these fans, the following must be taken into consideration:

Pulley alignment:

● The pulleys must be on the same plane, so it is important to 

check them with the help of a ruler or a laser aligner.

● In case they are not aligned, remove the pulley screws, and 

after removing the taper pin, the set of pulley and taper can 
be slided over the axis (this action can be performed both in 
the motor as well as in the fan).

Attention:

  Before  performing  these  operations,  it  is 

necessary to verify that the unit is disconnected from 
mains.

It  is  essential  to  tension  the  belts  using  the  “Defl ection  test” 
described below:

● The  belt  tension  must  be  checked  and  corrected  using  a 

suitable measuring instrument (tensiometer or dynamometer).

● “Ea” calculation:

-  Ea = (e x E)/100 = deformation in mm for a pulley centre 

distance of 100 mm

-  e = pulley centre distance in mm

-  E = see table below for the value

-  f = force applied

Belt type

f(N) 

d (mm) 

E (mm) 

 

SPZ

25

56 ≤ 71

2.45

< 71 ≤ 90

2.20

< 90 ≤ 125

2.05

125

1.90

Important: 

During  commissioning,  the  belt  tension 

must be checked after 48 hours of operation.

The  belt  tension  must  be  checked  in  all  cases  and 
before system start-up.



Load to be applied per belt f (N)



Small pulley diameter (mm)



Belt deformation for a pulley centre distance of 100 mm - E (mm)

● At the centre of the centre distance “e”, apply a force “f”, as 

determined in the table below, to each belt. Set the belt tension 
to obtain the calculated defl ection “Ea”. 

Содержание 40ZF Series

Страница 1: ...Nominal cooling capacity 20 135 kW Nominal heating capacity 20 145 kW Indoor units INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80259...

Страница 2: ...SSIONING 9 7 1 Electrical connections 9 7 2 Checks in the centrifugal fans 9 7 3 Checks in plug fans optional 10 7 4 Air ducts connections 11 7 5 Condensate drain connection 11 8 SAFETY ELEMENTS 12 9...

Страница 3: ...ak to atmospheric pressure the liquid phase evaporates The resulting vapours are still hazardous because they are heavier than air and can force the latter out of the machine rooms If refrigerant is a...

Страница 4: ...11 I MS221 I R N R N MC111 N E R I R MC011 MC021 N E R R I N N E E MC001 I I 40ZS ZF 420 to 600 assemblies with mixing box raised view N E MC101 R I I I I Designation 1 Rear Return 2 Top 3 Right hand...

Страница 5: ...t causing damage to the units or to workers These slings will be hooked to the two grips screwed on each crossbar in models 420 to 600 Make sure that the unit is protected from contact with the hooks...

Страница 6: ...0 705 1 044 MC0 1 088 1 350 660 1 224 MC1 1 148 1 350 930 1 697 40ZS ZF MS module Centre of gravity mm Weight kg X Y Z 90 100 120 Montajes 111 116 413 314 411 114 113 311 121 126 423 324 421 124 123 3...

Страница 7: ...ade With the help of the crane or the forklift truck the unit will be raised to a su cient height that the silent blocks can be screwed into its base The 4 silent blocks of the corners must remain obl...

Страница 8: ...600 1 300 2 061 40ZS ZF 90 to 360 40ZS ZF 420 to 600 6 3 Anchorage for silent blocks 6 4 Recommended service clearance for unit start up and maintenance operations mm 1000 1000 500 1700 500 1000 A 500...

Страница 9: ...fans Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check the operation conditions pressures ows and consumptions The over...

Страница 10: ...entrifugal motorfans are coupled through pulleys and belts In these fans the following must be taken into consideration Pulley alignment The pulleys must be on the same plane so it is important to che...

Страница 11: ...G Models 90 to 360 These indoor units are equipped with a condensate drain pan with a bronze gas threaded 3 4 M drain junction Condensate drain CONNECT SIPHON METTRE SIPHON PONER SIFON V220014 7 5 Con...

Страница 12: ...nsidered when selecting fans the pressure drop graphs in the options can be seen in the technical brochure 9 1 Mixing box In models 90 to 360 of the 40ZS ZF unit the mixing box is a separate module Th...

Страница 13: ...imensions mm A B C 90 100 120 1 supply outlet 6 9 1 row 150 482 443 12 2 rows 262 482 443 160 180 1 supply outlet 12 15 18 1 row 189 1 142 443 182 200 240 2 supply outlet 15 18 1 row 189 1 142 443 24...

Страница 14: ...to connect the hose to the electric power supply If it is not possible to perform the previous step the distance between holes as well as the frame dimensions are displayed in the following schemes S...

Страница 15: ...se frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the four M4 screws included in the kit The height of the frame on the support will de...

Страница 16: ...l in the technical brochure of this series Water outlet Water inlet Models 40ZS ZF 90 to 360 Recomendations Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Страница 17: ...re assembled over a sheet steel pro le Models 40ZS ZF 90 to 360 Modelos 40ZS ZF 420 to 600 Opacimetric filters Gravimetric filters Sheet profile Tab for displacement of gravimetric filters Tab for dis...

Страница 18: ...oise we recommend the use of noise dampening headgear Caution Before intervening in the unit cut o main power 10 1 General recommendations Do not lean on the unit A platform must be used to work on a...

Страница 19: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Страница 20: ...Order No 10259 12 2020 Supersedes order No 07 2019 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Отзывы: