Test Run & Fault Code
• Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V
mega-ohm meter and check if the resistance is above 1MO. Do not operate if it is below 1MO.
• Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To
protect the compressor on startup, power it on for 12 hours prior to the operation. Check if the
installations of the drainpipe and connection line are correct. The drainpipe should be placed lower
while the connection line should be placed lower. Heat preservation measures should be taken
such as wrapping the drainpipe esp. in the indoor units with heat insulating materials.
The drain pipe should be fixed in a slope to avoid protrusions at the upper end and concaving at
the lower end.
Checkup of Installation
Do ask the installation personnel to make a test run. Follow testing procedures according to the manual and check if
the temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be taken to initiative a
forced run. This function is not provided with remote control.
• Set the wired controller to refrigerating/heating mode, press “ON/OFF” button for 5 seconds to enter
into the compulsive refrigerating/heating mode. Press again, the “ON/OFF” button to quit the compulsive
running and stop the operation of the air conditioner.
When any fault appears, consult the fault code of line control or the flashing time for LED5 of computer panel of
indoor units/health lamp of receiving window of remote control and find out the faults as shown in the following
table to remove all faults.
Indoor Unit Faults
Before Test Run
Ways of Test Run
Fault Remedies
check if the mains voltage is correct
check for leakage at the piping joints
check if the connections of mains power
and indoor & outdoor units are correct
check if the serial numbers of the
terminals matching
check if the installation place meets the specifications
check if there is too much noise
check if the connecting line is fastened
check if the connectors for tubing are heat insulated
check if the water is draining outside properly
check if the indoor units are positioned correctly
Failure code at
wired controller
PCB LED5 (Indoor Units)/
Receiver Timer Lamp
(Remote Controller)
Fault Descriptions
01
1
Fault of indoor unit ambient temp. transducer TA
02
2
Fault of indoor unit pipe temp. transducer TC1
03
3
Fault of indoor unit pipe temp. transducer TC2
04
4
Fault of indoor unit dual heat source temp. tranducer
05
5
Fault of indoor unit EEPROM
06
6
Fault of communication between indoor & outdoor units
07
7
Fault of communication between indoor unit and wired control
08
8
Fault of indoor unit float switch
09
9
Fault of duplicate indoor unit address
12
12
Fault of indoor unit 50Hz Zero-crossing
13
13
DC motor match (AD*MQERA)
14
14
fault of indoor unit DC motor
16
16
DC motor communication (AD*MQERA)
18
18
BS valve box or 4WV switch failure
20
20
Corresponding faults of outdoor units
22
ENGLISH
Содержание 40VU007-054H-7S-QEE
Страница 8: ...Parts and Function Indoor unit air outlet port air inlet port air duct soft connection 1...
Страница 31: ...The manufacturer reserves the right to change any product specifications without notice...
Страница 57: ...Il produttore si riserva il diritto di modificare qualsiasi specifica del prodotto senza preavviso...
Страница 85: ...Teile und Funktionen Innenger t Luftauslass ffnung Lufteinlass ffnung Luftkanal Weiche Verbindung 1...
Страница 108: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...
Страница 134: ...El fabricante se reserva el derecho de cambiar cualesquiera especificaciones de producto sin previo aviso...
Страница 137: ...Parts and Function Unidade de interior porta de sa da do ar porta de entrada do ar Duto de ventila o conex o suave 1...
Страница 160: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...