13
Fig. 15 —Wireless Remote Controller
(40VM900001)
Use a tool to press and hold the LOCK button for at least ten
seconds. Press to activate. Click or to select an
address and press to send the setting.
To display an indoor unit address, use a tool to press and hold
the LOCK button for at least ten seconds, and press to
query the addresses.
Non-Programmable Controller
When setting an address, connect only one wired controller to
an indoor unit.
Press
ROOM TEMP
and
SWING
simultaneously for three
seconds. If there is no address for this indoor unit, the display
shows
FE# 00
as shown in Fig. 16. Otherwise, the display
shows the current address of the indoor unit.
Click
TEMP. UP
or
TEMP. DOWN
to change 00 to the
desired address as shown in Fig. 17. Press
OK
to confirm and
exit the setting interface.
Programmable Controller
When setting an address, connect only one wired controller to
an indoor unit.
1. Access parameter settings as shown in Fig. 18.
Fig. 18 —Programmable Controller IDU
Addressing Menu
2. Press
TEMP. UP
or
TEMP. DOWN
to move the cursor
down and choose IDU ADDRESSING, and select
MENU/OK
to access this setting.
RESET
TIMER ON
TIMER OFF
SWING
AIR DIRECTION
CLOCK
OK
SWING
MODE
FAN
AUTO
COOL
DRY
HEAT
FAN
TEMP
SET
CLOCK
SET
HOUR
FAN SPEED
LOCK C/H
6 – AIR DIRECTION
4 – ADJU S T UP
2 – FAN S PEED S ETTING
9 – CLOCK S ETTING
14 – OK (CONFIRM)
10 – TIMER ON
11 – TIMER OFF
1 – MODE S ETTING
3 – ADJU S T DOWN
12 – RE S ET
13 – LOCK
15 – COOL/HEAT
5 – ON/OFF
7 – AIR VERT.
S WING
8 – AIR HORIZ.
S WING
MODE
FAN
TEMP. DOWN
OK
TEMP. UP
ON/OFF
TIMER
ROOM TEMP.
SWING
#
Fig. 16 — Non-Programmable Controller IDU
Addressing Menu
#
MODE
FAN
TEMP. DOWN
TEMP. UP
OK
ON/OFF
TIMER
ROOM TEMP.
SWING
Fig. 17 — Non-Programmable Controller Setting
IDU Address
MODE
FAN
MENU
TEMP. DOWN
OK
TEMP. UP
BACK
ON/OFF